background image

T6372/T6373 FAN -COIL TERMOSTATS 2-PIPE FAN-COIL CONTROL

EN002-0903

               2

SPECIFICATIONS

Model

 Switches

Features

ON/OFF

3-speed

Fan/

Heat/Cool

Heat/Cool

Heat/Off/

Heat/Fan/

Fixed

Auto

Fan

Auto/Cont

Cool

Cool

Deadband

Change-

over

(SPST)

(SPTT)

(SPDT)

(SPDT)

(DPDT)

(DPTT)

(DPTT)

(Aquastat)

T6372A1018

4

T6372B1024

4

T6372B1032

4

4

T6372C1014

4

4

T6373AC1108

4

4

T6373BC1130      

4                   4

                  4

Setpoint range

10...30

o

C. By means of a large setpoint

dial

Supply voltage

230 V~, 50...60 Hz

Thermostat
switch

S.P.D.T.

Performance

Typical differential 1K (heating & cooling)
at 20

o

C at 50% load with anticipator

connected

Electrical ratings

4(2) A, 230 V~

  

Typical loads are fans, zone valves and
relays

Operational life

Greater than 100,000 cycles (all loads)
for thermostat contacts at 230 V~
Greater than 6,000 operations for all
manually operated switches

Mounting

Mounts directly onto wall or wall-box
(mounting screws supplied)

Wiring

Up to 8 screw-in terminals per unit,
capable of accepting wires up to 1.5 mm

2

Enclosure

Plastic 2-piece housing

Dimensions

85 x 130 x 40 mm (w x h x d).

Protection class

IP30

RFI suppression

  

Provided to B.S. EN 55014

Environmental
requirements

Operating temperature range 0 to 40

o

C

Shipping and storage temperature range
-20 to 50

o

C

Humidity range 0 to 90% rh, non-
condensing

Approvals

Designed to meet harmoniosed EC
approvals standard IEC 730

DIMENSIONS

Содержание XE70 Series

Страница 1: ... changeover operation is also possible on some versions This function can be accomplished either by a manually operated heat cool switch on the front of the thermostat or in some versions automatically by the use of a pipe thermostat on the supply water pipe of the fan coil FEATURES Dual diaphragm sensing element ensures close temperature control for all loads and applications Attractive modern st...

Страница 2: ...cted Electrical ratings 4 2 A 230 V Typical loads are fans zone valves and relays Operational life Greater than 100 000 cycles all loads for thermostat contacts at 230 V Greater than 6 000 operations for all manually operated switches Mounting Mounts directly onto wall or wall box mounting screws supplied Wiring Up to 8 screw in terminals per unit capable of accepting wires up to 1 5 mm 2 Enclosur...

Страница 3: ...70 Series thermostat can be directly mounted on the wall or on a conduit box see diagram Mounting screws are supplied for both alternatives Wiring the thermostat The standard wiring access is via a hole in the base of the thermostat near the top edge IMPORTANT 1 The installer must be a trained service engineer 2 Disconnect the power supply before beginning installation Switches All switches are sl...

Страница 4: ...ICIPATOR ANTICIPATOR ANTICIPATOR ANTICIPATOR ANTICIPATOR HEAT HEAT HEAT HEAT HEAT COOL HEAT COOL HEAT COOL HEAT COOL COOL COOL COOL COOL CLOSE VALVE CLOSE VALVE CLOSE VALVE CLOSE VALVE CLOSE VALVE CLOSE VALVE CLOSE VALVE LOAD VALVE VALVE VALVE VALVE VALVE VALVE VALVE VALVE VALVE FAN FAN FAN FAN FAN FAN FAN FAN link 4 5 for fan continuous 3 5 for fan automatic cycled WIRING T6373AC1108 T6373BC1130 ...

Отзывы: