MAN0969-02                                                   PAGE 5                                                  Mix577/977 Module 

 

INSTALLATION / SAFETY 

Warning:

   Remove power from the OCS controller, CAN port, and any peripheral equipment 

connected to this local system before adding or replacing this or any module 

a)  All applicable codes and standards should be followed in the installation of this product. 
b)  Shielded, twisted-pair wiring should be used for best performance. 
c)  Shields are to be terminated to frame ground. 
d)  In severe applications, shields should be tied directly to the ground block within the panel. 
e)  Ungrounded  thermocouple  sensors  are  preferred  due  to  their  isolated  electrical 

characteristics 

f)  Interposing terminal strips between the sensor and the module can cause errors due to cold 

junction effect. 

g)  If Interposing terminal strips must be used, use specially constructed terminal blocks, which 

match the material characteristics of the thermocouple sensor. 

h)  Horner  thermocouple  input  modules  use  a  high  impedance  differential  circuit  to  support  the 

use of grounded or ungrounded thermocouples.  For grounded thermocouples, the specified 

Common Mode Range 

allows for ground potential differences between the machine ground 

and  the  PLC  ground  within  that  range.    For  ungrounded  or  floating  thermocouples  the  high 
impedance  inputs  are  subject  to  common  mode  noise  pickup.    For  noisy  environments  it  is 
recommended  that  one  side  of  all  ungrounded  thermocouples  be  grounded  near  the  PLC.  
This does not affect open thermocouple detection or measurement accuracy and reduces the 
effect of common mode noise if present.  This PLC side ground connection must not be used 
with  grounded  thermocouples  or  accuracy  will  be  affected.    Any  thermocouple  should  be 
grounded in one place at most. 

 

When found on the product, the following symbols specify:  

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

All applicable codes and standards need to be followed in the installation of this product. 

 

For I/O wiring (discrete), use the following wire type or equivalent:  Belden 9918, 18 AWG or 
larger.  

 

Warning:

  Consult user documentation. 

Warning:

  Electrical Shock Hazard. 

WARNING:

  To avoid the risk of electric shock or burns, always connect the safety (or 

earth) ground before making any other connections. 
 

WARNING:

  To reduce the risk of fire, electrical shock, or physical injury it is strongly 

recommended to fuse the voltage measurement inputs.  Be sure to locate fuses as close to 
the source as possible. 
 

WARNING:

  Replace fuse with the same type and rating to provide protection against risk of 

fire and shock hazards. 
 

WARNING: 

 In the event of repeated failure, do not replace the fuse again as a repeated 

failure indicates a defective condition that will not clear by replacing the fuse. 
 

WARNING:

  Only qualified electrical personnel familiar with the construction and operation 

of this equipment and the hazards involved should install, adjust, operate, or service this 
equipment.  Read and understand this manual and other applicable manuals in their entirety 
before proceeding.  Failure to observe this precaution could result in severe bodily injury or 
loss of life. 

Содержание SmartBlock HE579MIX577

Страница 1: ... filter 1 128 scan digital running average filter ANALOG OUT Number of Outputs 2 577 or 4 977 Isolation Power to Analog Output 3K VDC 2 5K VAC Test IEC61010 1 400V RMS Output Ranges 0 5V 0 10V DC 4 20mA 0 20mA DC Isolation Method Magnetic Resolution 14 bits Output Clamp 24V 5V 600Wpk Accuracy 25 C 0 1 Output Type Sourcing Load Resistance V 500 ohms Min mA 500 ohms Max Register Value for Nominal Fu...

Страница 2: ...on into a grounded back plate Alternately a ground can be connected to the spade lug Please see Horner manual MAN0799 for details on CAN wiring CAN Network Power Port Pin Assignments Pin Signal Signal Description Direction 1 V CAN and Device Ground Black 2 CN_L CAN Data Low Blue In Out 3 SHLD Shield Ground None 4 CN_H CAN Data High White In Out 5 V Positive DC Voltage Input 10 30VDC Red 2 16 54 8m...

Страница 3: ...Mix577 977 Module 3 WIRING V1 I1 C V2 I2 C V3 I3 C V4 I4 C O1 C O2 C V5 I5 C V6 I6 C V7 I7 C V8 I8 C O3 C O4 C 977 Only Ox C Load Channel wiring detail with shielded cable INPUTS V V1 C I1 No Connection 10V V1 C I1 20mA ...

Страница 4: ... the device to be configured Below is the configuration for MIX577 977 device Network ID This should match the ID of the rotary switch on the SmartBlock unit and should be unique to the network I O Mapping These registers define how the OCS controller registers are mapped to the data to and from the SmartBlock I O These registers do no have to match the I O types typically used for I O such as AI ...

Страница 5: ...ar the PLC This does not affect open thermocouple detection or measurement accuracy and reduces the effect of common mode noise if present This PLC side ground connection must not be used with grounded thermocouples or accuracy will be affected Any thermocouple should be grounded in one place at most When found on the product the following symbols specify All applicable codes and standards need to...

Страница 6: ...uipment including safety glasses and insulated gloves when making connections to power circuits Ensure hands shoes and floor are dry before making any connection to a power line Make sure the unit is turned OFF before making connection to terminals Make sure all circuits are de energized before making connections Before each use inspect all cables for breaks or cracks in the insulation Replace imm...