INSTALLATION INSTRUCTIONS

69- 1339- 2

W8635A

Equipment Interface Module

APPLICATION

The W8635A Equipment Interface Module (EIM) pro-
vides 24 Vac control of single or multistage conventional 
HVAC equipment when used with a T8635L Microelec-

tronic Communicating Programmable Thermostat. The 
W8635A can be used with up to 2 heat/2 cool conven-
tional applications. See Table 1.

Table 1. Description.

INSTALLATION

When Installing this Product…

1.

Read these instructions carefully. Failure to follow 
these instructions can damage the product or 
cause a hazardous condition.

2.

Check the ratings given in the instructions and on 
the product to make sure the product is suitable for 
your application.

3.

Installer must be a trained, experienced service 
technician.

4.

After completing installation, use these instructions 
to check out the product operation.

CAUTION

Voltage Hazard.
Can cause electrical shock or equipment 
damage.
Disconnect power before supply before beginning 
installation.

Location

CAUTION

Mounting Location Hazard.
Mounting W8635A inside HVAC equipment 
can damage the EIM.
Mount the W8635A only on the outside of HVAC 
equipment.

1.

 Locate the W8635A in the equipment room near 
the HVAC equipment. See Fig. 1.

Fig. 1. Selecting W8635A Equipment 

Interface Module location.

2.

Remove the cover from the W8635A by pulling on 
the edge of the module.

3.

Locate the two mounting holes. See Fig. 2.

Model

Application

Stages

Terminals

Comments

W8635A

Conventional gas, oil 
or electric heat

Up to 2 heat/
2 cool

1, 2, 3, C, R, Rh, Rc, 
G, W1, W2, Y1, Y2

Use with T8635L Communicating 
Thermostat

M16637A

WATER HEATER

W8635
POSSIBLE
MOUNTING 
LOCATION

FURNACE OR BOILER

W8635

POSSIBLE

MOUNTING

LOCATION

Содержание W8635A

Страница 1: ...ller must be a trained experienced service technician 4 After completing installation use these instructions to check out the product operation CAUTION Voltage Hazard Can cause electrical shock or equipment damage Disconnect power before supply before beginning installation Location CAUTION Mounting Location Hazard Mounting W8635A inside HVAC equipment can damage the EIM Mount the W8635A only on t...

Страница 2: ... CAUTION Voltage Hazard Can cause electrical shock or equipment damage Disconnect power before beginning installation 1 Loosen the terminal screws on the W8635A and connect the system wires See Fig 3 2 Securely tighten each terminal screw Fig 3 Wiring the W8635A terminals Table 2 Terminal Designations Fig 4 2H 2C single transformer Y2 W2 Y1 G W1 C R RH RC 1 2 3 MOUNTING HOLES 2 MOUNTING SCREWS 2 W...

Страница 3: ...sed on the information it received during Discovery Mode See Table 4 To change the default cycle rate settings enter T8635L Thermostat Installer Setup and select the desired cycle rate settings for each stage All stages can be set between 1 and 12 cph Table 4 Default Cycle Rate Settings Electric Heat Setting When using the W8635A on an electric heat application set the T8635L Thermostat Installer ...

Страница 4: ...ection period To start the Installer System Test 1 Press and hold the T8635L Thermostat increase and decrease keys at the same time until 10 appears All display segments display before the 10 appears See Fig 7 and 8 Fig 7 LCD segments display Fig 8 Installer Test Number display 2 Refer to Table 6 for Installer System Test option Test Number System Test Description 10 12 Heating stages can be turne...

Страница 5: ... returns to normal operating mode Table 6 Installer System Test Options Continued Key to Press Test Number Description Run Program Table 7 Troubleshooting Guide Symptom Possible Cause Action Display does not come on at thermostat Thermostat is not being powered Check if the thermostat is mounted and latched on the wallplate if not mount and latch the thermostat on the wallplate Check if the circui...

Страница 6: ...ing If the Flash COM OK LED blinks check that 24 Vac is present at Y1 terminal If 24 Vac is not present check R to Rh to Rc jumper connection If the R to Rh to Rc connection is good replace the W8635A EIM wait is displayed and the call for Cool has not started Compressor protection is in effect Compressor protection can be set from 0 to 5 minutes to prevent compressor damage due to rapid cycling W...

Отзывы: