Honeywell Zio TR70 Скачать руководство пользователя страница 7

ZIO

®

/ZIO PLUS LCD WALL MODULES

7

63-2719—03

PARAMETER TYPES AND LIMITS

See Fig. 12 for an illustration of the Parameter Type drop 

down list. There is a limit to the number of parameters that can 

be configured. In addition to the parameter limit, there is also a 

memory limit (see “Memory Usage” on page 4).

Fig. 12. Parameter Type selection.

The individual parameters are defined as:

— Controller Value

• These are read-only inputs to the wall module from 

the controller and include system status and 

occupancy status, if configured. Controller Value 

parameters take up less memory than other 

parameters.

— Value From Wall Module

• These are outputs from the wall module such as 

room setpoint.

— Network Setpoints

• A network setpoint is a network variable from the 

controller that you want to view and change at the 

wall module.

— Sensors

• 2 sensors (Temperature and Humidity)

• 2 Sensor Offset Values (temperature and humidity)

See Table 5 for the individual parameter maximums.

IMPORTANT

You can not maximize all of these parameters 

together. The size of the data files limits the total 

number. See the memory usage tool by clicking on 

the Memory Usage Details button in the left pane of 

the Configuration Wizard.

* The TR71/TR75 may vary from these capacity numbers 

depending on label names, parameter limit reuse, and other 

devices that Zio interacts with on the Sylk bus.

NOTE: Network Variables need to be linked to the appropri-

ate S-Bus wall module’s function block slots. See 

“Link Slots on the Wire Sheet” on page 18 for details.

PARAMETER OPTIONS

The TR71 and TR75 support additional parameter control. 

See Table 1 on page 2 for details.

ENUMERATED VALUES

Meaningful enumerated values can be displayed using the 

Enumerated option.

From the Add/Edit parameter window check the Enumerated 

box and click on the Define Enum Range as shown in Fig. 13. 

Fig. 13. Click on the Enumerated Checkbox, then the Define 

Enum Range button.

Once in the Zio Enum Library dialog box (Fig. 14), click on the 

dropdown to see pre-defined facets or define your own. For 

more detailed information see the online help in the 

Configuration Wizard.

Table 5. TR70 Series Parameter Capacity Guidelines.*

Parameter Type

TR70

TR71

TR75

Controller Value

30

95

250

Value From Wall Module

20

50

180

Network Setpoints

10

50

125

Содержание Zio TR70

Страница 1: ... three softkeys and two Up Down adjustment keys Models with H also include an onboard humidity sensor PREFACE This Operating Guide is intended to provide configuration information using the Niagara Workbench tool and a general overview of the TR70 Series operator interface Configuration begins with Initial Power Up on page 2 and the general overview begins with Operating the Zio Wall Module on pag...

Страница 2: ...Wall Module LCD screen The new Spyder tool 6 0 or greater assumes the latest Spyder capability At download the Tool reads the brand model of the connected Spyder and determines if it matches the features on the wire sheet If old or new Spyder is programmed with aTR70 it can be physically replaced with a TR71 or TR75 Table 1 TR70 Series Features Features Zio TR70 Zio TR71 ZioPlus TR75 Scheduling x ...

Страница 3: ...ation and Memory Usage The Honeywell Spyder Tool uses an intuitive window based interface A Help button on each screen provides assistance with any entry or process IMPORTANT Use the Help button to display context specific help for the current window or pane display See the lower left corner of Fig 6 on page 5 for the location of the Help button NOTE At any time clicking the Preview button lower l...

Страница 4: ...gories should be below 100 See Fig 4 on page 4 NOTE For a single Zio memory usage must be equal to or less than 100 in order to download the configura tion to the programmable controller If using multiple Zios you should also check the Spyder Resource usage Total Zio memory use is limited to 5K bytes on Spyder View the online help in the WEBs AX Workbench to see troubleshooting tips for reducing m...

Страница 5: ...can use the Remove button to delete unused categories and parameters to free up memory space Fig 7 Category Preview CATEGORY DETAILS When you select a category from the Categories tree list and click the Edit button a details pane displays for that category see Fig 8 on page 6 Here you can enter a category name and description The number of parameters in this category are shown The description tex...

Страница 6: ...rameter from the tree list and click the Edit button a details pane displays for that parameter Here you can select Viewable by Tenant and Editable by Tenant As an example Fig 10 shows the Details for the ROOMTEMP parameter Here you would enter the description select the parameter type from its drop down list enter the decimal accuracy default sensor offset value temperature units and select the d...

Страница 7: ...the data files limits the total number See the memory usage tool by clicking on the Memory Usage Details button in the left pane of the Configuration Wizard The TR71 TR75 may vary from these capacity numbers depending on label names parameter limit reuse and other devices that Zio interacts with on the Sylk bus NOTE Network Variables need to be linked to the appropri ate S Bus wall module s functi...

Страница 8: ... related unoccupied heat setpoint parameter as the low limit and the occupied cooling setpoint parameter as the high limit To assign a setpoint to another setpoint s high or low limit click on the Browse button next to the Low Limit or High Limit field From the Select Parameter dialog box you can select the appropriate setpoint This feature is an alternative to assigning a numeric value in the Hig...

Страница 9: ...ome screen to be the initial Home screen for the wall module after the configuration is downloaded to the wall module The Description text you enter allows more information to be entered on the home screen and will be loaded to the controller but cannot be previewed Use the Option Type selection to choose either single or multiple 1 to 3 parameters to display on the Home screen For the Single Para...

Страница 10: ... Settings button for the Valid States That You Can Override section opens the Override to Occupied Settings dialog box where you can configure values to any desired number from 0 to 255 To conserve Zio memory choose the same Override Type and Timed Override Details for Occupied Unoccupied and Standby Fig 17 Occupancy and Override screens OCCUPANCY STATUS DISPLAY OPTIONS Here you select how the ove...

Страница 11: ...ils will be determined by the programmable controller configuration This option only applies to Occupancy override settings Unoccupied and Standby do not use bypass ADVANCED SETTINGS When the Show Advanced Settings button is clicked overrides to Occupied Unoccupied and Standby options are possible The Override to Unoccupied selection s Settings button displays pop ups similar to the Override to Oc...

Страница 12: ...the fan commend is a network setpoint then the default value is set on the controller s network setpoint The Fan command value cannot be changed from Zio in the Contractor mode After you choose the setting use the Fan Command Preview at the bottom of the window to exercise the Fan softkey to cycle through the options If the Set as Network Setpoint box is checked for the TR71 TR75 the Preview scree...

Страница 13: ...the top of the wall module s LCD screen For TR71 TR75s click on the System Command checkbox to allow the System Command to be configured as a network setpoint The default System Command option is Off Heat Heat Only The System commands are selectable The System command value cannot be changed from Zio in the Contractor mode After you choose the setting use the Preview button at the bottom of the wi...

Страница 14: ... or not the tenant can view or edit etc We recommend setting the time in Spyder before configuring the Schedule Time in the configuration tool NOTE Setting an invalid time at Zio will cause Spyder to set the time to invalid You also have the ability to configure how the Spyder schedule will display at the TR75 8 day schedule 7 day schedule 5 2 1 day schedule or the 5 2 schedule If using the 5 2 1 ...

Страница 15: ...tem changes from the TR71 TR75 The password option is not available for the TR70 The password can be assigned an eight character label that is displayed at the TR71 TR75 and a four digit password from 0000 to 9999 All TR71 TR75s on a Spyder can have the same or unique passwords If the password option is enabled and the password is forgotten it can be retrieved through the WEBs AX Workbench in the ...

Страница 16: ...ey rectangles below the labels of the preview display exercises the features you have configured NOTE Since the up and down arrow keys do not display in Preview mode no adjustments to parameters e g setpoint temperature can be made Fig 24 shows your current configuration of the wall module Home screen You can select either the Tenant or Contractor view The three softkeys in the preview LCD display...

Страница 17: ...o see how the wall module LCD screen will operate for your selected configuration see Preview on page 16 Confirm Memory Usage is within Limits To view the current memory use information click on the Memory Usage Details button A new window opens and displays a a bar graph indicating the percentage of current memory used in each memory category Each of the memory categories should be below 100 You ...

Страница 18: ...see an example in Fig 26 A maximum of four Zios may be wired on a single Sylk bus with no more than one TR70 per bus When making links from existing blocks to the wall module function block input slots there is no need to break the existing links from these existing blocks The new tool allows for multiple output connections When connecting to slots on function blocks which lie on different wire sh...

Страница 19: ...gate from one digit to the next Fig 28 Password entry screen Contractor Mode Operation Contractor mode allows advanced options such as modifying configured parameters using the softkeys Contractor mode also allows for customizing the tenant s view including setting the tenant s Home screen and controlling the tenant s View More access which can provide the tenant with a view of the configured para...

Страница 20: ...ey moves to the next parameter Click the DONE softkey when finished The CANCEL softkey exits VIEW MORE without saving changes to that parameter Fig 31 Set View More parameter display PARAMETERS allows the contractor to monitor and or adjust parameters in the programmable controller Clicking the PARAMETERS softkey displays the first configured category as shown in Fig 31 and the softkeys change to ...

Страница 21: ... Schedule option lets you modify the schedule and change Spyder s time The desired scheduling option 8 day 7 day etc is setup in the Configuration Wizard see Wall Module Configuration on page 4 and based on that selection option screens vary The example below shows the flow for viewing editing a schedule Use the Edit softkey to move to the next screen and use the up down arrows to change values Wh...

Страница 22: ... softkey does not display on the tenant s Home screen 3 If there are no parameters configured for tenant access the VIEW MORE softkey does not display on the tenant s Home screen FAN allows the tenant to adjust the fan settings depending on the fan options 2 3 or 5 position configured As shown in Fig 41 each click of the FAN softkey changes the fan icon display between 2 position ON and AUTO 3 pos...

Страница 23: ...finished Fig 43 System and View More display for Tenant Tenant Home Screen Display The LCD display may be customized for the tenant This section includes a few examples of the various tenant Home screens that are configurable for the LCD Wall Modules Not all possible Home screens are illustrated here There are many other configurable Home screens NOTE Home screens can display one to three of any o...

Страница 24: ... Home screen with Room Temperature and Time predominant NOTE In Fig 47 there are no Fan System or View More softkey options configured for this Home screen Fig 48 Sample Tenant Home screen with a single custom parameter NOTE In Fig 48 the Home screen is configured with only a single custom parameter See Preview on page 9 Fig 49 View More display showing CO2 sensor value from controller NOTE As sho...

Отзывы: