MAN0980-01-EN

          

Specifications/Installation 

10/29/2013                                   

No part of this publication may be reproduced without the prior agreement and written permission of Horner APG, LLC. Information in this document is subject to change without notice.

  

Page 

4

 of 

5

 

5.  NETWORK DATA

 

 

Consumed Digital Data

 

– This data is sent from the controller to the SmartBlock. For typical applications, the I/O configuration setup in 

Cscape will automatically populate this data. For more advanced applications, you may use NetPut functions to write this data. Please 
see the advanced programming guide 

MAN0880

 for more details.

 

Bit 

Description 

1-8 

Digital Outputs 

Bits that control the relay or DC outputs 

9-64 

Reserved 

65-72 

Output Hold 

1 = Hold on stop, 0 = Override 

73-79 

Reserved 

80 

Positive/Negative Inputs 

0 = Positive Logic, 1 = Negative Logic 

81-96 

Reserved 

97-104 

Output Override Data 

Output on stop when hold = 0 

105-120 

Reserved 

 

Produced Digital Data

 

– This data is sent from the SmartBlock to the controller. Normally this data is mapped into specific registers in 

the I/O configuration in Cscape. For advanced applications, NetGet functions can be used to obtain this data. Since this data is 
broadcasted to all controllers on the network, additional controllers can use NetGet functions to obtain this data as well. 

Bit 

Description 

1-8 

Digital Inputs 

Data from the digital inputs 

HE579DIQ881 

0 = OK, 1 = Fault on output channels 1-4 

10 

HE579DIQ881 

0 = OK, 1 = Fault on output channels 5-8 

11-32 

Reserved 

33-48 

Status & Diagnosis Data 

49-56 

Firmware Version 

57-64 

Device Class 

 

6.  SETTING ID SWITCHES 

 

CsCAN Network IDs are set using the hexadecimal number system from 01 to FD.  The decimal equivalents are whole numbers 1-253.  
Refer to following Conversion Table, which shows the decimal equivalent of hexadecimal numbers.  Set a unique Network ID by 
inserting a small flat-bladed screwdriver into the two identical switches. 

NOTE:

  The CsCAN Baud Rate for SmartBlock I/O is fixed at 125KBaud 

 

 

 

Содержание SmartBlock HE579DIQ880

Страница 1: ...rt circuit Overtemp Automatic Reset Operating Temperature 0 to 60 C Max Switching Rate Limited by message rate Weight 12 oz 340 g 24VDC Supply Voltage NOTES A I O common pins C are internally connected to the power supply negative B Digital inputs are configurable for positive or negative logic using Cscape C When configured for positive logic the inputs are pulled down to common by a 10K resistor...

Страница 2: ...eproduced without the prior agreement and written permission of Horner APG LLC Information in this document is subject to change without notice Page 2 of 5 3 INTERNAL WIRING Figure 1 HE57DIQ880 Outputs Figure 2 He579DIQ881 Outputs Figure 3 HE57DIQ880 881 Inputs Positive Logic Negative Logic ...

Страница 3: ...the I O types typically used for I O such as AI Q Any standard controller registers may be used such as R T and M Input Update Method Defines how often analog data is sent from the SmartBlock to the CsCAN network Digital data is transmitted on change of state by default Timeout Sets the time a controller will wait before assuming the host OCS is off line Status The host controller reports a 16 bit...

Страница 4: ...hold 0 105 120 Reserved Produced Digital Data This data is sent from the SmartBlock to the controller Normally this data is mapped into specific registers in the I O configuration in Cscape For advanced applications NetGet functions can be used to obtain this data Since this data is broadcasted to all controllers on the network additional controllers can use NetGet functions to obtain this data as...

Страница 5: ...NING In the event of repeated failure do not replace the fuse again as a repeated failure indicates a defective condition that will not clear by replacing the fuse WARNING Only qualified electrical personnel familiar with the construction and operation of this equipment and the hazards involved should install adjust operate or service this equipment Read and understand this manual and other applic...

Отзывы: