4.4 Illustration of connection points

The following connections are located on rear side (see picture 2): 

 

 

 

   Picture 2: Connection points on rear side of the WEGA 2.2 

4-pole flat connector: 
 

 

L1, L2, L3  

 

-  

Connections for the capacitive taps of the switchgear  

 

 

 

 

 

 

unit

 

           Earth symbol    

-  

Connection of the earth socket to the frame and    

 

 

 

 

 

 

to the shield in case of  coax cable

6-pole plug-in connector element:
 

 

 U ≠ 0               

NO or NC of the relay „Voltage Present“

 

 

 U = 0               

NO or NC of the relay „No Voltage Present“

2-pole plug-in connector element
 

  

Auxiliary voltage   

24...230V (AC or DC)

5. Operating Instructions
5.1 Function test

The function test can be carried out with the device in installed and thus active condition (indication 

of arrow or arrow and dot) or in dismounted condition.
Testing with the device in active condition:
The test is carried out by short-circuiting one of the three measuring sockets with the earth socket. 

The respective light of the arrow and dot symbol of L1, L2 or L3 will extinguish and the respective tool 

symbol appear. The dedicated relay „No Voltage Present“ is switched on.

5.2 Testing with the device in non-active condition (Self-test)

This test can be carried out with the switchgear unit in voltage-free condition. The arrow and dot 

symbols  are  not  indicated.  When  the  auxiliary  voltage  is  switched  on,  the  LCD  display  will  be 

illuminated and the three tool symbols start flashing. By gently pushing the „Display Test“ button all 

symbols of the LCD display will be illuminated for a short time. 

5.3 Active zero voltage indication

This will be activated, once the switchgear unit switches to voltage-free condition. The indication is 

visualized by three flashing tool symbols at the bottom of the LCD display frame. This indication is 

permanently activated with the presence of auxiliary voltage.

If any of the defined indications fails to appear during function testing, this will be a sign 

that the integrated voltage detecting system is defect. In this case its indication must not be 

made use of for the evaluation of voltage conditions.

6

Dipl.-Ing. H. Horstmann GmbH

Содержание WEGA 2.2

Страница 1: ...Instructions for Use WEGA 2 2 4025122 001 May 2008 Dipl Ing H Horstmann GmbH Humboldtstra e 2 42579 Heiligenhaus www horstmanngmbh com...

Страница 2: ...5 4 3 Remote indication 5 4 4 Illustration of connection points 6 5 Operating Instructions 6 5 1 Function test 6 5 2 Testing with the device in non active condition Self test 6 5 3 Active zero voltage...

Страница 3: ...arisons It is imperative that the safety rules of VDE 0105 Part 1 and Part 100 are always observed when using this voltage detecting device Please observe especially the following Integrated WEGA 2 2...

Страница 4: ...panel a display test can be carried out activating all symbols on the display for a short time The indications of the arrow and dot symbols on the display do not require any auxiliary energy because...

Страница 5: ...overall system is in voltage free condition U 0 10 Un all of the three wrenches active zero voltage indication start flashing 4 2 Mechanical characteristics Dimensions 96mm x 48mm x 42 5mm Plug in ho...

Страница 6: ...ght of the arrow and dot symbol of L1 L2 or L3 will extinguish and the respective tool symbol appear The dedicated relay No Voltage Present is switched on 5 2 Testing with the device in non active con...

Страница 7: ...by Horstmann GmbH which is fixed onto the LRM interface on the front plate The sockets are accessible after the protection caps have been removed The attachment of the phase comparator to the device m...

Страница 8: ...to each installation Attention Any warranty claim is void in the case of damages caused by non observance of these operating instructions We are not liable for consequential damages arising out of or...

Отзывы: