HORNER X7 OCS Скачать руководство пользователя страница 2

12/18/2018 | MAN1202-01-EN

Indianapolis, USA  |  Cork, Ireland  |  Calgary, Canada  |  Bangalore, India  |  Oakleigh, Australia  |  Tianjin, China  |  Esteio, Brazil

Please visit our website for a complete listing and to learn more about certified Horner Automation products.
This document is the property of Horner Automation Group, and is subject to change. 

2.1 - Port Connectors

3.1 - Installation Procedure

page 2 of 4

4.1 - Panel Cut-Out

1.  Touch Screen

2.  High Capacity microSD Slot

3.  RS232/RS485 Serial Connector, CAN port (via RJ45), LAN Port (Ethernet)

4.  USB Mini-B Port

5.  Analog I/O, DC Inputs, DC Outputs

6.  DC Power

2

3

5

6

4

1

The X7 utilizes a clip installation method to ensure a robust and watertight seal to the 
enclosure. Please follow the steps below for the proper installation and operation of 
the unit.

1. 

Carefully locate an appropriate place to mount the X7. Be sure to leave  

 

enough room at the top of the unit for insertion and removal of the  

 

microSD™ card. 

2.  Carefully cut the host panel per the diagram on Page 1, creating a 174.63mm  
 

x 130.96mm +/- 0.1mm opening into which the X7 may be installed.  

 

 

If the opening is too large, water may leak into the enclosure, potentially  

 

 

damaging the unit. If the opening is too small, the OCS may not fit through   

 

the hole without damage.

3.  Remove any burrs and or sharp edges and ensure the panel is not warped in  
 

the cutting process. 

4.  Install and tighten the four mounting clips (provided in the box) until the  
 

gasket forms a tight seal. For standard composite mounting clips (included with  

 

product), use a torque rating of 2-3 in-lbs (0.23-0.34 Nm). For optional metal  

 

mounting clips, use a torque rating of 4-8 in lbs (0.45-0.90 Nm). 

5.  Connect communications cables to the serial port, USB ports, and CAN  
 

port as required.

The graphics below detail the dimensions and depth of the overall controller itself. 
The X7 panel cut-out measures  6.88” (174.63mm) wide x 5.16” (130.96mm) tall. 

 

Содержание X7 OCS

Страница 1: ...ht 100 154mA 24V Power Backlight Off 123mA 24V Inrush Current 30A 1ms Real Time Clock Battery backed lithium coin cell CR2450 Clock Accuracy 90 Secs Month Relative Humidity 5 to 95 Non condensing OperatingTemp 10 C to 60 C Storage Temp 20 C to 70 C Weight 20 8 oz 590 g Included in Box Controller 3 x I 0 connectors 4 x mounting clips 1 x power connector Quick Reference Guide Certifications UL CE US...

Страница 2: ... sure to leave enough room at the top of the unit for insertion and removal of the microSD card 2 Carefully cut the host panel per the diagram on Page 1 creating a 174 63mm x 130 96mm 0 1mm opening into which the X7 may be installed If the opening is too large water may leak into the enclosure potentially damaging the unit If the opening is too small the OCS may not fit through the hole without da...

Страница 3: ...gital Out NOTE Internal 10kΩ resistors between V and Q1 V and Q2 LOAD LOAD LOAD LOAD LOAD LOAD LOAD LOAD 230 VAC or 25 VDC 230 VAC or 25 VDC 230 VAC or 25 VDC 230 VAC or 25 VDC 230 VAC or 25 VDC 230 VAC or 25 VDC SINKING SOURCING X 7 M O D E L R O N LY X 7 M O D E L S R A B O T H 5 4 J3 Wiring Connector RTD Wiring Primary Power Range 24VDC 20 5 5 Wiring Connectors Model R A Power PIN 4x2 Wire RTD ...

Страница 4: ...to the following two conditions 1 This device may not cause harmful interference 2 This device must accept any interference received including interference that may cause undesired operation 6 1 Connecting the X7 to a PC 8 1 Technical Support For further details please refer to the Datasheet MAN1138 For assistance and manual updates contact Technical Support at the following locations North Americ...

Отзывы: