1  TECHNICAL SPECIFICATIONS

1.4 Control & Logic

Control Language 
Support

Advanced ladder logic 
Full IEC 61131-3 languages

Logic Program Size

256kB

Non-Retentive Memory

128kB

Internal Storage 
Memory

16Mb

Total Program 
Memory 

2.5Mb

Logic Scan Rate

0.4ms/kB 

%I (Digital Inputs)

1024

%Q (Digital Outputs)

1024

%AI (Analog Inputs)

256

%AQ (Analog 
Outputs)

256

%M (Retentive Bits)

1024

%T (Temporary Bits)

1024

%R (Retentive Registers) 5000
%D (Display Bits)

250

%K (Key Bit)

4

%S (Status Bits)

16

%SR (System Registers) 192

1.3 Connectivity

Serial Ports

1 x RS232, 1 x RS485

485 Terminations

On-board, software 
controlled

USB mini-B

Slave only

USB Programming 
Support

Yes

USB Type

USB 2.0

CAN Hardware

CAN 2.0

CAN Port Connector

RJ45 (Red)

CAN Port Speeds 
Support

125kB, 250kB, 500kB,  
1Mb/sec.

CAN Port Termination

On-board, software 
controlled

CAN Protocols

CsCAN

Removable Memory In

microSD (SDHC, SDXC 
IN FAT32 format, 
support for 32GB max. 
Application Updates, 
Datalogging, more)

1.2 User Interface

Display

4.3” 65k Color 
Transmissive

Resolution

480 x 272 pixels

Backlight

White LED

Backlight Lifetime

20,000 hrs to reach 
50% brightness

Backlight Control

Yes, software  
controlled (ON/OFF)

User-Programmable 
Screens/Pages

250

No. of Objects/Screens

30

Screen Memory

256kB

Keypad

Slide Keys (Touch)

Tactile Feedback

Optional Sound

Number of Keys

Slide Keys (Touch)

X OCS MODEL: HE-X4

1.1 General

Primary Pwr. 
Range

24VDC +/- 20%

Typical power 
Backlight 100%

140mA @ 24VDC
170mA @ 19.2VDC

Power 
Backlight Off

105mA @ 24VDC
135mA @ 19.2VDC

Inrush Current

30mA 

˂

 1ms

Real Time Clock

Battery backed;
lithium coin cell CR2450

Clock Accuracy

+/- 90 Secs/Month

Relative Humidity

5 to 95%  Non-condensing

Operating Temp.

-10°C to +60°C

Storage Temp.

-20°C to +70°C

Weight

360g 

Mounting Clips

4 composite type

Housing Material

Polycarbonate, UL rated

Panel Seal

Silicone rubber

Packaging

100% Recyclable  
paper fiber materials

Included in Box

Controller,  
3 x I/0 connectors,  
4 x mounting clips,  
1 x power connector, Quick 
Reference Guide

1.5 I/O Connections

Terminal Type

Removable 3.5 m 
color-coded

I/O Options

None

Remote I/O

Serial, CAN, Ethernet

1.6 Testing

Shock

IEC 60068-2-27

Vibration

IEC 60068-2-6

Washdown

NEMA 4X

Certifications 
(UL/CE)

USA:    h

ttps://hornerauto-

mation.com/certifications/ 

Europe:  h

ttp://www.

horner-apg.com/en/support/
certification.aspx

1.7 Inputs/Outputs Model Overview

MODEL R

MODEL A

DC In

12

12

DC Out

2

12

Relays

6

HS In

4

4

HS Out

2

2

mA In/RTD

4

4

mA Out

2

2

There are four high-speed inputs of the total DC Inputs.  

There are two high-speed outputs of the total DC outputs.

Model A supports sourcing outputs. Model R DC outputs are 

sinking with integral pull up resistors.

page 1 of 7

technical specifications continued on next page...

MODEL A BUILT-IN I/O:  12 DIGITAL IN, 12 DIGITAL OUT, 4 ANALOG IN/RTD IN, 2 ANALOG OUT

MODEL R BUILT-IN I/O:  12 DIGITAL IN, 6 RELAY OUT, 2 PWM OUT, 4 ANALOG IN/RTD IN, 2 ANALOG OUT

Содержание X Series

Страница 1: ... ON OFF User Programmable Screens Pages 250 No of Objects Screens 30 Screen Memory 256kB Keypad Slide Keys Touch Tactile Feedback Optional Sound Number of Keys Slide Keys Touch X OCS MODEL HE X4 1 1 General Primary Pwr Range 24VDC 20 Typical power Backlight 100 140mA 24VDC 170mA 19 2VDC Power Backlight Off 105mA 24VDC 135mA 19 2VDC Inrush Current 30mA 1ms Real Time Clock Battery backed lithium coi...

Страница 2: ...uts Models R A Inputs per Module 12 Including 4 Config urable HSC Inputs Commons per Module 1 Input Voltage Range 12VDC 24VDC Absolute Max Voltage 35VDC Max Input Impedance 10kΩ Input Current Positive Logic Negative Logic Upper Threshold Lower Threshold 0 8mA 0 3mA 1 6mA 2 1mA Max Upper Threshold 8VDC Min Lower Threshold 3VDC OFF to ON Response 0 1ms ON to OFF Response 0 1ms Number of Counters 4 M...

Страница 3: ...puts 10 DC Power 1 2 3 4 5 6 7 8 9 10 POSITION PIN DIGITAL MODEL 1 Q1 Output 1 PWM 2 Q2 Output 2 PWM 3 Q3 Output 3 4 Q4 Output 4 5 V External V 6 C Common 7 Q5 Output 5 8 Q6 Output 6 9 Q7 Output 7 10 Q8 Output 8 11 Q9 Output 9 12 Q10 Output 10 13 Q11 Output 11 14 Q12 Output 12 15 V External V 2 16 C Common Q1 Q2 Q3 Q4 V C Q5 Q6 Q7 Q8 Q9 Q 1 0 Q 1 1 Q 1 2 V C LOAD LOAD LOAD LOAD LOAD LOAD LOAD LOAD...

Страница 4: ... 6 I6 Input 6 7 I7 Input 7 8 I8 Input 8 9 I9 Input 9 HSC1 10 I10 Input 10 HSC2 11 I11 Input 11 HSC3 12 I12 Input 12 HSC4 13 C Common 14 C Common I1 I2 I3 I4 I5 I6 I7 I8 I9 I10 I11 I12 C C 12 24 VDC Model R Model A Digital Input J2 Wiring 3 4 RTD Wiring Removing and Inserting Connectors Use a small screwdriver to gently pry up the connector Gently press on connector to snap into place Wiring Detail...

Страница 5: ...her end of the CAN network Only the two devices on either end of the CAN network should be terminated page 5 of 7 I O STATUS AND CALIBRATION This controller supports field calibration for higher accuracy Refer to the X4 User Manual MAN1137 for full details MJ1 MJ2 PINS PIN SIGNAL DIRECTION 8 TXD OUT 7 RXD IN 6 0V Common 5 5V 60 mA OUT 4 RTS OUT 3 CTS IN 2 RX TX IN OUT 1 RX TX IN OUT 4 2 Serial Com...

Страница 6: ...X4 utilizes a clip installation method to ensure a robust and watertight seal to the enclosure Please follow the steps below for the proper installation and operation of the unit 1 Carefully locate an appropriate place to mount the X4 Be sure to leave enough room at the top of the unit for insertion and removal of the microSD card 2 Carefully cut the host panel per the diagram on Page 1 creating a...

Страница 7: ...ct to the following two conditions 1 This device may not cause harmful interference 2 This device must accept any interference received including interference that may cause undesired operation 8 3 PRECAUTIONS All applicable codes and standards need to be followed in the installation of this product Adhere to the following safety precautions whenever any type of connection is made to the module 1 ...

Отзывы: