MAN0927-03                                                   PAGE 4                                            Thermocouple module 

 

 
                                                                                                           

                                                    

 

 

4  

NETWORK DATA 

Consumed Digital Data

 – This data is sent from the controller to the SmartBlock.  

For typical 

applications the I/O configuration setup in Cscape will automatically populate this data. 

 For more 

advanced applications you may use NetPut functions to write this data.  Please see the advanced 
programming guide MAN0880 for more details. 

Bit 

Description 

12 

0 = 0.1

°

C   1 = 0.1

°

 

13-16 

Filter 

See programming Guide  

17-20 

Thermocouple Type Channel 1 

21-24 

Thermocouple Type Channel 2 

25-28 

Thermocouple Type Channel 3 

29-32 

Thermocouple Type Channel 4 

65-68 

Thermocouple Type Channel 5 

69-72 

Thermocouple Type Channel 6 

73-80 

Thermocouple Type Channel 7 

77-80 

Thermocouple Type Channel 8 

0 = J,  -210°C to 1200°C 
1 = K,  -200° to 1372°C 
2 = N,  -200°C to 1300°C 
3 = T,  -200°C to 400°C 
4 = E,  -200°C to 1000°C 
5 = R,  -50°C to 1768°C    
6 = S,   -50°C to 1768°C 
7 = B,  250°C to 1820°C 

8 = C,  0°C to 2320°C 
 
12 = 25mV 
13 = 50mV 
14 = 100mV 
15 = 200mV 

 

Produced Analog Data

 – This data is sent from the SmartBlock to the controller.  

Normally this data is 

mapped into specific registers in the I/O configuration in Cscape.

  For advanced applications NetGet 

functions can be used to obtain this data.  Since this data is broadcast to all controllers on the network 
additional controllers can use NetGet functions to obtain this data as well. 
 

Word 

Function 

Word 1 

INT 

Thermocouple Input 1 

Word 2 

INT 

Thermocouple Input 2 

Word 3 

INT 

Thermocouple Input 3 

Word 4 

INT 

Thermocouple Input 4 

Word 5 

INT 

Thermocouple Input 5 (THM200 Only) 

Word 6 

INT 

Thermocouple Input 5 (THM200 Only) 

Word 7 

INT 

Thermocouple Input 5 (THM200 Only) 

Word 8 

INT 

Thermocouple Input 5 (THM200 Only) 

 
 

Содержание SmartBlock HE579THM100

Страница 1: ...orted J K N T E C R S B Relative Humidity 5 to 95 Non condensing Millivolt Ranges 25mv 50mv 100mv 200mv 16 bit Resolution Operating Temperature 0 to 60 Celsius Millivolt Accuracy 0 1 Full Scale Weight 12oz 340g Accuracy Note Accuracy Specifications not guaranteed below 200 C Common Mode Range wrt field common 10VDC Max Types J K T E N Type C B Types R S A D Conversion Time 6 channels per second 1 ...

Страница 2: ...e lower left grounding location into a grounded back plate Alternately a ground can be connected to the spade lug Please see Horner manual MAN0799 for details on CAN wiring CAN Network Power Port Pin Assignments Pin Signal Signal Description Direction 1 V CAN and Device Ground Black 2 CN_L CAN Data Low Blue In Out 3 SHLD Shield Ground None 4 CN_H CAN Data High White In Out 5 V Positive DC Voltage ...

Страница 3: ...y may be used to reduce noise Ungrounded thermocouples wiring options Preferred shield connection Alternate shield connection Ungrounded thermocouples should have one side tied to isolated common to reduce noise pickup Grounded thermocouples may use type 3 or 4 shield connections if shield is not grounded at field end Type 1 Type 2 Type 3 Type 4 7VAC 7VAC ...

Страница 4: ...hannel 8 0 J 210 C to 1200 C 1 K 200 to 1372 C 2 N 200 C to 1300 C 3 T 200 C to 400 C 4 E 200 C to 1000 C 5 R 50 C to 1768 C 6 S 50 C to 1768 C 7 B 250 C to 1820 C 8 C 0 C to 2320 C 12 25mV 13 50mV 14 100mV 15 200mV Produced Analog Data This data is sent from the SmartBlock to the controller Normally this data is mapped into specific registers in the I O configuration in Cscape For advanced applic...

Страница 5: ...ear the PLC This does not affect open thermocouple detection or measurement accuracy and reduces the effect of common mode noise if present This PLC side ground connection must not be used with grounded thermocouples or accuracy will be affected Any thermocouple should be grounded in one place at most When found on the product the following symbols specify All applicable codes and standards need t...

Страница 6: ...quipment including safety glasses and insulated gloves when making connections to power circuits Ensure hands shoes and floor are dry before making any connection to a power line Make sure the unit is turned OFF before making connection to terminals Make sure all circuits are de energized before making connections Before each use inspect all cables for breaks or cracks in the insulation Replace im...