14
Freeze Termination
: CB monitors time after ET temperature ≤ 32°F (0°C).
CB terminates freeze cycle when the following equation is satisfied:
temp. (absolute value) × time (min.) = (absolute value of CB Setting 2) × (CB Setting 3)
Using default settings, freeze cycle is terminated when:
temp. (absolute value) × time (min.) = 382.5
This formula helps maintain consistent dimple size regardless of differences in
seasonal ambient and water temperatures.
ET temperature is recorded 30 seconds after PM energizes. Water temperature
correction value (CB Setting 13) is added to ET temperature and this is used as WT
value in the following harvest cycle.
If CBT > 32°F (0°C) (CB Setting 74) and CBT ≤ 111°F (44°C) (CB Setting 70), when
ET ≤ -8.5°F (-22.5°C) (CB Setting 2), HGV energizes 10 sec., de-energizes 20
sec., energizes 10 sec. (CB Settings 71 and 72) to reduce bonding of the water pan
assembly to the evaporator.
4)
Harvest Cycle
: Same as the initial harvest cycle. Return to step 2) above.
Note: Appliance continues to cycle until BC is satisfied or power is switched off.
The appliance always restarts at the startup cycle.
2. Shutdown Diagnosis
1)
When BC is engaged (open) for more than 10 sec., if in freeze cycle, the icemaker
shuts down after harvest cycle (water pan assembly open). If in harvest cycle or if BC
is engaged (open) while the water pan assembly is opening after the power supply is
turned on (or after the "RESET" button is pressed), shutdown does not start: Shutdown
occurs 10 sec. after AMPS indicates water pan assembly is fully open (down). When
BC is disengaged (closed) for more than 80 sec., icemaker restarts at startup cycle.
See "II.D.1. Bin Control Check."
Legend:
AMD
–actuator motor down;
AMPS
–actuator motor position sensor;
AMU
–actuator motor up;
BC
–bin control;
CB
–control board;
CBT
–control board
thermistor;
Comp
–compressor;
CS
–control switch;
CR
–compressor relay;
ET
–evaporator thermistor;
FM
–fan motor;
HGV
–hot gas valve;
HPS
–high-pressure
switch;
PM
–pump motor;
WT
–water temperature;
WV
–inlet water valve