26
Control Board (CB) Setting Menu
Category
No. Item
Range
IM-500SAB
Default
Water
Supply,
continued
12 Freeze Cycle Water Supply Time 1: Partial Drain (CB
Setting 14)
0 to 90 sec.
(1 sec. increments)
30
Freeze Cycle Water Supply Time 1: Full Drain (CB
Setting 14)
60
13 Water Temperature Correction Value
Value added to correct the difference between
the temperature at the evaporator (cube control)
thermistor and actual water supply temperature.
+0 to +20°C
(1°C increments)
11
14 Partial/Full Drain Selection
Controls timing for inlet water valve and pump motor
in the freeze cycle.
Partial Drain: Pump motor energizes after freeze
cycle water supply time 1 (CB Setting 12) timer
terminates. During the first freeze cycle after startup
or following a bin control initiated shutdown and
restart, freeze cycle water supply times 1 and 2 (CB
Settings 12 and 15) are doubled.
Full Drain: Pump motor energizes after freeze cycle
water supply time 1 (CB Setting 12) timer terminates.
If full drain is selected, change freeze cycle making
water supply times 1 and 2 (CB Settings 12 and 15)
to the full drain times listed in this table and move
the water tank drain pipe to the drain position. For
details, see "III.G.2. Ice Clarity."
Partial=1; Full=0
1
15 Freeze Cycle Water Supply Time 2: Partial Drain (CB
Setting 14)
0 to 90 sec.
(1 sec. increments)
22
Freeze Cycle Water Supply Time 2: Full Drain (CB
Setting 14)
44
Other
21 Stackable Bin Control
Allows for stacked units to be controlled through one
bin control.
DO NOT ADJUST
Yes=1; No=0
1
22 Refrigeration Circuit Cycling when Bin Full
DO NOT ADJUST
On=1; Off=0
0
Model
30 Type
0: WC, PS, No CondTherm, Ignore CB Setting 34
1: AC, No PS, No CondTherm, Use CB Setting 34
2: AC, No PS, CondTherm, Use CB Setting 34
3: AC, PS, No CondTherm, Use CB Setting 34
DO NOT ADJUST
0 to 3
3
Harvest
Cycle High
Temperature
Control
34 Harvest Cycle High Temperature Control
Active if type setting (CB Setting 30) is set to 1, 2,
or 3. If control board thermistor temperature at the
beginning of harvest cycle is equal to or greater than
the harvest cycle high temperature control setting,
fan motor operates continuously in harvest cycle.
40 to 70°C
(1°C increments)
48
Water
Regulating
Valve
36 Water Regulating Valve Error Detection Temperature
DO NOT ADJUST
0 to 50°C
0=ignore, air-cooled
model
(1°C increments)
0