DIMENSIONS AND INSTALLATION 

 
 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 
 

Network, Power and Grounding: 

A single 5 pin connector is used to make both a network connection and power input.  A quality class 2 
power supply should be used for this product.  If the power is run with the network cable, care must be 
taken such that the voltage does not drop below the lower supply limit on longer runs. 
 
A quality earth ground is required for safe and proper operation.  The best ground is achieved by 
screwing the lower left grounding location into a grounded back plate.  Alternately a ground can be 
connected to the spade lug. 
 
Please see Horner manual MAN0799 for details on CAN wiring. 

CAN Network & Power Port Pin Assignments 

Pin 

Signal 

Signal Description 

Direction 

V- 

CAN and Device 

Ground - Black 

!

 

CN_L 

CAN Data Low - Blue 

In/Out 

SHLD 

Shield Ground - None 

!

 

CN_H 

CAN Data High - White 

In/Out 

V+ 

Positive DC Voltage 

Input (10-30VDC) - Red 

!

 

4.56” 
(115.8mm) 

4.48” 
(113.7mm) 

2.16” 

(54.8mm) 

With connector 

2.84” 

(72.1mm) 

CAN Network & Power 

Connector 

 

Torque rating 4.5 – 7 Lb-In 

(0.50 – 0.78 N-m) 

 

 

J2 
Thermocouples  
5-8 THM200 only 

J1 
Thermocouples 
1-4 

Can and 
Power 
Connector 

Network ID 
Selector 
Switches 

Status LEDs 

Earth Ground 
Location 

Содержание SmartBlock HE579THM100

Страница 1: ...orted J K N T E C R S B Relative Humidity 5 to 95 Non condensing Millivolt Ranges 25mv 50mv 100mv 200mv 16 bit Resolution Operating Temperature 0 to 60 Celsius Millivolt Accuracy 0 1 Full Scale Weight 12oz 340g Accuracy Note Accuracy Specifications not guaranteed below 200 C Common Mode Range wrt field common 10VDC Max Types J K T E N Type C B Types R S A D Conversion Time 6 channels per second 1 ...

Страница 2: ...e lower left grounding location into a grounded back plate Alternately a ground can be connected to the spade lug Please see Horner manual MAN0799 for details on CAN wiring CAN Network Power Port Pin Assignments Pin Signal Signal Description Direction 1 V CAN and Device Ground Black 2 CN_L CAN Data Low Blue In Out 3 SHLD Shield Ground None 4 CN_H CAN Data High White In Out 5 V Positive DC Voltage ...

Страница 3: ...y may be used to reduce noise Ungrounded thermocouples wiring options Preferred shield connection Alternate shield connection Ungrounded thermocouples should have one side tied to isolated common to reduce noise pickup Grounded thermocouples may use type 3 or 4 shield connections if shield is not grounded at field end Type 1 Type 2 Type 3 Type 4 7VAC 7VAC ...

Страница 4: ...hannel 8 0 J 210 C to 1200 C 1 K 200 to 1372 C 2 N 200 C to 1300 C 3 T 200 C to 400 C 4 E 200 C to 1000 C 5 R 50 C to 1768 C 6 S 50 C to 1768 C 7 B 250 C to 1820 C 8 C 0 C to 2320 C 12 25mV 13 50mV 14 100mV 15 200mV Produced Analog Data This data is sent from the SmartBlock to the controller Normally this data is mapped into specific registers in the I O configuration in Cscape For advanced applic...

Страница 5: ...ear the PLC This does not affect open thermocouple detection or measurement accuracy and reduces the effect of common mode noise if present This PLC side ground connection must not be used with grounded thermocouples or accuracy will be affected Any thermocouple should be grounded in one place at most When found on the product the following symbols specify All applicable codes and standards need t...

Страница 6: ...quipment including safety glasses and insulated gloves when making connections to power circuits Ensure hands shoes and floor are dry before making any connection to a power line Make sure the unit is turned OFF before making connection to terminals Make sure all circuits are de energized before making connections Before each use inspect all cables for breaks or cracks in the insulation Replace im...

Отзывы: