12. SERVICE DIAGNOSIS

PROBLEM

POSSIBLE CAUSE

REMEDEY

[1] Showcase will not 

start.

1. Ground fault circuit interrupter in 

OFF position.

1. Turn ON.

2. Unplugged.

2. Plug in.

3. Supply voltage too low.

3. Plug into a separate receptacle of 

115V ± 10%.

4. No power supply to the wall outlet. 

(Breaker or fuse blown out.)

4. Correct.

5. Electrical circuit open or bad 

contacts.

5. Correct.

6. Motor protector tripped.

6. Ventilate and reset fan motor.

[2] Poor cooling 

performance

1. Gas leaks.

1. Repair the leaks and recharge.

2. Fan motor defective.

2. Replace.

3. Condenser and/or air filter clogged. 3. Clean.
4. Condenser air inlet blocked.

4 - 9. Instruct the user on 

characteristics and proper use 
of the showcase.

5. Exposed to direct sunlight.
6. Located next to a high heat 

producing equipment.

7. Doors opened too frequently or left 

open.

8. Packed with foods, or warm or hot 

foods inside.

9. Ambient temperature exceeding 80

°F (27°C).

[3] Dry foods

1. Foods have been stored from the 

previous day.

1 - 2. Instruct the user on 

characteristics and proper use 
of the showcase.

2. Foods have been stored for a long 

time.

[4] Frosting

1. [Exterior] Relative humidity 

exceeding 60%.

1 - 2. Instruct the user on 

characteristics and proper 
use of the showcase. Wipe off 
excessive frost with a soft cloth.

2. [Interior] Doors opened too 

frequently or left open.

Содержание HNC-120BA-L-S

Страница 1: ...NO S041 789 ISSUED OCT 26 2009 REVISED HOSHIZAKI COUNTER SHOWCASE SERVICE MANUAL MODEL HNC 120BA L R S HNC 150BA L R S HNC 180BA L R S HNC 210BA L R S...

Страница 2: ...ce of the product Should the reader have any questions or concerns which have not been satisfactorily addressed please call write or send an e mail message to the Hoshizaki Technical Support Departmen...

Страница 3: ...r reference that may be necessary CONTENTS PAGE 1 SAFETY INSTRUCTIONS 1 2 MODEL NAME 3 3 OPERATING INSTRUCTIONS 4 4 SPECIFICATIONS 5 5 DIMENSIONS 6 a HNC 120BA L S 6 b HNC 120BA R S 7 c HNC 150BA L S...

Страница 4: ...11 CONSTANT PRESSURE EXPANSION VALVE AND REFRIGERANT CHARGE 20 a SPECIFICATIONS 20 b FUNCTION 20 c CONSTRUCTION 20 d REPLACEMENT 21 12 SERVICE DIAGNOSIS 22 ii...

Страница 5: ...be sure to unplug the unit or disconnect the main power supply before servicing the unit to prevent electric shocks 3 If the unit must be energized for inspection of the electric circuit use rubber g...

Страница 6: ...connectors or the like with their closed ends up to avoid entrance of moisture that could lead to electric leaks or re 6 After servicing always use a megohmmeter 500V DC to check for the insulation re...

Страница 7: ...E H NC 120 B A L R S High Grade Exterior S Stainless steel Counter Showcase Unit Location Width cm L Unit on left 120 150 180 210 R Unit on right Development Order HA model Starts from A Unit on right...

Страница 8: ...ay rise resulting in food deterioration 4 Do not pack the showcase with foods The cooling performance may reduce resulting in food deterioration 5 The showcase should not be exposed to direct sunlight...

Страница 9: ...R D04763 L D04764 R D04765 L D04766 R D04767 L D04768 R D04769 REFRIGERATION SYSTEM DEFROST SYSTEM Convection Cooling None Hermetic 130W Model CE56Y 1ZU Fin and Tube Type Cooling Fan Motor x 1 UPPER...

Страница 10: ...6 5 DIMENSIONS a HNC 120BA L S...

Страница 11: ...7 b HNC 120BA R S...

Страница 12: ...8 c HNC 150BA L S...

Страница 13: ...9 d HNC 150BA R S...

Страница 14: ...10 e HNC 180BA L S...

Страница 15: ...11 f HNC 180BA R S...

Страница 16: ...12 g HNC 210BA L S...

Страница 17: ...13 h HNC 210BA R S...

Страница 18: ...14 6 REFRIGERATION CIRCUIT Refrigerant R134a Heat Exchange Condenser Drier Expansion Valve Evaporator Upper Evaporator Lower Fan Motor Compressor...

Страница 19: ...15 7 WIRING DIAGRAM CM Compressor SR Start Relay SC Start Capacitor OL Overload Relay FM Fan Motor ELB Ground Fault Circuit Interrupter Power Supply 1 phase 115V 60Hz BK W BK W BU...

Страница 20: ...16 8 CONSTRUCTION Top Cover Nameplate Joint Hose Front Glass Plug Power Switch Ground Fault Interrupter Condenser Center Frame Air Filter Slider Louver Sliding Glass Door Food Mount...

Страница 21: ...r is hooked and xed on the top frame aluminum 2 Lift up and unhook the rear end of the top cover 3 When the rear part is lifted off move it forward to unhook and remove the front part The top cover is...

Страница 22: ...nd release it from the t f HOLDER EVAPORATOR PIPE Remove the truss head tapping screw 4 x 25 from the bottom of the top frame Take off the center frame Be careful with the evaporator pipe It will be r...

Страница 23: ...the same handy ux that has been used for the current refrigerants However its entrance into the refrigerant circuit should be avoided as much as possible 4 Oil for Processing of Copper Tubing R134a Wh...

Страница 24: ...re may cause R134a to suddenly react with oxygen and explode Be sure to use nitrogen to prevent explosion 11 CONSTANT PRESSURE EXPANSION VALVE AND REFRIGERANT CHARGE a SPECIFICATIONS Model HYP 2 5QHD...

Страница 25: ...r every time the sealed refrigeration system is opened Do not replace the Drier until after all other repairs or replacement have been made 1 Recover the refrigerant R134a and store it in an approved...

Страница 26: ...or air lter clogged 3 Clean 4 Condenser air inlet blocked 4 9 Instruct the user on characteristics and proper use of the showcase 5 Exposed to direct sunlight 6 Located next to a high heat producing...

Отзывы: