background image

12/3/2019 | MAN1131-06-EN

Indianapolis, USA  |  Cork, Ireland  |  Calgary, Canada  |  Bangalore, India  |  Oakleigh, Australia  |  Tianjin, China  |  Esteio, Brazil

Please visit our website for a complete listing and to learn more about certified Horner Automation products.
This document is the property of Horner Automation Group, and is subject to change. 

  wiring: I-O continued... 

page 4 of 6

3.4 - Wiring Connectors

J1 Wiring: Model A -  Digital Out

POSITION/PIN

DIGITAL MODEL

1

Q1

Output 1 (PWM)

2

Q2

Output 2 (PWM)

3

Q3

Output 3

4

Q4

Output 4

5

V+

External V+

6

C

Common

7

Q5

Output 5

8

Q6

Output 6

9

Q7

Output 7

10

Q8

Output 8

11

Q9

Output 9

12

Q10

Output 10

13

Q11

Output 11

14

Q12

Output 12

15

V+

External V 2 +

16

C

Common

Q1
Q2
Q3
Q4
V+
C
Q5
Q6
Q7
Q8
Q9
Q10
Q11

Q12
V+
C

LOAD

LOAD

LOAD

LOAD

LOAD

LOAD

LOAD

LOAD

LOAD

LOAD

LOAD

LOAD

wiring: I-O continued on next page...

Sinking:

 Outputs can sink 500mA

Model R: Sinking Outputs

 Q1

 C

Load

LOAD

SINKING

Q1
Q2
V+
C

Model R: Sourcing Outputs

LOAD

SOURCING

Q1
Q2
V+
C

   

   

 

        
                     Q1

 10k

Ω

 V+

 C

Load 

Sourcing:

  0.5A sourcing @ 24V

L

N

L

N

L

N

L

N

L

N

L

N

J1 Wiring: Model R -  Relay and Digital Out

POSITION/PIN

DIGITAL MODEL

1

R1

Relay 1 N.O.

2

C1

Relay 1 C

3

R2

Relay 2 N.O.

4

C2

Relay 2 C

5

R3

Relay 3 N.O.

6

C3

Relay 3 C

7

R4

Relay 4 N.O.

8

C4

Relay 4 C

9

R5

Relay 5 N.O.

10

C5

Relay 5 C

11

R6

Relay 6 N.O.

12

C6

Relay 6 C

13

Q1

Output 1

14

Q2

Output 2

15

V+

External V+

16

C

Common

60 VAC or 30 VDC

60 VAC or 30 VDC

60 VAC or 30 VDC

60 VAC or 30 VDC

60 VAC or 30 VDC

60 VAC or 30 VDC

R1
C1
R2
C2
R3
C3
R4
C4
R5
C5
R6
C6
Q1
Q2
V+
C

NOTE:  Internal 10k

Ω

 resistors 

between:  V+ and Q1; V+ and Q2

Sinking and 
Sourcing wiring 
below.

LOAD

LOAD

LOAD

LOAD

LOAD

LOAD

POSITION/PIN

DIGITAL MODEL

1

I1

Input 1 (HSC)

2

I2

Input 2 (HSC)

3

I3

Input 3 (HSC)

4

I4

Input 4 (HSC)

5

I5

Input 5

6

I6

Input 6

7

I7

Input 7

8

I8

Input 8

9

I9

Input 9

10

I10

Input 10

11

I11

Input 11

12

I12

Input 12

13

C

Common 

14

C

Common

I1
I2
I3
I4
I5
I6
I7
I8
I9
I10
I11
I12
C
C

12-24 

VDC

J2 Wiring - Model R & Model A  - Digital Input

Содержание X OCS Series

Страница 1: ...edback Yes Number of Keys 4 Soft keys 16 numeric function keys X OCS MODEL HE X2 MODEL A BUILT IN I O 12 DIGITAL INPUTS 12 DIGITAL OUTPUTS 4 ANALOG INPUTS 2 ANALOG OUTPUTS MODEL R BUILT IN I O 12 DIGITAL INPUTS 6 RELAY OUTPUTS 2 PWM OUTPUTS 4 ANALOG INPUTS 2 ANALOG OUTPUTS 1 1 General Primary Pwr Range 24VDC 20 Typical power back light 100 64mA 24V 1 53W Power Backlight Off 15mA 24V 0 36W Inrush C...

Страница 2: ...ncludes information on Built In I O Common S SR Registers Resource Limits 1 9 Model R Digital DC Outputs Sinking Sourcing Outputs per Module 2 PWM or HSC Commons per Module 1 Type Sinking Absolute Max Voltage 28VDC Output Protec tion Short circuit Max Output per Point Sinking 0 5A Max Output per Point Sourcing 2 4mA 24V Max Voltage Drop at Rated Current 0 25VDC Max Outrush 650mA Min Max OFF to ON ...

Страница 3: ... wiring used in order for the correct input states to be registered Removing and Inserting Connectors Use a small screwdriver to gently pry up the connector Gently press on connector to snap into place Wiring Details Solid Stranded Wire 12 24 awg 2 5 0 2mm Strip Length 0 28 7mm Torque Rating 4 5 7 in lbs 0 50 0 78 Nm 3 2 Relay Life WARNING Exposure to some chemicals may degrade the sealing proper ...

Страница 4: ... Outputs Q1 C Load LOAD SINKING Q1 Q2 V C Model R Sourcing Outputs LOAD SOURCING Q1 Q2 V C Q1 10kΩ V C Load Sourcing 0 5A sourcing 24V L N L N L N L N L N L N J1 Wiring Model R Relay and Digital Out POSITION PIN DIGITAL MODEL 1 R1 Relay 1 N O 2 C1 Relay 1 C 3 R2 Relay 2 N O 4 C2 Relay 2 C 5 R3 Relay 3 N O 6 C3 Relay 3 C 7 R4 Relay 4 N O 8 C4 Relay 4 C 9 R5 Relay 5 N O 10 C5 Relay 5 C 11 R6 Relay 6...

Страница 5: ...CAN network should be terminated 4 COMMUNICATIONS 4 1 CAN Communications CAN Pin Assignments PIN SIGNAL 8 No Connection 7 Ground 6 Shield 5 No Connection 4 No Connection 3 Ground 2 CAN Data Low 1 CAN Data High CAN Modular jack 8posn RJ45 POSITION PIN DIGITAL MODEL 1 AI1 Analog Input 1 2 AI2 Analog Input 2 3 AI3 Analog Input 3 4 AI4 Analog Input 4 5 C Common 6 C Common 7 AQ1 Analog Output 1 8 AQ2 A...

Страница 6: ...ended to fuse the voltage measurement inputs Be sure to locate fuses as close to the source as possible 5 Replace fuse with the same type and rating to provide protection against risk of fire and shock hazards 6 In the event of repeated failure do NOT replace the fuse again as repeated failure indicates a defective condition that will NOT clear by replacing the fuse 7 Only qualified electrical per...

Отзывы: