12/3/2019 | MAN1131-06-EN
Indianapolis, USA | Cork, Ireland | Calgary, Canada | Bangalore, India | Oakleigh, Australia | Tianjin, China | Esteio, Brazil
Please visit our website for a complete listing and to learn more about certified Horner Automation products.
This document is the property of Horner Automation Group, and is subject to change.
wiring: I-O continued...
page 4 of 6
3.4 - Wiring Connectors
J1 Wiring: Model A - Digital Out
POSITION/PIN
DIGITAL MODEL
1
Q1
Output 1 (PWM)
2
Q2
Output 2 (PWM)
3
Q3
Output 3
4
Q4
Output 4
5
V+
External V+
6
C
Common
7
Q5
Output 5
8
Q6
Output 6
9
Q7
Output 7
10
Q8
Output 8
11
Q9
Output 9
12
Q10
Output 10
13
Q11
Output 11
14
Q12
Output 12
15
V+
External V 2 +
16
C
Common
Q1
Q2
Q3
Q4
V+
C
Q5
Q6
Q7
Q8
Q9
Q10
Q11
Q12
V+
C
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
wiring: I-O continued on next page...
Sinking:
Outputs can sink 500mA
Model R: Sinking Outputs
Q1
C
Load
LOAD
SINKING
Q1
Q2
V+
C
Model R: Sourcing Outputs
LOAD
SOURCING
Q1
Q2
V+
C
Q1
10k
Ω
V+
C
Load
Sourcing:
0.5A sourcing @ 24V
L
N
L
N
L
N
L
N
L
N
L
N
J1 Wiring: Model R - Relay and Digital Out
POSITION/PIN
DIGITAL MODEL
1
R1
Relay 1 N.O.
2
C1
Relay 1 C
3
R2
Relay 2 N.O.
4
C2
Relay 2 C
5
R3
Relay 3 N.O.
6
C3
Relay 3 C
7
R4
Relay 4 N.O.
8
C4
Relay 4 C
9
R5
Relay 5 N.O.
10
C5
Relay 5 C
11
R6
Relay 6 N.O.
12
C6
Relay 6 C
13
Q1
Output 1
14
Q2
Output 2
15
V+
External V+
16
C
Common
60 VAC or 30 VDC
60 VAC or 30 VDC
60 VAC or 30 VDC
60 VAC or 30 VDC
60 VAC or 30 VDC
60 VAC or 30 VDC
R1
C1
R2
C2
R3
C3
R4
C4
R5
C5
R6
C6
Q1
Q2
V+
C
NOTE: Internal 10k
Ω
resistors
between: V+ and Q1; V+ and Q2
Sinking and
Sourcing wiring
below.
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
POSITION/PIN
DIGITAL MODEL
1
I1
Input 1 (HSC)
2
I2
Input 2 (HSC)
3
I3
Input 3 (HSC)
4
I4
Input 4 (HSC)
5
I5
Input 5
6
I6
Input 6
7
I7
Input 7
8
I8
Input 8
9
I9
Input 9
10
I10
Input 10
11
I11
Input 11
12
I12
Input 12
13
C
Common
14
C
Common
I1
I2
I3
I4
I5
I6
I7
I8
I9
I10
I11
I12
C
C
12-24
VDC
J2 Wiring - Model R & Model A - Digital Input