Power Flue with External Fan
SILENCER
8
” x 900
REDUCER
7” – 6”
8” – 6”
9” – 6”
10” – 6”
12” – 6”
14 ”-- 6”
WALL MOUNTED
FAN
2x 8” 45 DEG
12” – 8”
REDUCING CAP
6
” x 900
12.5” x 900
Installation Instructions Kemlan Power Flue Horizon Gas Fireplaces
2x 6” 45 DEG
12.5” x 200 VENTED FLUE
10MM GAP BETWEEN
END OF FLUE TO WALL
Note:
Power flue Horizontal runs greater than 5 meters in length may be compromised by
fluctuations in power. Flue runs greater than 5 meters when tested with underload power
of 15% caused the fan to cut out and burner to turn off and require resetting.
Resetting can be done by turning power off and on. Should power be consistent in supply
then longer flue runs can be recommended and burner will perform correctly.
28/02/2019
Ver. 25
11