10. REMOVAL AND REPLACEMENT OF CONDENSING PRESSURE
REGULATOR (C.P.R.) - REMOTE AIR-COOLED MODEL ONLY
IMPORTANT
Always install a new Drier every time the sealed refrigeration system is
opened. Do not replace the Drier until after all other repair or replacement
has been made.
1) Turn off the power supply.
2) Remove the panels from the remote condenser unit.
3) Recover the refrigerant and store it in an approved container.
4) Before heating, break off the stub on the dome to release the dome charge.
5) Disconnect the C.P.R. using brazing equipment.
6) Install the new C.P.R. Use nitrogen gas at the pressure of 3-4 PSIG when brazing
the C.P.R.
WARNING
Always protect the C.P.R. body by using a damp cloth to prevent the
C.P.R. from overheating. Do not braze with the C.P.R. body exceeding
250° F.
7) Install the new Drier in the icemaker.
8) Check for leaks using nitrogen gas (140 PSIG) and soap bubbles.
9) Evacuate the system and charge it with refrigerant. See the Charge Label in the
machine compartment in the icemaker.
10) Replace the panels in their correct positions.
11) Turn on the power supply.
Содержание KM-630MAF
Страница 6: ...6 2 KM 630MWF We reserve the right to make changes in specifications and design without prior notice ...
Страница 7: ...7 3 KM 630MRF We reserve the right to make changes in specifications and design without prior notice ...
Страница 11: ...11 b KM 630MWF ...
Страница 12: ...12 c KM 630MRF ...
Страница 25: ...25 III TECHNICAL INFORMATION 1 WATER CIRCUIT AND REFRIGERANT CIRCUIT a KM 630MAF ...
Страница 26: ...26 b KM 630MWF ...
Страница 27: ...27 c KM 630MRF ...
Страница 28: ...28 2 WIRING DIAGRAMS a KM 630MAF and KM 630MWF Note Pressure Switch Cut out 412 PSIG Cut in 327 21 PSIG 21 0 ...
Страница 29: ...29 b KM 630MRF U1GMA0179608 Note Pressure Switch Cut out 412 PSIG Cut in 327 21 PSIG 21 0 ...