Commissioning Procedure
Installed correctly the burner should not emit any
fumes into the room. The following procedure should be
undertaken to test that the unit is operating correctly.
1 After unit has been operating for a short period a
smoke match, smoke tube, carbon dioxide analyser or
similar should be directed at the top opening of the unit.
2 This procedure should be undertaken with the following
conditions in the room:
• Open or closed windows
• Operation of extraction/exhaust fans, range hoods etc
• Operation of other gas appliances
• Operation of optional appliance fan at any speed.
3 Should any spillage be detected the cause must be
rectified before allowing commissioning of unit.
4. Please test appliance operation before leaving.
2 Initially the Kemlan coal fire may burn with a
slightly blue flame. After approximately 20 minutes
the fire will settle down and burn with a yellow flame.
3 As with all gas fires your gas coal/pebble or log
fire should be regularly serviced. We recommend
once each year. Service information for an
authorised person to follow has been set out in
attached leaflet.
4 PLEASE NOTE: Only logs provided by
Kemlan should be used with this appliance.
5 DO NOT place articles on or against this
appliance.
DO NOT use or store flammable materials near
this appliance.
DO NOT spray aerosols in the vicinity of this
appliance whilst it is in operation.
DO NOT modify this appliance.
Primarily a decorative appliance not certified as a
space heater.
6 The appliance is a live fuel effect product
designed to operate with luminous flames and may
exhibit slight carbon deposition.
7. The guard is fitted to this appliance to reduce the
risk of fire or injury from burns and no part of it
should be permanently removed.
SERVICE - WARNING: ONLY TO BE SERVICED
BY AN AUTHORISED PERSON
Warranty
Provided the appliance has been correctly
installed according to instructions, Kemlan guarantee
the cost of replacing parts and the labour in
connection therewith for a period of 12 months from
the date of installation.
User Instructions
1. WARNING NOTE:
Properly installed and
operated this appliance will not leak gases. Persistent
fume emission must not be tolerated. If fume emission
does exist, then the following immediate action should
be taken.
A Open doors and windows to ventilate room. B Turn
the fire off.
C Check for flue blockage and clear if necessary.
D Do not attempt to relight the burner until the cause
of the emission has been identified and rectified.
Should assistance be required contact nearest agent.
E The gas burner is designed to work in a Kemlan
Horizon electronic power flue ignition system.
Working correctly there will be no spillage. Unit should
cut out if not enough draw to ensure proper
functioning.