35
B. Control Module Check
Before replacing a control module that does not show a visible defect and that you
suspect is bad, always conduct the following check procedure. This procedure will help
you verify your diagnosis. Always choose a neutral (W wire) to establish a good neutral
connection when checking high voltages. Also, confirm that there is a good neutral
connection to the control module terminal N5.
Alarm Reset: To silence the alarm, press and release the upper or lower button with
power on. For alarm information, see "II.D.2. Alarm Safeties."
Startup/Cool Down:
1) Check all wiring connections. Confirm that the DM cable, CTh, and DTh are properly
connected.
2) Move the power switch to the "ON" position.
3) Check for 115VAC between CM terminals L3 and N5. If 115VAC is not present, check
power supply and power switch.
4) Check that DM is on and cabinet temperature is displayed. If not, replace DM and CM.
5) Freezer: Check that EvapFM is energized. Make sure that the door(s) are closed and
the door switch is engaged. Next, check for 115VAC between CM terminals F6 and N5.
If 115VAC is not present, replace CM.
6) Check that Comp and ConFM energize. If not, check for 115VAC between CM terminals
C1 and N5. If 115VAC is not present, replace CM.
Defrost:
7) Press and hold the lower button until "dEF" appears on DM.
8) Confirm that the Comp, ConFM, and EvapFM (freezer) de-energize. Check for 115VAC
between CM terminals C1 and N5 for Comp and ConFM, then between terminals F6
and N5 (freezer) for EvapFM. If "dEF" is displayed and there is 115VAC between the
terminals, replace CM.
9) Freezer: Confirm that DH energizes. Check for 115VAC between CM terminals H4 and
N5. If "dEF" is displayed and 115VAC is not present, replace CM.
10) Check that the components restart after defrost termination.
Refrigerator: Comp and ConFM energize as soon as the DTh termination temperature
is satisfied. See "
Defrost Termination
" under "IV.A.1.9) Defrost" and "IV.C. Thermistor
Check." If components fail to start, replace CM.
Freezer: Comp and ConFM energize 3-minutes after defrost termination temperature
is satisfied. EvapFM energizes 5-minutes after that (except manual defrost), and the
cabinet temperature appears on DM 5-minutes after EvapFM energizes. See "
Defrost
Termination
" under "IV.A.2.9) Defrost" and "IV.C. Thermistor Check." If components fail
to start, replace CM.
Legend:
CM
–control module;
Comp
–compressor;
ConFM
–condenser fan motor;
CTh
–cabinet thermistor;
DH
–defrost heater;
DM
–display module;
DTh
–defrost thermistor;
EvapFM
–evaporator fan motors;
Содержание AMERICA 73183
Страница 22: ...22 B Wiring Diagrams 1 CR1B FG High Pressure Switch Cut out 270 10 PSIG Cut in 190 20 PSIG...
Страница 23: ...23 High Pressure Switch Cut out 270 10 PSIG Cut in 190 20 PSIG 2 CR1B FS HS CR3B FS HS...
Страница 24: ...24 3 CR2B FG High Pressure Switch Cut out 270 10 PSIG Cut in 190 20 PSIG...
Страница 25: ...25 4 CR2B FS HS CR3B FS HS High Pressure Switch Cut out 270 10 PSIG Cut in 190 20 PSIG...