MAN0969-02                                                   PAGE 4                                                  Mix577/977 Module 

 

 
                                                                                                           

                                                    

 

 

4  

CONFIGURATION 

For most applications the I/O scanner built into Cscape and the OCS firmware will provide a fast, robust 
and easy to use method to configure and scan the SmartBlock I/O.  For advanced operations such as on-
the-fly changes to the input type please see the following chapter on network data and the SmartStix and 
SmartBlock programming guide. 

To configure SmartBlock I/O from Cscape open the Hardware Configuration dialog from the Controller | 
Hardware Configuration menu.  Select the option for CsCAN I/O, then click Add.  Select the SmartBlock 
Tab and select the device to be configured. 
 
Below is the configuration for MIX577/977 device. 

 

Network ID

 

– This should match the ID of the rotary switch on the SmartBlock unit and should be unique 

to the network. 

I/O Mapping

 

– These registers define how the OCS controller registers are mapped to the data to and 

from the SmartBlock I/O.  These registers do no have to match the I/O types typically used for I/O such as 
%AI, Q… Any standard controller registers may be used such as %R, %T and %M. 
 

Input Update Method

 

– This defines how often analog data is sent from the SmartBlock to the CsCAN 

network.  Digital data is transmitted on change of state. 
 

Channel Configuration

 

– This selects how each analog channel is configured including filtering. 

 

Timeout 

– This sets the time a controller will wait before assuming the host OCS is off-line. 

Содержание SmartBlock HE579MIX577

Страница 1: ... filter 1 128 scan digital running average filter ANALOG OUT Number of Outputs 2 577 or 4 977 Isolation Power to Analog Output 3K VDC 2 5K VAC Test IEC61010 1 400V RMS Output Ranges 0 5V 0 10V DC 4 20mA 0 20mA DC Isolation Method Magnetic Resolution 14 bits Output Clamp 24V 5V 600Wpk Accuracy 25 C 0 1 Output Type Sourcing Load Resistance V 500 ohms Min mA 500 ohms Max Register Value for Nominal Fu...

Страница 2: ...on into a grounded back plate Alternately a ground can be connected to the spade lug Please see Horner manual MAN0799 for details on CAN wiring CAN Network Power Port Pin Assignments Pin Signal Signal Description Direction 1 V CAN and Device Ground Black 2 CN_L CAN Data Low Blue In Out 3 SHLD Shield Ground None 4 CN_H CAN Data High White In Out 5 V Positive DC Voltage Input 10 30VDC Red 2 16 54 8m...

Страница 3: ...Mix577 977 Module 3 WIRING V1 I1 C V2 I2 C V3 I3 C V4 I4 C O1 C O2 C V5 I5 C V6 I6 C V7 I7 C V8 I8 C O3 C O4 C 977 Only Ox C Load Channel wiring detail with shielded cable INPUTS V V1 C I1 No Connection 10V V1 C I1 20mA ...

Страница 4: ... the device to be configured Below is the configuration for MIX577 977 device Network ID This should match the ID of the rotary switch on the SmartBlock unit and should be unique to the network I O Mapping These registers define how the OCS controller registers are mapped to the data to and from the SmartBlock I O These registers do no have to match the I O types typically used for I O such as AI ...

Страница 5: ...ar the PLC This does not affect open thermocouple detection or measurement accuracy and reduces the effect of common mode noise if present This PLC side ground connection must not be used with grounded thermocouples or accuracy will be affected Any thermocouple should be grounded in one place at most When found on the product the following symbols specify All applicable codes and standards need to...

Страница 6: ...uipment including safety glasses and insulated gloves when making connections to power circuits Ensure hands shoes and floor are dry before making any connection to a power line Make sure the unit is turned OFF before making connection to terminals Make sure all circuits are de energized before making connections Before each use inspect all cables for breaks or cracks in the insulation Replace imm...