Table 2 – Configuration Parameters
Byte
%AI
Size
%I
Size
1
2
3
4
5
0:0.5
°
C
00: J
03: T
06: S
01: K
04: E
07: B
08: C
16
16
1
(see
chart)
1:0.5
°
F
0
02: N
05: R
09: X
Byte 2 sets digital filtering, Byte 3 sets temperature units, and Byte 5 sets the thermocouple type.
The effect of digital filtering (set with Byte 2) on module response to a temperature change. (% temp
change completed vs. time).
Table 3 – Temperature Scaling
Byte 3
Formula
0
°
C = %AI / 2
1
°
F = %AI / 2
Temperature values are written to the %AI registers in 0.5°C or 0.5°F increments, depending upon the
value of Byte 3.
0
10
20
30
40
50
60
70
80
90
100
0
2 0 0 0
4 0 0 0
6 0 0 0
8000
% Temperature Change Completed
Response Time (Milliseconds)
Figure 4 - Digital Filtering