3.6.4.5.6.11.4 Initialization String for IEC-103 (ASDU Type 6)
This initialization string is sent with ascending IEC address every second unless the minute
change. The IEC address is continuously repeated from 1 to a selectable value of maximal
254 ($01-$FE). Setting up the IEC address is done via S6 and S5.
Disable the initialization string:
•
Setting S6 and S5
Settings for Initialization String IEC-103
To be set with special settings S6 and S5:
B7
B6
B5
B4
B3
B2
B1
B0
DEZ
HEX
Notes to S6 & S5
0
0
0
0
0
0
0
0
0
$00
S6=1, S5=1 (deactivated)
0
0
0
0
0
0
0
1
1
$01
:
:
:
:
:
:
:
:
:
0
0
1
1
1
1
0
1
63
$3F
S6=1, S5=0
:
:
:
:
:
:
:
:
:
0
1
1
1
1
1
1
1
127
$7F
S6=0, S5=1
:
:
:
:
:
:
:
:
:
1
1
1
1
1
1
0
1
253
$FD
1
1
1
1
1
1
1
0
254
$FE
S6=0, S5=0 (max value)
Structure IEC-103
Character no.
Meaning
Hex Value
1
Start flag
10
2
Control field
47
3
IEC-Address
$01-$FE
4
Checksum (sum of fields 2 & 3 mod 256)
$00-$FF
5
End flag
16
Example
The length of data string consists of 5 characters. Just binary values are sent.
The hexadecimal values of the transmitted characters are stated:
<10><47>
<01>
<48><<16>
(String initializes unit with the address 01)
<10><47>
<02>
<49><<16>
:
<10><47>
<0F>
<56><<16>
<10><47>
<10>
<57><<16>
:
<10><47>
<FE>
<45><<16>
(String with maximal valid address)