MAN0090-05 

06 December 2004 

PAGE 5 

Route power wires in a safe manner in accordance with good practice and local codes. 
 
Wear proper personal protective equipment including safety glasses and insulated gloves when making 
connections to power circuits.  
 
Ensure hands, shoes, and floor are dry before making any connection to a power line.  
 
Make sure the unit is turned OFF before making connection to terminals.  Make sure all circuits are de-
energized before making connections.  
 
Before each use, inspect all cables for breaks or cracks in the insulation.  Replace immediately if 
defective.  
 
 
 

TECHNICAL ASSISTANCE 

 
For manual updates and assistance, contact Technical Support at the following locations: 
 

North America:   

(317) 916-4274 
www.heapg.com  
email:  [email protected] 
 

Europe:  

(+) 353-21-4321-266 
www.horner-apg.com 
 
 

Содержание HE693THM166

Страница 1: ... temperature values may be reported to the PLC AI I O table in 0 5 C or 0 5 F increments This module features open circuit detection where the AI register goes to its maximum value upon an open circuit condition and a corresponding I bit is energized Field wiring is connected to a special high density 32 position removable terminal block Recommended wire size is 24 AWG Figure 1 HE693THM166 Front V...

Страница 2: ...ode Rejection 100dB A D Conversion Type Integrating Input Range Temp X 210 to 1200 C 2 C Maximum Reading not guaranteed below 200 C N 270 to 1300 C R 0 to 1768 C C 0 to 2320 C A D Conversion Time 40 channels per second Resolution 0 5 C or 0 5 F Operating Temperature 0 to 60 C 32 to 140 F Accuracy 0 5 C typical J K N T Relative Humidity 5 to 95 non condensing NOTE Model F and later support the Exte...

Страница 3: ...ets the thermocouple type The effect of digital filtering set with Byte 2 on module response to a temperature change temp change completed vs time Table 3 Temperature Scaling Byte 3 Formula 0 C AI 2 1 F AI 2 Temperature values are written to the AI registers in 0 5 C or 0 5 F increments depending upon the value of Byte 3 0 10 20 30 40 50 60 70 80 90 100 0 2000 4000 6000 8000 Temperature Change Com...

Страница 4: ... twisted pair extension wiring offers best noise immunity If shielded wiring is used a good earth ground connection is critical Recommended wire size for terminal strip is 24 AWG Adhere to the following safety precautions whenever any type of connection is made to the module Connect the green safety earth ground first before making any other connections When connecting to electric circuits or puls...

Страница 5: ...aking any connection to a power line Make sure the unit is turned OFF before making connection to terminals Make sure all circuits are de energized before making connections Before each use inspect all cables for breaks or cracks in the insulation Replace immediately if defective 6 TECHNICAL ASSISTANCE For manual updates and assistance contact Technical Support at the following locations North Ame...

Страница 6: ...PAGE 6 06 December 2004 MAN0090 05 NOTES ...