Table 2 – Configuration Parameters 

Byte 

%AI 
Size 

%I 

Size 

0:0.5

°

00: J 

03: T 

06: S 

01: K 

04: E 

07: B 
08: C 

16 

16 

(see 

chart) 

1:0.5

°

02: N 

05: R 

09: X 

 
Byte 2 sets digital filtering, Byte 3 sets temperature units, and Byte 5 sets the thermocouple type. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
The effect of digital filtering (set with Byte 2) on module response to a temperature change. (% temp 
change completed vs. time). 
 
 

Table 3 – Temperature Scaling 

Byte 3 

Formula 

°

C = %AI / 2 

°

F = %AI / 2 

 
Temperature values are written to the %AI registers in 0.5°C or 0.5°F increments, depending upon the 
value of Byte 3. 
 

0

10

20

30

40

50

60

70

80

90

100

0

2 0 0 0

4 0 0 0

6 0 0 0

8000

% Temperature Change Completed

 

Response Time (Milliseconds) 

Figure 4 - Digital Filtering 

Содержание HE693THM166

Страница 1: ... temperature values may be reported to the PLC AI I O table in 0 5 C or 0 5 F increments This module features open circuit detection where the AI register goes to its maximum value upon an open circuit condition and a corresponding I bit is energized Field wiring is connected to a special high density 32 position removable terminal block Recommended wire size is 24 AWG Figure 1 HE693THM166 Front V...

Страница 2: ...ode Rejection 100dB A D Conversion Type Integrating Input Range Temp X 210 to 1200 C 2 C Maximum Reading not guaranteed below 200 C N 270 to 1300 C R 0 to 1768 C C 0 to 2320 C A D Conversion Time 40 channels per second Resolution 0 5 C or 0 5 F Operating Temperature 0 to 60 C 32 to 140 F Accuracy 0 5 C typical J K N T Relative Humidity 5 to 95 non condensing NOTE Model F and later support the Exte...

Страница 3: ...ets the thermocouple type The effect of digital filtering set with Byte 2 on module response to a temperature change temp change completed vs time Table 3 Temperature Scaling Byte 3 Formula 0 C AI 2 1 F AI 2 Temperature values are written to the AI registers in 0 5 C or 0 5 F increments depending upon the value of Byte 3 0 10 20 30 40 50 60 70 80 90 100 0 2000 4000 6000 8000 Temperature Change Com...

Страница 4: ... twisted pair extension wiring offers best noise immunity If shielded wiring is used a good earth ground connection is critical Recommended wire size for terminal strip is 24 AWG Adhere to the following safety precautions whenever any type of connection is made to the module Connect the green safety earth ground first before making any other connections When connecting to electric circuits or puls...

Страница 5: ...aking any connection to a power line Make sure the unit is turned OFF before making connection to terminals Make sure all circuits are de energized before making connections Before each use inspect all cables for breaks or cracks in the insulation Replace immediately if defective 6 TECHNICAL ASSISTANCE For manual updates and assistance contact Technical Support at the following locations North Ame...

Страница 6: ...PAGE 6 06 December 2004 MAN0090 05 NOTES ...

Отзывы: