Honeywell W8635A Скачать руководство пользователя страница 2

W8635A EQUIPMENT INTERFACE MODULE

69-1339—2

2

Fig. 2. Mounting W8635A 

Equipment Interface Module.

4.

Position the W8635A on the wall or on the cold air 
return.

5.

Level the W8635A for appearance only; the device 
functions properly even when not level.

6.

Use a pencil to mark the position of the mounting 
holes on the wall or cold air return.

7.

Remove the W8635A from the wall or cold air 
return and drill 3/16 in. holes in the wall (if drywall) 
where marked. For firmer materials such as plaster 
or wood, drill 7/32 in. holes.

8.

When mounting on the cold air return, drill a pilot 
hole where marked.

9.

Gently tap the anchors (provided) into the holes 
until flush with the wall.

10.

Reposition the W8635A over the holes.

11.

Loosely insert the screws into the holes and tighten 
each screw.

WIRING

All wiring must comply with local electrical codes and 
ordinances. See Fig. 4 through 6 wiring diagrams for 
specific equipment applications. Refer to Table 2 for 
terminal designations.

CAUTION

Voltage Hazard.
Can cause electrical shock or equipment 
damage.
Disconnect power before beginning installation.

1.

Loosen the terminal screws on the W8635A and 
connect the system wires. See Fig. 3.

2.

Securely tighten each terminal screw.

Fig. 3. Wiring the W8635A terminals.

Table 2. Terminal Designations.

Fig. 4. 2H/2C single transformer. 

Y2

W2

Y1

G

W1

C

R

RH

RC

1

2

3

MOUNTING 
HOLES (2)

MOUNTING 
SCREWS (2)

W8635

WALL

M16636

W8635A 

Terminal 

Designations

Function

1

To Communicating Thermostat 
Terminal 1

2

To Communicating Thermostat 
Terminal 2

3

To Communicating Thermostat 
Terminal 3

R

24 Vac System Transformer 

Rh

24 Vac Heating Transformer 

Rc

24 Vac Cooling Transformer 

C

24 Vac Transformer Common 

G

Fan  Relay

W1

Stage 1 Heat Relay

W2

Stage 2 Heat Relay

Y1

Stage 1 Cool Relay

Y2

Stage 2 Cool Relay

Green LED

Indicates Data Communication

FOR WRAPAROUND
CONNECTION—
STRIP 7/16 IN. (11 MM)

FOR STRAIGHT
CONNECTION—
STRIP 5/16 IN. (8 MM)

M16639

W8635

L1 
(HOT)

L2

COOL 1
RELAY

HEAT 2
RELAY

FAN 
RELAY

OT

OT

2

1

3

FACTORY INSTALLER JUMPERS.

M13429

C7089B 
OUTDOOR
TEMPERATURE 
SENSOR

1

T8635L

HEAT 1
RELAY

W8635A

C

R

RH
RC

1

2

3

Y2

W2

Y1

G

W1

COOL 2
RELAY

1

SYSTEM

TRANSFORMER

Содержание W8635A

Страница 1: ...ller must be a trained experienced service technician 4 After completing installation use these instructions to check out the product operation CAUTION Voltage Hazard Can cause electrical shock or equipment damage Disconnect power before supply before beginning installation Location CAUTION Mounting Location Hazard Mounting W8635A inside HVAC equipment can damage the EIM Mount the W8635A only on t...

Страница 2: ... CAUTION Voltage Hazard Can cause electrical shock or equipment damage Disconnect power before beginning installation 1 Loosen the terminal screws on the W8635A and connect the system wires See Fig 3 2 Securely tighten each terminal screw Fig 3 Wiring the W8635A terminals Table 2 Terminal Designations Fig 4 2H 2C single transformer Y2 W2 Y1 G W1 C R RH RC 1 2 3 MOUNTING HOLES 2 MOUNTING SCREWS 2 W...

Страница 3: ...sed on the information it received during Discovery Mode See Table 4 To change the default cycle rate settings enter T8635L Thermostat Installer Setup and select the desired cycle rate settings for each stage All stages can be set between 1 and 12 cph Table 4 Default Cycle Rate Settings Electric Heat Setting When using the W8635A on an electric heat application set the T8635L Thermostat Installer ...

Страница 4: ...ection period To start the Installer System Test 1 Press and hold the T8635L Thermostat increase and decrease keys at the same time until 10 appears All display segments display before the 10 appears See Fig 7 and 8 Fig 7 LCD segments display Fig 8 Installer Test Number display 2 Refer to Table 6 for Installer System Test option Test Number System Test Description 10 12 Heating stages can be turne...

Страница 5: ... returns to normal operating mode Table 6 Installer System Test Options Continued Key to Press Test Number Description Run Program Table 7 Troubleshooting Guide Symptom Possible Cause Action Display does not come on at thermostat Thermostat is not being powered Check if the thermostat is mounted and latched on the wallplate if not mount and latch the thermostat on the wallplate Check if the circui...

Страница 6: ...ing If the Flash COM OK LED blinks check that 24 Vac is present at Y1 terminal If 24 Vac is not present check R to Rh to Rc jumper connection If the R to Rh to Rc connection is good replace the W8635A EIM wait is displayed and the call for Cool has not started Compressor protection is in effect Compressor protection can be set from 0 to 5 minutes to prevent compressor damage due to rapid cycling W...