OPERATION
Before starting up the KAP, check all fasteners for tightness and be sure to check
the module connection seal and door seals. With power to the fan shut off, check
the airflow direction of the filters to match the label on the filters.
START-UP TOOLS REQUIRED:
1. Standard Hand Tools
2. Static Pressure Meter
START-UP PROCEDURE:
1. Check duct connections to inlet and outlet of unit for proper welds.
2. Check that entire duct system is intact and that all clean-out doors are
properly installed.
3. Install all filters in correct direction
4. Start fan and check for rotation, voltage and proper operation.
5. Inspect entering & exiting ductwork connections and grease duct for
leaks or pinholes (grease rated duct must be continuously welded to
the transition, if factory provided).
6. Inspect all fire suppression piping and components.