34
Error Codes
Error
Code
Problem
Corrective Action/Reset Details
E1
Freeze Cycle Backup Timer
Freeze cycle backup timer (Control Board
Setting 6) has terminated.
50 min. after water tank starts to close in preceding
harvest cycle, unit stops if the evaporator
temperature is above 32°F (0°C).
Check for inlet water valve leaking by, hot gas valve
leaking by, pump motor not pumping, thermostatic
expansion valve not feeding properly, low charge, or
inefficient compressor.
Press the "RESET" button to reset.
E2
Harvest Cycle Backup Timer
Harvest cycle backup timer has terminated.
30 min. after water tank starts to open in harvest
cycle, unit stops if harvest cycle termination
temperature (Control Board Setting 1) has not been
reached.
Check for open thermistor, HGV not opening, TXV
leaking by, low charge, or inefficient compressor.
Press the "RESET" button to reset.
EE
(E3)
Water Tank Opening Backup Timer
3-minute opening backup timer starts when water
tank starts to open.
If actuator motor's internal position sensor does not
indicate water tank is fully open within 3 minutes,
display shows "EE" and unit stops for 60 minutes.
If error recurs after unit resumes operation, display
shows "EE" and unit shuts down.
Check actuator motor and control board.
Press the "RESET" button to reset.
EE
(E4)
Water Tank Closing Backup Timer
50-second closing backup timer starts when water
tank starts to close.
If actuator motor's internal position sensor does not
indicate water tank is fully closed within 50 seconds,
display shows "EE" and unit stops for 60 minutes.
If error recurs after unit resumes operation, display
shows "EE" and unit shuts down.
Check actuator motor and control board.
Press the "RESET" button to reset.
EE
(E5)
High Evaporator Temperature
If evaporator temperature 140°F (60°C) or higher for
5 sec., unit stops.
Check for harvest problem (stuck HGV or control
board relay), hot water entering unit, or shorted
thermistor.
Press the "RESET" button to reset.
EE
(E9)
Condenser Thermistor Error
If condenser thermistor is open or shorted for 2 sec.,
unit stops.
Note: IM-200BAC does not utilize a condenser
thermistor, therefore E9 error will not occur.
Replace condenser thermistor.
EE
(EA)
Control Board Error
If model data IC is defective, unit stops.
Replace control board.
EE
(EC)
Evaporator (Cube Control) Thermistor Error
If evaporator thermistor is open or shorted for
2 sec., unit stops.
Replace evaporator thermistor.
EE
(Ed)
Water Regulating Valve Error
If water regulating valve thermistor detects a
temperature below the water regulating valve error
detection temperature (Control Board Setting 36),
error is displayed but unit continues to operate.
Note: IM-200BAC does not utilize a water regulating
valve, therefore Ed error will not occur.
Check water regulating valve.
Press the "RESET" button to reset.