28
Min. 24" (61 cm) Clearance
Air
Air
Icemaker
Remote
Condenser
Unit
Service Loop
Max.
33'
(10 m)
Remote
Condenser
Unit
Max.
10'
(3 m)
Icemaker
Service Loop
G. Installation of Remote Condenser Unit
WARNING
• Installation of remote condenser unit must be performed by properly trained and
EPA-certified service personnel.
• The remote condenser unit must be installed in accordance with applicable
national, state, and local codes and regulations.
• Failure to install the remote condenser unit within these guidelines may adversely
affect safety, performance, component life, and warranty coverage.
• Power supply and ground wire to the remote condenser unit are supplied from the
icemaker. For details, see section "II.G.6. Electrical Connection."
1. Location
NOTICE
• The remote condenser unit is intended for outdoor use. Normal operating ambient
temperature must be within -20°F to +122°F (-29°C to +50°C). Operation of the
remote condenser unit, for extended periods, outside of this normal temperature
range may affect appliance performance.
• The maximum line length for the standard line sizes and refrigerant charge is
66' (20 m). With larger line sizes and/or additional refrigerant, the maximum line
length is 100' (30.5 m). For details, see "II.G.4 Line Set Size and Refrigerant
Charge."
• The maximum vertical distance between the remote condenser unit and the
icemaker is 33' (10 m) above or 10' (3 m) below the icemaker. These distances
are measured fitting to fitting. See Fig. 11.
The remote condenser unit must be positioned in a permanent site under the following
guidelines:
• A firm and flat site.
• A dry and well ventilated area with 24" (61 cm) clearance at front and rear for proper air
circulation and ease of maintenance and/or service should they be required. See Fig. 12.
Fig. 11
Fig. 12