XNX Universal Transmitter
Section 3 - Calibration
105
Using the Calibration Cup
to attach the calibration cup:
1. Snap the calibration cup into the weather protector. The two
protrusions on the cup fit into recesses in the weather protector.
2. Attach the hose from the gas cylinder to the calibration cup. Note
that the cup’s flow is unidirectional. There is an arrow on the
bottom showing flow direction
3.
Adjust the calibration flow rate
1
.
weather
protector
calibration cup
attach gas
cylinder hose
Figure 202. Attaching the Calibration Cup
1 300-375 ml/min for XNX EC sensors, 300-700 ml/min for XNX mV sensors, unless other-
wise directed.
Zero and Span Calibration of EC Sensors
Caution:
Before initial calibration, allow the sensor to stabilize for 30 minutes after applying power.
When in zero and span calibration modes, the current output from the sensor is inhibited (default
2mA) to avoid false alarms.
Caution:
Recalibrate if the temperature of local environment has varied by more than ±15°C from
the temperature of calibration.
CAUTION
!
Hydrogen Sulfide
Hydrogen Sulfide sensors can be affected by extreme humidity
changes. A sudden increase in ambient humidity can result in a short-
term positive drift in the instrument’s reading. A sudden decrease
in ambient humidity can result in a short-term negative drift in the
instrument’s reading. These are most likely to be noticed during
calibration with dry or cylinder gas.
When calibrating hydrogen sulfide cartridges, follow the procedure
. To zero the sensor, use a compressed gas
cylinder of 20.9%Vol oxygen (not nitrogen). Do not use background air.
If a span calibration is to be performed, apply the span calibration gas
immediately after the zeroing procedure. Do not allow the sensor to
return to ambient air conditions.
Warning:
Long-term exposure (>20 minutes) to concentrations exceediing the full-scale range of
the H2
S sensor Type 2 can cause it to lose sensitivity. The measured value may then decrease
even though high levels of toxic gas are still present. If such conditions can occur, set the control unit
to latch at overrange. In standalone operation, set alarms to latching. When resetting the overrange
or alarm, verify the correct operation of the transmitter. Before re-calibrating the transmitter, verify
the absence of gas.
WARNING
!
Содержание XNX-AM Series
Страница 2: ...This page is intentionally left blank ...
Страница 7: ...XNX Universal Transmitter Safety and Information 5 Safety and Information ...
Страница 12: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 10 Introduction ...
Страница 27: ...XNX Universal Transmitter Introduction 25 Menu Navigation ...
Страница 31: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 29 Installation and Operation ...
Страница 102: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 100 Calibration ...
Страница 118: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 116 Maintenance ...
Страница 122: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 120 Warnings and Faults ...
Страница 139: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 137 Specifications ...
Страница 174: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 172 Control Drawings ...
Страница 177: ...XNX Universal Transmitter Control Drawings 175 ...
Страница 179: ...XNX Universal Transmitter Control Drawings 177 Remote Sensor Mount ...
Страница 180: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 178 HART Protocol ...
Страница 193: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 191 Modbus Protocol ...
Страница 200: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 198 Warranty ...
Страница 202: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 200 Index ...
Страница 206: ...This page is intentionally left blank ...