Honeywell W8735ER Скачать руководство пользователя страница 4

W8735ER WIRELESS OUTDOOR RESET MODULE

66-1202—01

4

OPERATION

General

The W8735ER Wireless Outdoor Reset Module is a device 

which when connected to an AquaReset enabled Electronic 

Aquastat, Integrated Boiler Control (IBC) or SOLA control via 

the EnviraCOM™ communication bus, enhances the available 

control features to include Outdoor Temperature Reset, a 

stepped Boost function as well as Warm Weather Shutdown 

to provide increased boiler efficiency while servicing the heat 

demand. Set-up of the Outdoor Setback curve as well as the 

Boost function is done using the 3-digit/3-button display on the 

L7224/L7248 Aquastat (see L7224 Installation Instructions 

Form Number 69-1720 and/or Form Number 68-0281 for 

more information). For the IBC setup see

 

Form Number 66-

1203 Installation Instructions for more information. For SOLA, 

set-up of the reset curve is done using the S7910 or S7999 

display (See Form Numbers 65-0315, 66-1175, and 68-0295 

for more information.)

Adjusting Aquastat and IBC Settings

To discourage unauthorized/unintentional changing of 

Aquastat and IBC settings, a procedure to enter the 

ADJUSTMENT mode is required. To enter the ADJUSTMENT 

mode, press the UP, DOWN, and I buttons (See Fig. 4) 

simultaneously for three seconds. Next, press the 

I

 button until 

the feature requiring adjustment is displayed then use the 

arrow up/down buttons to set the parameter value (See Table 

4). After 60 seconds without any button inputs, the controller 

will automatically return to the normal display mode.

Fig. 4. Location of L7224/L7248 and S936X 3-digit display and buttons.

Outdoor Reset

The Outdoor Reset feature adjusts the target boiler 

temperature to a point below its local high limit setting and 

above the boiler's condensation temperature by using the 

EnviraCOM communication bus to directly adjust the Aquastat 

set-point. Should a call for Domestic Hot Water be detected, 

the boiler temperature is commanded to return to the High 

Limit setting, ensuring a hot water supply is available. When 

the Domestic Hot Water demand is met, the Outdoor Reset 

feature is once again enabled. See Table 1 and Fig. 5.

Application and Settings Pointers

The energy savings concept behind Outdoor Reset is to 

minimize the energy in the boiler that is lost during the off 

cycle. This is accomplished by maintaining the boiler 

temperature as low as possible and/or running the boiler for 

longer periods of time. Although considerable energy savings 

exists, the boiler is only one part of the system that includes 

thermostats, other controls, and radiation. To maximize 

savings while avoiding call-backs due to uncomfortable 

homeowners, care must be taken when adjusting the control 

parameters. Listed below are operation and adjustment 

pointers. See Fig. 5.

Low Boiler Temperature:

 This is the minimum temperature 

at which the boiler is designed to operate. Setting this too low 

during warmer periods may result in condensation in the boiler 

and reduce boiler life. Typically this setting is 130 °F (54 °C) 

for gas boilers and 140 °F (60 °C) for oil boilers and is 

adjusted to be maintained at the high outdoor temperature 

setting. Some new cast iron boilers are designed to operate at 

lower temperatures. Consult the manufactures' specifications.

Low Outdoor Temperature:

 As the outdoor temperature 

decreases, the boiler temperature must increase to provide 

more heat to the space. The Low Outdoor Temperature 

C1

B1

ZC

L2

LINE

C2

ZR

L1

B2

T
T 3

2
1

THREE-DIGIT 

DISPLAY

BUTTONS

M33913

GND

BUTTONS

THREE-DIGIT 

DISPLAY

Содержание W8735ER

Страница 1: ...munication protocol Fast wireless connection to outdoor sensor Enables Boiler Outdoor Temperature Reset Enables Warm Weather Shutdown Enables Boost Override Simple low voltage 3 wire installation to combustion control 3 EnviraCOM EnviraCOM RedLink Enabled INSTALLATION When Installing this Product 1 Read these instructions carefully Failure to follow them could damage the product or cause a hazardo...

Страница 2: ...ower on 5 Bind the C7089R Wireless Outdoor Sensor to the Wire less Outdoor Reset Module See Sensor Binding on page 3 Fig 1 W8735ER Wireless Outdoor Reset Module wiring diagram C7089R INSTALLATION Mount Outdoor Sensor Before installing the C7089 sensor make sure 2 AA lithium preferred batteries are inserted See Fig 2 Fig 2 Battery Installation 1 Mount the sensor bracket on a vertical wall at least ...

Страница 3: ...e positioned at least 3 feet apart during the binding process 5 Once the flashing rate goes back to 1 blink second press the CONNECT button on the W8735ER to end the binding process 6 Once the C7089R sensor and the W8735ER bind the CONNECTED LED on the W8735ER will be ON solid green 7 Place sensor cover back on the sensor and return the sensor to the bracket See Fig 3 NOTE Pressing the CONNECT but...

Страница 4: ...rature to a point below its local high limit setting and above the boiler s condensation temperature by using the EnviraCOM communication bus to directly adjust the Aquastat set point Should a call for Domestic Hot Water be detected the boiler temperature is commanded to return to the High Limit setting ensuring a hot water supply is available When the Domestic Hot Water demand is met the Outdoor ...

Страница 5: ...oint does not reset the Boost Continuous Boost calls may be an indication of a poorly set Outdoor Reset Curve for the environment or faulty equipment For the Aquastat a Boost warning will be indicated on the 3 digit Aquastat display if Boost is required on 60 consecutive cycles See Table 5 For the Aquastat the Boost Period can be set from OFF to a range of 5 minutes to 30 minutes adjustable in 1 m...

Страница 6: ...ture High maximum parameter for outdoor reset curve F or C btL Boiler Temperature Low minimum parameter for outdoor reset curve bP Boost Period minutes OFF is displayed if Boost is inactive bS Boost step F or C shown only if Boost is active bP ON UUS Warm Weather Shutdown Temperature F or C tPL Thermal Purging Limit Temperature F or C OFF if disabled tPt Thermal Purging Time Delay minutes shown on...

Страница 7: ...power if the alarm condition is no longer present Table 5 Aquastat Outdoor Reset Related Error Codes Error Code Cause Action EnviraCOM Alarm Err 9a Warning Outdoor Reset System failure communication to Outdoor Reset Module lost Outdoor Reset Module failure multiple outdoor temperature sensors detected on the bus or outdoor temperature sensor failure Check EnviraCOM wiring 1 2 3 check sensor wiring...

Страница 8: ... to try to correct the interference by one of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio TV technician for help Wireless adapter To comply with FCC and Industry Canada RF...

Отзывы: