MAN0969-02                                                   PAGE 1                                                  Mix577/977 Module 

 

 

 
 
 
 

SPECIFICATIONS 

  

 

 

Analog Inputs High Resolution 

Steady State Current 

Consumption 

120mA @ 24v 

Number of Channels

 

4 (577) or 8 (977) 

Input Ranges 

  0 to 10 VDC 

0 to 5 VDC 

 0 to 20 mA 

– 20 mA 

Safe input voltage range 

-0.5 to +30 V 

Isolation 

3K VDC 2.5K VAC Test 

IEC61010-1 400V RMS

 

Input Impedance 

 

Current Mode: 

55 

 

Voltage Mode: 

1 meg 

 

Nominal Resolution 

16 Bits 

%AI full scale 

32,000 counts 

Max. Over-Current 

35 mA 

Max. Error at 25

(excluding zero)

 

0.1% 

Additional error for 

temperatures other than 25

TBD 

Filtering 

16 Hz hash (noise) filter 

1-128 scan digital running average 

filter 

 

 

 

 

ANALOG OUT 

Number of 
Outputs 

2 (577) or 4 (977) 

Isolation (Power to 
Analog Output) 

3K VDC 2.5K VAC Test

 

IEC61010-1 400V RMS 

Output Ranges 

0-5V, 0-10V DC 

4-20mA, 0-20mA DC 

Isolation Method 

Magnetic 

Resolution 

14 bits 

Output Clamp  

+24V -.5V, 600Wpk 

Accuracy, 25°C 

0.1% 

Output Type 

Sourcing 

Load Resistance 

V: 500 ohms Min 

mA: 500 ohms Max 

Register Value for 
Nominal Full Scale 

32000 

 
 
 

General Specifications 

Voltage Input

 

10-30 VDC 

Relative Humidity 

5 to 95% Non-condensing 

Required Power 

(Steady State) 

4W (150mA @ 24VDC) 

Required Power 

(Inrush) 

DC Switched: 12A 50uS 

AC Switched: 120mA 10mS  

Operating Temperature 

0

 to 60

 Celsius 

Weight 

12oz/340g 

 

SmartBlock I/O Module 

HE579MIX577/977 Isolated 

4/8 Analog Inputs 2/4 Analog Outputs 

Содержание SmartBlock HE579MIX577

Страница 1: ... filter 1 128 scan digital running average filter ANALOG OUT Number of Outputs 2 577 or 4 977 Isolation Power to Analog Output 3K VDC 2 5K VAC Test IEC61010 1 400V RMS Output Ranges 0 5V 0 10V DC 4 20mA 0 20mA DC Isolation Method Magnetic Resolution 14 bits Output Clamp 24V 5V 600Wpk Accuracy 25 C 0 1 Output Type Sourcing Load Resistance V 500 ohms Min mA 500 ohms Max Register Value for Nominal Fu...

Страница 2: ...on into a grounded back plate Alternately a ground can be connected to the spade lug Please see Horner manual MAN0799 for details on CAN wiring CAN Network Power Port Pin Assignments Pin Signal Signal Description Direction 1 V CAN and Device Ground Black 2 CN_L CAN Data Low Blue In Out 3 SHLD Shield Ground None 4 CN_H CAN Data High White In Out 5 V Positive DC Voltage Input 10 30VDC Red 2 16 54 8m...

Страница 3: ...Mix577 977 Module 3 WIRING V1 I1 C V2 I2 C V3 I3 C V4 I4 C O1 C O2 C V5 I5 C V6 I6 C V7 I7 C V8 I8 C O3 C O4 C 977 Only Ox C Load Channel wiring detail with shielded cable INPUTS V V1 C I1 No Connection 10V V1 C I1 20mA ...

Страница 4: ... the device to be configured Below is the configuration for MIX577 977 device Network ID This should match the ID of the rotary switch on the SmartBlock unit and should be unique to the network I O Mapping These registers define how the OCS controller registers are mapped to the data to and from the SmartBlock I O These registers do no have to match the I O types typically used for I O such as AI ...

Страница 5: ...ar the PLC This does not affect open thermocouple detection or measurement accuracy and reduces the effect of common mode noise if present This PLC side ground connection must not be used with grounded thermocouples or accuracy will be affected Any thermocouple should be grounded in one place at most When found on the product the following symbols specify All applicable codes and standards need to...

Страница 6: ...uipment including safety glasses and insulated gloves when making connections to power circuits Ensure hands shoes and floor are dry before making any connection to a power line Make sure the unit is turned OFF before making connection to terminals Make sure all circuits are de energized before making connections Before each use inspect all cables for breaks or cracks in the insulation Replace imm...

Отзывы: