Honeywell XE70 Series Скачать руководство пользователя страница 3

T6372/T6373 FAN -COIL TERMOSTATS 2-PIPE FAN-COIL CONTROL

EN002-0903

3

INSTALLATION

OPERATION

Sensing element

The thermostat sensing element comprises two circular,
flexible metal plates welded together at the rims and
encapsulating a gas/liquid combination whose pressure
changes in response to variations in temperature.  This dual-
diaphragm expands and contracts with ambient temperature
changes to operate a snap-acting switch which controls the
heating or cooling circuit.

Heat anticipator

It is recommended that the heat anticipator is always
connected for both heating and cooling operation.

Location

The XE70 Series thermostat is the temperature control
element in the fan-coil or air-conditioning system, and must
be located in a position with good air circulation, on an inside
wall about 1.5 m above the floor to sense the average
temperature.  Do not position the thermostat in draughts,
near hot or cold air sources or where it will be affected by
radiant heat from the sun or other appliances.

Mounting the thermostat

Any XE70 Series thermostat can be directly mounted on the
wall or on a conduit box (see diagram). Mounting screws are
supplied for both alternatives.

Wiring the thermostat

The standard wiring access is via a hole in the base of the
thermostat, near the top edge.

IMPORTANT

1. The installer must be a trained service engineer

2. Disconnect the power supply before beginning

installation

Switches

All switches are slide switches for ease of operation.

The ON/OFF switch is a system on/off switch, as it removes
power from the thermostat.

The FAN SPEED switch allows selection of 3 different fan
speeds, 1 (low), 2 (medium), and 3 (high)

The SPDT HEAT/COOL switch allows selection of either
heating or cooling operation.  There is only a single output
connection capable of powering a fan or a single zone valve
in a 2-pipe fan-coil unit.

Application

T6372A T6372B T6372B T6372C   T6373AC       T6373BC

1018

1024

1032

1014       

1108              1130

Ventilation

F

F

F

2-pipe fan-coil

F

F

F

F

 

F

  

F

Application

4-pipe fan-coil
Heatpump
Air-conditioner

Heat or Cool

F

 

F

Heat/cool

F

F

F

   

F

Control

Changeover (auto or manual)

 manual

manual

auto

          manual

Capability

Fan control (auto or cont)

a or c

a or c

a or c

a or c

    cont

         cont

Fan speed control

    

F

  

F

Valve control

F

F

F

F

   

F

  

F

Compressor control

Содержание XE70 Series

Страница 1: ... changeover operation is also possible on some versions This function can be accomplished either by a manually operated heat cool switch on the front of the thermostat or in some versions automatically by the use of a pipe thermostat on the supply water pipe of the fan coil FEATURES Dual diaphragm sensing element ensures close temperature control for all loads and applications Attractive modern st...

Страница 2: ...cted Electrical ratings 4 2 A 230 V Typical loads are fans zone valves and relays Operational life Greater than 100 000 cycles all loads for thermostat contacts at 230 V Greater than 6 000 operations for all manually operated switches Mounting Mounts directly onto wall or wall box mounting screws supplied Wiring Up to 8 screw in terminals per unit capable of accepting wires up to 1 5 mm 2 Enclosur...

Страница 3: ...70 Series thermostat can be directly mounted on the wall or on a conduit box see diagram Mounting screws are supplied for both alternatives Wiring the thermostat The standard wiring access is via a hole in the base of the thermostat near the top edge IMPORTANT 1 The installer must be a trained service engineer 2 Disconnect the power supply before beginning installation Switches All switches are sl...

Страница 4: ...ICIPATOR ANTICIPATOR ANTICIPATOR ANTICIPATOR ANTICIPATOR HEAT HEAT HEAT HEAT HEAT COOL HEAT COOL HEAT COOL HEAT COOL COOL COOL COOL COOL CLOSE VALVE CLOSE VALVE CLOSE VALVE CLOSE VALVE CLOSE VALVE CLOSE VALVE CLOSE VALVE LOAD VALVE VALVE VALVE VALVE VALVE VALVE VALVE VALVE VALVE FAN FAN FAN FAN FAN FAN FAN FAN link 4 5 for fan continuous 3 5 for fan automatic cycled WIRING T6373AC1108 T6373BC1130 ...

Отзывы: