C. Defrost

This unit uses an off-cycle defrost. When a sensor in the evaporator coil reaches the 
initiation setpoint, the unit enters defrost. When the sensor reaches the termination 
setpoint, the unit ends defrost.
Units with a control board of revision level R23 or later (board revision level can be seen 
on display at power up) also feature an adjustable time-initiated defrost along with the 
normal temperature-initiated defrost.
The time-initiated defrost is factory set for normal conditions. Before changing this 
setting, contact the HOSHIZAKI Technical Support Department for recommendations. If 
necessary, adjust the time-initiated defrost frequency as follows:

1) Press and hold the up/down arrows simultaneously for 3 seconds. Press "ENTER" until 

the dF frequency is displayed.

2) To change the time-initiated defrost frequency, press the up/down arrows until the 

desired value is displayed. The defrost frequency is adjustable between 0 and 12 
defrosts per 24 hours. The factory default is 6.

3) Press "ENTER" to set the value and view the next setting. If no change in the value is 

desired, press "ENTER" and the unit will return to normal display mode. 

Important Note:

 For the change to take effect, you must cycle through the menu until 

you return to the normal display.

Note: The change in the defrost setting will take effect after the next defrost based on 

the previous setting. If it is desired that this change in interval timing take effect 
immediately, turn the unit off and back on. The next time-initiated defrost will take 
effect "x" hours after power is resupplied. For example, if the setting is dF 6, x=4 
and the next defrost will take place 4 hours from the time that power is applied.

D. Temperature Display Scale (°F or °C)

To change the display scale, follow the steps below.

1) Press and hold the up/down arrows simultaneously for 3 seconds. Press "ENTER" until 

the F or C temperature display scale is displayed.

2) To change the temperature display, press the up/down arrows until the desired scale is 

displayed. The factory default is F.

3) Press "ENTER" to set the value and return to normal display mode. 

Important Note:

 For the change to take effect, you must return to the normal display.

E. Perimeter Frame Heater

This unit is equipped with a perimeter frame heater. This prevents the formation of 
condensate on the front frame of the unit under high humidity conditions. If operating the 
unit under conditions where condensate will not form, these heaters may be turned off 
using the switch on the control box.

Содержание TempGuard PTR1SSB Series

Страница 1: ...Hoshizaki A Superior Degree of Reliability www hoshizaki com Models PTR1SSB xxxx TempGuard Pass Thru Refrigerator Hoshizaki America Inc Issued 9 19 2002 Revised 10 30 2006 INSTRUCTION MANUAL...

Страница 2: ...tenance and service of the unit Should the reader have any questions or concerns which have not been satisfactorily addressed please call write or send an e mail message to the HOSHIZAKI Technical Sup...

Страница 3: ...lation Instructions 6 A Location 6 B Checks Before Installation 6 C How to Open the Front Panel 7 D Setup 7 E Electrical Connection 7 F Door Reversing Stainless Steel Doors Only 7 G Final Checklist 8...

Страница 4: ...to make speci cation and design changes without prior notice MODEL NAME PTR1SSB xxxx SERIAL NUMBER AC SUPPLY VOLTAGE 115 60 1 AMPERES 12 0 DESIGN PRESSURE HI PSI 450 DESIGN PRESSURE LO PSI 250 REFRIG...

Страница 5: ...elf Space Depth with Doors Open 674 l 23 8 ft3 1 26 m2 13 6 ft2 Glass on both sides 2 146 2 mm 84 7 in Glass on one side and solid on the other 2 161 6 mm 85 3 in Solid on both sides 2 177 mm 85 9 in...

Страница 6: ...ions The nameplate is located on the right side wall of the cabinet interior We reserve the right to make speci cation and design changes without prior notice 1 All tape packing material and shipping...

Страница 7: ...lips at the same height E Electrical Connection Cord connected units should only be plugged into a 115 volt 10 60 Hz circuit with a national and local electrical code approved grounded wall receptacle...

Страница 8: ...ches 254 mm overhead clearance for proper ventilation 4 Have all shipping cartons tapes and packing materials been removed from the unit 5 Has the power supply been checked or tested against the namep...

Страница 9: ...value for the average cabinet temperature For example setpoint 36 F compressor on at 39 F compressor off at 33 F If necessary adjust the setpoint temperature as follows 1 Press and hold the up down a...

Страница 10: ...portant Note For the change to take effect you must cycle through the menu until you return to the normal display Note The change in the defrost setting will take effect after the next defrost based o...

Страница 11: ...t cloth Use a damp cloth containing a neutral cleaner to wipe off oil or dirt build up B Maintenance 1 Air Filter Check the lter at least once a month If it is dirty use warm water and a neutral clean...

Страница 12: ...service technician E4 6 beeps every ten seconds High Pressure Alarm Compressor discharge pressure is outside normal operating range Pressure switch has been triggered 3 or more times in 1 hour Press...

Страница 13: ...will reset During alarm press RESET to silence buzzer for 5 minutes CF 1 beep every ten seconds Clogged Filter Alarm Condenser lter needs cleaning Clean lter Allow time for sensor to react then press...

Страница 14: ...14 HOSHIZAKI AMERICA INC 618 Hwy 74 S Peachtree City GA 30269 USA TEL 770 487 2331 FAX 770 487 3360 www hoshizaki com 91A3GA10B...

Отзывы: