34
5. Bin Control Selector (S1 dip switch 7)
The bin control selector is factory set. Do not adjust. When used on a standard ice
storage bin, only the mechanical bin control should be used. When the mechanical
bin control is used (S1 dip switch 7 in the off position), the gear motor delay after the
upper float switch closes is 5 sec.
WARNING! Do not adjust S1 dip switch 7 out of
the factory default position. This dip switch must be left in the factory default
position. If moved, the appliance will not operate correctly and could lead to no
ice operation, control board alarms, or ice overflow.
S1 Dip Switch
Setting
Bin Control Application
Gear Motor Delay
No. 7
OFF
BC (stand-alone) (Standard Ice Storage Bins Only)
5 seconds
ON
BC1 (infrared sensor) Stand-Alone and
BC1 (infrared sensor) with BC2 (mechanical backup)
30 seconds
6. Agitation and Ice Purge Timer (S1 dip switch 8)
Not available when S1 dip switch 7 is on. Factory set for normal operation. No
adjustment is required.
WARNING! Do not adjust S1 dip switch 8 out of the factory
default position. This dip switch must be left in the factory default position or the
appliance will not operate correctly.
S1 Dip Switch
Setting
Storage Bin Periodic Agitation
Ice Purge Timer
No. 8
OFF
2 Seconds
60 Seconds (1 min.)
ON
No Agitation
300 Seconds (5 min.)
7. Mechanical Shutdown Delay (S1 dip switch 9)
The shutdown delay is the time between the bin control micro-switch opening and the
control board shutting down the appliance.
WARNING! Do not adjust S1 dip switch
9 out of the factory default position. This dip switch must be left in the factory
default position or the appliance will not operate correctly.
S1 Dip Switch
Setting
Mechanical Shutdown Delay
No. 9
OFF
90-60 Second Sequence (150 sec. total)
ON
6 to 10 Seconds
8. Factory Use (S1 Dip Switch 10)
Factory set for optimum performance. Do not adjust.