Honeywell W884B Скачать руководство пользователя страница 8

8

W884B,E

SETTINGS AND ADJUSTMENTS

The recommended maximum settings for mildew pre-

vention are 60 percent RH and 85

°

F [29

°

C].

HUMIDITY ADJUSTMENT (All Models)

In some cases, it may be desirable to deviate from

recommended setting. The setting knob has a movable
pointer, which can be adjusted to produce an upward or
downward shift in the setpoint of as much as six percent
relative humidity. Adjust as follows:

1. Remove the cover of the W884.
2. While holding the knob still, push the movable

pointer on the humidity setting dial toward MORE or
LESS. See Fig. 10.

For W884B only, set the pointer according to the type

of building construction (Table 1).

Fig. 10—An adjustment of 

±

 six percent RH in

the humidity control point is possible by
moving the pointer of the knob.

HUMIDITY INDICATOR RECALIBRATION
(All Models)

The humidity indicator in the W884 Comfort Control

Center has been carefully calibrated at the factory and
should require no further adjustment.

If, after several hours of operation, it appears that

recalibration is necessary, proceed as follows:

1. Obtain a proven test hygrometer (humidity gauge).

Do not attempt to use the humidity from the weather
report or an ordinary hygrometer. This will result in an
inaccurate setting.

2. Place it near the humidity indicator and allow

several hours for its reading to stabilize.

3. Rotate the bracket holding the spiral sensing ele-

ment in the W884 until the humidity indicator agrees
with the test hygrometer.

THERMOSTAT HEAT ANTICIPATOR
ADJUSTMENT

Adjust the heat anticipator to match the current rating

of the primary control; this rating is usually stamped on
the control nameplate. Move the indicator on the scale to
correspond with this rating and the heat anticipator will
be properly adjusted. Move the indicator with your fin-
gers, a pin, a pencil point, or a wire inserted in the small
hole. See Fig. 11. If the current rating is not given,
proceed as follows before mounting the thermostat:

1. Connect an ac ammeter of appropriate range (0 to

2.0A, for example) between the terminals R and W on
the subbase. The subbase system switch must be in the
HEAT position.

2. Let the heating system operate for one minute

before reading the ammeter.

3. Use this current reading to set the heat anticipator.
A slightly higher setting will produce longer burner-

on times (and thus fewer cycles per hour). This may be
desirable on some systems such as a one-pipe steam
system.

Fig. 11—T87F Heat Anticipator is adjusted to

match the current draw of the primary control.

EXAMPLE: If burner-on time is too short with a set-

ting of 0.4, adjust it to 0.45 and check system opera-
tion. Make further adjustments as necessary until the
desired burner-on time is obtained.

THERMOSTAT CALIBRATION

The thermostat was accurately calibrated at the fac-

tory and should not need recalibration. If the thermo-
stat seems out of adjustment, first check for accurate
leveling. Also check the location to be sure the thermo-
stat is exposed to average room temperature only. Heat
due to nearby appliances, hot water pipes, fireplaces,
solar heat, radiators, and registers or cold due to drafts
or cold water pipes may affect operation.

If the thermostat is still out of calibration, order Part

No. 104994A Calibration Wrench. Instructions for
recalibration are furnished with the wrench.

Содержание W884B

Страница 1: ... The W884E includes a dehumidifier control All comfort controls are combined in the W884 to make a convenient attractive control center CONTENTS Specifications 2 Ordering Information 2 Recycling Notice 3 Installation 4 Settings and Adjustments 7 Checkout 9 Humidistat dial on the W884B can be set for prevailing outdoor temperature to provide opti mum relative humidity over a wide range of con ditio...

Страница 2: ... outdoor temperature W884E The dial is marked ON LOW NOR MAL HIGH and OFF Optimum relative hu midity is maintained by rotating the humidity selection dial DIFFERENTIAL 4 to 6 percent RH cycling at midscale THERMOSTAT RATINGS Switching Spdt Switch Rating 1 5A at 30 Vac Range 50 F to 100 F 10 C to 38 C Adjustable Heat Anticipator Range 0 10 to 1 2A factory set at 0 4A SUBBASE RATINGS System Switch C...

Страница 3: ... at the end of its useful life If this control is replacing a control that contains mer cury in a sealed tube do not place your old control in the trash Contact your local waste management authority for instructions regarding recycling and the proper disposal of this control or of an old control containing mercury in a sealed tube If you have questions call Honeywell at 1 800 468 1502 M3375 ...

Страница 4: ...ant heat from the sun or appliances concealed pipes and chimneys unheated uncooled areas such as an outside wall behind the thermostat MOUNTING IMPORTANT The thermostat used with the W884 was mounted at true level when calibrated at the fac tory The W884 must be level to maintain calibra tion 1 Remove cover and thermostat and level W884 at the selected location Mark locations for mounting screws a...

Страница 5: ...ion Push excess wire back into wall and plug the hole to prevent drafts from affect ing the W884 7 Mount the thermostat and replace W884 cover WIRING Disconnect power supply to prevent electrical shock or equipment damage All wiring must comply with local codes and ordi nances Wiring to the W884 must be NEC Class 2 Humidistat requires separate 24V power supply Refer to the wiring diagrams and inst...

Страница 6: ...AY W B G Y O H H Q539 DEHUMIDISTAT W884E 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED USED IN DUCT HEATER OR SIMILAR APPLICATIONS TO ENERGIZE SYSTEM FAN DURING HEATING M1335 FAN RELAY 2 2 SPST N C SWITCHING RELAY R 1 HUMIDIFIER RELAY COOLING DAMPER MOTOR COOLING CONTACTOR FAN RELAY HEATING RELAY W B G Y O H H Q539A HUMIDISTAT W884B 1 POWER SUPPLY PROVIDE DISCONNECT M...

Страница 7: ...et as recom mended and frost or condensation forms on inside windows adjust humidistat setting for outdoor tem per ature setting less 5 F 3 C Frost or condensa tion should disappear within 24 hours If not con tinue reducing outdoor temperature setting and ad just humidistat accordingly Humidity Selection W884B The humidity controller should be set at the prevail ing outdoor temperature This will p...

Страница 8: ... rating of the primary control this rating is usually stamped on the control nameplate Move the indicator on the scale to correspond with this rating and the heat anticipator will be properly adjusted Move the indicator with your fin gers a pin a pencil point or a wire inserted in the small hole See Fig 11 If the current rating is not given proceed as follows before mounting the thermostat 1 Conne...

Страница 9: ... system through one complete cycle to make sure all components function as intended CAUTION On low voltage gas system if jumpering gas valve to check system operation do NOT jumper across valve coil This may burn out thermostat heat anticipator See Fig 12 Fig 12 Do not jumper across valve coil ...

Страница 10: ...ome and Building Control Helping You Control Your World Honeywell Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 740 Ellesmere Road Golden Valley MN 55422 Scarborough Ontario M1P 2V9 Printed in U S A QUALITY IS KEY ...

Отзывы: