Installation Instructions Kemlan Natural Draft Electronic Ignition Gas Fireplaces
PROBLEM
PILOT WILL NOT
LIGHT WITH FAN WORKING
FAN DOES NOT TURN ON
FAN COMES ON. PILOT ON.
MAIN BURNER DOES NOT
LIGHT
FLAME FAIL LOCKOUT UNIT
HAS DETECTED LOSS OF
FLAME AND LOCKED OUT
POSSIBLE CAUSE
1)NO GAS
2)NO SPARK AT PILOT
1)POWER SUPPLY
1)FLAME SENSOR NOT
SENDING SIGNAL TO OPEN
VALVE
2)MODULE NOT SENDING
SIGNAL TO OPEN VALVE
3)FAULTY VALVE
1)POWER FAILURE
2)GAS SUPPLY
3)DIRTY ELECTRODE
4)PILOT BLOCKED
5)PRESSURE SWITCHES
CORRECTIVE ACTION
•
CHECK FOR GAS SUPPLY AND TURN ON
ALL CONNECTIONS
•
CHECK GAS PRESSURE
•
CHECK PILOT AND CLEAN INJECTOR
•
CHECK ALL CONNECTIONS
•
CHECK SPARK ELECTRODE
CONNECTIONS AND REPLACE
ELECTRODE IF DAMAGED.
•
CHECK SOLENOID CONNECTIONS AT
VALVE
• CHECK PRESSURE SWITCH FUNCTIONS IN
FAN. Note :flash codes/red LED for pressure
switch functions on module.
• TURN ON ALL POWER SWITCHES
•
CHECK ALL CONNECTIONS
• CHECK FAN ON INDEPENDENT POWER
SWITCH
•
CHECK ELECTRODE IS IN PILOT FLAME
•
CLEAN ELECTRODE
•
CHECK ELECTRODE CONNECTIONS
•
REPLACE ELECTRODE IF DAMAGED
•
CHECK CONNECTIONS
•
REPLACE MODULE
•
REPLACE VALVE
• TURN ON/OFF SWITCH OFF AND ON AGAIN
TO RESET ONCE POWER ESTABLISHED
•
CHECK GAS PRESSURE AND ADJUST
• RESET AT ON/OFF SWITCH
•
CLEAN ELECTODE OR REPLACE
•
CLEAN PILOT INJECTOR
• NOTE:FLASH CODES (RED LED) WITH
ENCLOSED INSTRUCTIONS TO IDENTIFY
PRESSURE SWITCH PROBLEMS.
Service Instructions for Direct Ignition and Power Flue
Horizon fireplaces
POWER FLUE SERVICE INSTRUCTIONS