Connection terminals
To access the connection terminal the cover of the housing needs to be removed by loosening the four plastic
screws.
Error states
The following error stated can be detected by the pump- and control unit (refer to Table 1):
Maintenance
The pump motor and the control unit of the Electrolyte Circulation System are maintenance free. However
HOPPECKE recommends replacing the air intake filter every year.
Error
Cause
Indication
Error Correction
Pump is switched off
because air pressure ist
not reached.
Detached or leaking air
tubes.
Pump is switched off,
red LED flashes 1x.
Check tube connections
and remove fuses for a
few seconds an insert
again.
Pump is switched off
because operating tem-
perature is > 65 °C.
E.g. pump- and control
unit is exposed to direct
sunlight.
Pump is switched off,
red LED flashes 2x.
Pump will start again
automatically once the
temperature has fallen
below ca. 60 °C.
Table 1: Error states