HORNE T105A Скачать руководство пользователя страница 1

Horne Engineering Ltd 

Issue 7, November 2018 

 

 

 

 

1

 

 

Horne Engineering Ltd 

Po Box 7, Rankine Street 

Johnstone, Renfrewshire 

Scotland, PA5 8BD 

Tel: 01505 321455 

Fax: 01505 336287 

Email: 

[email protected]

 

Web: www.horne.co.uk

 

HORNE T105A/106A/107A/108A THERMOSTATIC SHOWER PANEL 

FOR SURFACE MOUNTING WITH DUAL CONTROLS 

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS 

Note that these instructions feature the T108A shower panel. The T105A, T106A and T107A feature the 
same TSV1-3 thermostatic valve but differ in the water outlet fittings.  All comments relating to the T108A 
also apply to the other shower panels mentioned above and their variants. 

Approvals 

The TSV1-3 Thermostatic Shower valve has been independently tested by WRc-NSF and approved to all 
the requirements of NHS Model Engineering Specifications D08 Thermostatic Mixing Valves (Healthcare 
Premises) to the following designations and for the following applications: 

HP-S 

Shower with supply pressures of 1 

– 5 bar and unrestricted flow rate 

LP-SE 

Shower with supply pressures of 0.2 

– 1 bar and unrestricted flow rate 

Supply Water Pressure requirements 

The minimum water pressure required to achieve a spray at the spray head is a dynamic head of 2m (3 
psi, 0.2 bar) at the spray head.  Note that for very low head installations, both hot and cold water supplies 
must be at the same pressure. 

Note that dynamic head is measured with the water running. 

Where  the  TSV1-3  panel  is  fed  by  supplies  with  differing  pressures,  use  the  following  to  determine 
whether  a  pressure-reducing  valve  (PRV)  is  required  on  the  side  with  the  higher  pressure.    Note  that 
output flow-rate is always determined by the lower of the two inlet pressures.  If the lower inlet pressure is 
low enough (typically 0.2 to 1Bar dynamic) that the flow-regulator in the outlet fitting (see pages 11,12,13) 
can be removed, then a PRV should not be required.  If the lower of the 2 supply pressures is higher than 
around 1Bar, then a flow-regulator will be required to restrict flow.  If the flow-regulator is needed, and the 
supply pressures are substantially unbalanced, then a PRV will also be needed to prevent pulsing of the 
flow.  Although thermostatic performance is unaffected by this, the flow pulsing is undesirable. 

 

High Pressure 

Low Pressure 

Maximum Static Pressure  

10 bar 

10 bar 

Flow Pressure, Hot & Cold 

1 to 5 bar 

0.2 

– 1 bar 

Hot Water Supply Temperature 

52 

– 65C 

52 

– 65C 

Cold Water Supply Temperature 

– 20C 

– 20C 

Minimum Temperature Differential 

(Hot 

– Mixed, Mixed – Cold) 

5K 

(K = degrees C) 

5K 

(K = degrees C) 

Temperature Adjustment Range 

The mixed water temperature can be adjusted from cool through to a top limit (which can be preset during 
installation 

– factory set to approx. 41°C - with full anti-scald protection throughout the range). 

 

Water and Energy Conservation 

The TSV1 range shower panels are fitted at the factory with flow regulators at the shower outlet to reduce 
the flow rate and conserve water and energy.  The drawings at the end of this document provide 
information for accessing the flow restrictors/regulators for removal or replacement. 

Содержание T105A

Страница 1: ...fed by supplies with differing pressures use the following to determine whether a pressure reducing valve PRV is required on the side with the higher pressure Note that output flow rate is always det...

Страница 2: ...head shown p13 Bottom of panel should be 1 1 metres from finished floor level 1 Position the Pre Plumbed Enclosure Identify a suitable position for the Enclosure and mark a line on the wall level wit...

Страница 3: ...screw and being careful not to scratch the enclosure or its covers lay it down where it will not be damaged Drill the 4 holes and install the wall plugs 6 Attach the Pre Plumbed Enclosure to the Wall...

Страница 4: ...rk in accordance with Water Bylaws 2000 Scotland and BS 6700 1997 England Wales The use of a Horne flushing kit is strongly recommended because this connects directly to the water inlets to the mixing...

Страница 5: ...before the pre plumbed enclosure is attached to the wall Accordingly point 7 on the attached installation instructions Connect the Supply Pipes should be performed before point 6 Attach the Pre Plumbe...

Страница 6: ...ve the set temperature In either case there is no scalding risk If the temperature rises above this then it is likely that there is contamination in the TSV1 3 that is preventing it from shutting off...

Страница 7: ...2 5 Nm Ensure the on off assembly is torqued down to 25 Nm 34 lbft to prevent the user from inadvertently unscrewing the assembly during flow control Do not over tighten the assembly The Check Valves...

Страница 8: ...efore performing this test If mixed water continues to flow and is coming from the showerhead at a temperature of more than 2 C above the maximum mixed water temperature setting then the TSV1 3 is due...

Страница 9: ...fter commissioning If small adjustments 1 to 2 K are required then check the strainers for cleanliness make sure the isolating valves are fully open and verify the check valves are operating correctly...

Страница 10: ...Horne Engineering Ltd Issue 7 November 2018 10...

Страница 11: ...Horne Engineering Ltd Issue 7 November 2018 11...

Страница 12: ...Horne Engineering Ltd Issue 7 November 2018 12...

Страница 13: ...Horne Engineering Ltd Issue 7 November 2018 13...

Страница 14: ...Max Mixed Water Temp during CW Isolation test C Mixed Water Temp on restoration of CW Supply C Note MWT should return within 2 degrees of set temp and be no greater than 43C after this test Comments...

Страница 15: ...y C Note MWT should return within 2 degrees of set temp and be no greater than 43C after this test Comments Recommended Date of Next In Service Test In Service Testing Record Establishment Location of...

Страница 16: ...ng Ltd Issue 7 November 2018 16 Brochure Ref L 189 T10XA Horne Engineering Ltd PO Box 7 Rankine Street Johnstone SCOTLAND PA5 8BD Tel 44 0 1505 321455 Fax 44 0 1505 336287 Email Technical horne co uk...

Отзывы: