6
GB
PLEASE PHONE US TO REGISTER YOUR APPLIANCE AND ACTIVATE YOUR PARTS GUARANTEE ON 08448 24 24 24
Installation
SPACE FOR FIXING
The cooker can be close fitted below hotplate level.
This requires a minimum distance of 600mm between
cupboard units of hotplate height.
When installing next to a tall cupboard, partition or wall,
for a minimum distance of 400mm above hotplate level,
allow a side clearance of at least 65mm. The diagram
below illustrates the minimum clearance between the
cooker and adjacent walls, cupboards etc.
The wall behind the cooker, 50mm below and 450mm
above, and the width of the cooker, must be a non-
combustible material such as ceramic wall tiles.
If the cooker is to be fitted close to a corner on the left
hand side, ensure that there is a clearance of at least
50mm to allow the main oven door to open fully for
when removing oven shelves.
65 mm Min
840 mm Min
400 mm Min
600 mm Min
750mm Min
COOKER HOODS
If a cooker hood is to be installed, refer to the cooker
hood manufacturers’ instructions regarding fixing
height.
UNPACKING THE COOKER
Unpack the components from inside the grill and oven.
Check that the following parts are present:
Grill pan and grid
Top oven/grill shelf heat
shield
Pan supports
Main oven shelves (2)
Enamelled burner caps (4) Top oven/grill shelf (1)
Aluminium burner bodies(4) Literature
LOCATION
The cooker may be located in a kitchen, kitchen/diner
or a bed-sitting room, but not in a room containing a
bath or shower. The cooker must not be installed in a
bed-sitting room of less than 20m
3
.
When adjusted for use on Butane (G30) or Propane
(G31), the cooker must not be installed in a room or
internal space below ground level, e.g. in a basement.
PROVISION FOR VENTILATION
The room containing the cooker should have an air
supply in accordance with BS 5440: Part 2.
The room must have an opening window or equivalent;
some rooms may also require a permanent vent. If the
room has a volume between 5 and 10m
3
, it will require
an air vent of 50cm
2
effective area unless it has a
door which opens directly to outside. If the room has
a volume of less than 5m
3
, it will require an air vent of
100cm
2
effective area. If there are other fuel burning
appliances in the same room, BS 5440: Part 2 should
be consulted to determine air vent requirements.
TECHNICAL DATA
Gas connection
Rp ½ (½” BSP female)
Pressure test point
Front left hotplate
injector
Gas rate adjustment
None
Aeration adjustment
None
Electrical connection
Flexible cord fitted with a
3
pin
13
amp
plug
230/240V
a.c.
50Hz.
13A
fuse.
a)The cooker may be located in a kitchen, a kitchen/
diner or bed sitting room, but not in a bathroom or
shower room.
b)The hoods must be installed according to the
requirements in the hood handbook.
c)The wall in contact with the back of the cooker must
be of flameproof material.
d)The cooker is fitted with a safety chain that must be
attached to a hook, secured to the wall behind the
appliance.
!Some models can have their
gas connection inverted. It is
important to make sure the safety
chain is always situated on the
side which corresponds to the
hose holder (Fig. B).