Honeywell W8735ER Скачать руководство пользователя страница 1

INSTALLATION INSTRUCTIONS

66-1202-01

W8735ER Wireless Outdoor Reset 

Module

APPLICATION

The W8735ER Wireless Outdoor Reset Module, when 

connected to the C7089R1013 Wireless Outdoor Sensor, 

works with any AquaReset enabled Aquastat® such as the 

L7224/48 Aquastat, S9360/61/80 Integrated Boiler Control, 

and R7910 SOLA Control via the EnviraCOM™ 3-wire bus. 

The Wireless Outdoor Reset Module enables efficiency 

control functionality, such as Outdoor Temperature Reset, 

Boost function, and Warm Weather Shutdown function to 

generate average operational savings of up to 15%.

SPECIFICATIONS

Electrical Ratings: 

Voltage: 24 Vac, 60 Hz. 

Environmental Ratings: 

Temperature: -30 °F to +150 °F (-34 °C to +66 °C).

Humidity: 0 to 95% relative humidity, non-condensing.

Accessories (Can be ordered separately):

C7089R1013 Wireless Outdoor Temperature Sensor 

FEATURES

• RedLink™ wireless communication protocol
• Fast wireless connection to outdoor sensor
• Enables Boiler Outdoor Temperature Reset
• Enables Warm Weather Shutdown
• Enables Boost Override
• Simple low-voltage, 3-wire installation to combustion 

control (3 EnviraCOM)

• EnviraCOM™/RedLink Enabled

INSTALLATION

When Installing this Product...

1.

Read these instructions carefully. Failure to follow them 

could damage the product or cause a hazardous condi-

tion.

2.

Check the ratings given in the instructions and on the 

product to make sure the product is suitable for your 

application.

3.

The installer must be a trained, experienced service 

technician.

4.

After installation is complete, check out product opera-

tion as provided in these instructions.

CAUTION

Electrical Shock Hazard.

Can cause electrical shock or equipment damage.

Disconnect power supply before connecting wiring.

5.

The Outdoor Reset Module can be wall mounted in any 

orientation desired or dictated by the surroundings.

6.

The holes are sized for the #6 sheet metal screws 

(included).

7.

Precise leveling of the product is not required.

Содержание W8735ER

Страница 1: ...munication protocol Fast wireless connection to outdoor sensor Enables Boiler Outdoor Temperature Reset Enables Warm Weather Shutdown Enables Boost Override Simple low voltage 3 wire installation to combustion control 3 EnviraCOM EnviraCOM RedLink Enabled INSTALLATION When Installing this Product 1 Read these instructions carefully Failure to follow them could damage the product or cause a hazardo...

Страница 2: ...ower on 5 Bind the C7089R Wireless Outdoor Sensor to the Wire less Outdoor Reset Module See Sensor Binding on page 3 Fig 1 W8735ER Wireless Outdoor Reset Module wiring diagram C7089R INSTALLATION Mount Outdoor Sensor Before installing the C7089 sensor make sure 2 AA lithium preferred batteries are inserted See Fig 2 Fig 2 Battery Installation 1 Mount the sensor bracket on a vertical wall at least ...

Страница 3: ...e positioned at least 3 feet apart during the binding process 5 Once the flashing rate goes back to 1 blink second press the CONNECT button on the W8735ER to end the binding process 6 Once the C7089R sensor and the W8735ER bind the CONNECTED LED on the W8735ER will be ON solid green 7 Place sensor cover back on the sensor and return the sensor to the bracket See Fig 3 NOTE Pressing the CONNECT but...

Страница 4: ...rature to a point below its local high limit setting and above the boiler s condensation temperature by using the EnviraCOM communication bus to directly adjust the Aquastat set point Should a call for Domestic Hot Water be detected the boiler temperature is commanded to return to the High Limit setting ensuring a hot water supply is available When the Domestic Hot Water demand is met the Outdoor ...

Страница 5: ...oint does not reset the Boost Continuous Boost calls may be an indication of a poorly set Outdoor Reset Curve for the environment or faulty equipment For the Aquastat a Boost warning will be indicated on the 3 digit Aquastat display if Boost is required on 60 consecutive cycles See Table 5 For the Aquastat the Boost Period can be set from OFF to a range of 5 minutes to 30 minutes adjustable in 1 m...

Страница 6: ...ture High maximum parameter for outdoor reset curve F or C btL Boiler Temperature Low minimum parameter for outdoor reset curve bP Boost Period minutes OFF is displayed if Boost is inactive bS Boost step F or C shown only if Boost is active bP ON UUS Warm Weather Shutdown Temperature F or C tPL Thermal Purging Limit Temperature F or C OFF if disabled tPt Thermal Purging Time Delay minutes shown on...

Страница 7: ...power if the alarm condition is no longer present Table 5 Aquastat Outdoor Reset Related Error Codes Error Code Cause Action EnviraCOM Alarm Err 9a Warning Outdoor Reset System failure communication to Outdoor Reset Module lost Outdoor Reset Module failure multiple outdoor temperature sensors detected on the bus or outdoor temperature sensor failure Check EnviraCOM wiring 1 2 3 check sensor wiring...

Страница 8: ... to try to correct the interference by one of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio TV technician for help Wireless adapter To comply with FCC and Industry Canada RF...

Отзывы: