W7340, W7345 COMMUNICATING ECONOMIZER LOGIC MODULES

9

63-2569—04

Limit On Minimum Damper Position

On the W7340A and B models, the logic module as shipped 

from the factory, limits the minimum position setpoint to 50%. 

The logic module will not allow a minimum position greater 

than 50% open (from fully closed).

NOTE: This setpoint limit can only be changed using a 

Modbus command.

Equation 1. Formula to aid in minimum position adjustment.

 or 

Where:

T

O

 = Outdoor air temperature

OA = Percent of outdoor air

T

R

 = Return air temperature

RA = Percent of return air

T

M

 = Resulting mixed air temperature

NOTE: The following sample calculation uses 

only

 

Fahrenheit temperature.

EXAMPLE: Assume local codes require 10% outdoor air 

during occupied conditions, outdoor air is 60° F 

and return air is 75° F. Under these conditions, 

what is the temperature of the mixed air?

 or

 

Mixed air will be 73.5° F when OA is 60° F and RA is 75° F with 

10 percent outdoor air entering the building.

NOTE: The W7340C model min position and DCV min must 

be set in the field by the installer. See Section DCV 

Min and Min Position Damper Set up.

Enthalpy Changeover (W7340 only)

Outdoor Enthalpy Changeover Setpoint (Single 
Enthalpy Changeover)

The outdoor enthalpy changeover setpoint returns the outdoor 

air damper to minimum position when enthalpy rises above its 

setpoint. Enthalpy setpoint scale markings, located on the 

device, are A, B, C, D and E. See Fig. 10 for the corresponding 

control point.

Differential Enthalpy Changeover Setting

Differential enthalpy control uses:

— W7340A and B use two C7400A Enthalpy Sensors 

connected to one logic module, or

— Two 10K NTC temperature sensors and two C7600C 

Humidity Sensors connected to one logic module.

— W7340C uses C7400C Enthalpy Sensor(s) or

— Two 10K NTC temperature sensors and two C7600C 

Humidity Sensors connected to one logic module.

With outdoor and return air sensors, the logic module 

compares outdoor air to return air instead of to a setpoint as it 

does for single enthalpy. The logic module selects the lower 

enthalpy air (return or outdoor) for cooling; for example, when 

outdoor air has lower enthalpy than return air, the outdoor air 

damper opens to bring in outdoor air for free cooling.

NOTE: When using the W7340 for differential enthalpy, keep 

the setpoint potentiometer set at D.

Exhaust Setpoint (W7340 only)

The exhaust setpoint determines when the exhaust fan will run 

based on the damper position.

The logic module, as shipped from the factory, uses an 

exhaust setpoint of 25%. When the damper position is greater 

than 25% open (from fully closed), relay contact for the 

exhaust fan is closed. When the damper position is below 22% 

open, the relay is de-energized.

Control Configuration (W7340 only)

The W7340 can be configured for humidity or enthalpy 

sensors. Configuration can be performed manually or over the 

Modbus.

IMPORTANT

If only a temperature sensor is connected to the 

W7340, the device will operate using dry bulb 

changeover control.

To configure the W7340 manually:

1.

Within the first three minutes after powering the device, 

short the external minimum damper position terminals 

(P-P1).

NOTE: The LED will go solid within five seconds of 

shorting these terminals.

2.

Maintaining the short for another five seconds causes 

the LED to flash quick pulses (between off periods) 

indicating the sensor configuration type:

a. Two quick pulses: Humidity.

b. Three quick pulses: Enthalpy.

3.

To toggle the sensor configuration type:

a. Remove the short until the LED goes solid again.

b. Reapply the short for another five seconds.

NOTE: Once the short is removed for over 10 seconds, 

the device saves the most recent configuration.

T

O

OA

×

(

)

T

R

RA

×

(

)

+

T

M

=

T

O

T

R

(

)

OA

T

R

+

×

T

M

=

0.1

x

6° F

(

)

0.9

x

75° F

(

)

+

6.0° F 67.5° F

+

73.5° F

=

=

60° F 75° F

(

)

0.1

75° F

+

×

1.5

75° F

+

73.5° F

=

=

Содержание W7340

Страница 1: ...onal S963B1136 Remote Potentiometer for remote minimum damper position control Communicates using a modified Modbus protocol Case matches the lines of the M7215 Damper Motor LED indicates the status of the device input W7340 Only Operates from the Modbus input environmental sensors and a DCV sensor to provide a totally integrated control system Combines minimum damper position potentiometer with s...

Страница 2: ...alpy or dry bulb curve setting 3 W7340C has the ability to set DCV minimum position and has the E curve setting Dimensions See Fig 1 Temperature Ratings Operating Ambient 40 to 149 F 40 to 65 C Shipping 25 to 125 F 32 to 52 C Humidity Ratings Noncondensing 5 to 95 RH Condensing 100 RH Inputs and Outputs See Table 1 Electrical Ratings Input Voltage 24 Vac 25 50 60 Hz Class 2 Nominal Power Consumpti...

Страница 3: ...tected from rain snow and direct sunlight The logic module mounts on the side of an M7215 Damper Motor or directly on a sheet metal duct or panel NOTE Refer to Figures 4 and 5 for representative locations of connected system devices CAUTION Equipment Damage Hazard Mounting screws longer than 5 8 in can damage internal motor components When mounting the module to an M7215 use only the included 6 5 ...

Страница 4: ...n the damper position on a call from the CO2 sensor DCV the damper can go 100 open W7340C The W7340C DCV economizer logic module has the ability to set DCV minimum damper position and minimum position The DCV minimum position is set to ventilate the building contaminants and the minimum position is set to ventilate for the building contaminants and the building occupants The installer sets the dam...

Страница 5: ...NTIAL ENTHALPY CONTROL PROVIDES GREATER ENERGY SAVINGS THAN SINGLE ENTHALPY CONTROL USE EITHER MIXED AIR SENSOR OR DISCHARGE AIR SENSOR NOT BOTH A C7600 HUMIDITY SENSOR USED IN CONJUNCTION WITH A 10K NTC TEMPERATURE SENSOR CAN BE USED INSTEAD OF A C7400 ENTHALPY SENSOR FOR DRY BULB CONTROL USE ONLY A 10K NTC TEMPERATURE SENSOR M22814 INDOOR AIR CO2 SENSOR MODBUS EXHAUST AIR DISCHARGE AIR INDOOR FA...

Страница 6: ... dc common connections Fig 6 W7340 Typical Wiring P1 TR1 TR1 24 VAC TR TR P EXF M23875 PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED OPTIONAL REMOTE MINIMUM POSITION POTENTIOMETER WHEN USING C7400 ENTHALPY SENSORS CONNECT THE ENTHALPY SENSOR TO THE HUMIDITY SENSOR TERMINALS LEAVE THE TEMPERATURE SENSOR TERMINALS EMPTY 1 2 3 3 3 3 3 2 R B W CCW OPEN MOD BUS CW CLOSE S963B M7215 W7340...

Страница 7: ...ing heating It holds the outdoor air damper at the minimum position setting The W7340 operates as a basic free cooling controller Table 2 details the input output I O logic of the W7340 The logic module energizes the Unit Control and Indoor Fan contacts and operates according to Table 2 SETTINGS AND ADJUSTMENT W7345 Potentiometers with screwdriver adjustment slots located on the face of the device...

Страница 8: ...modulating between DCV minimum position and 100 open d Modulation based on DCV signal limited by minimum position e Modulation based on the greater of the DCV and mixed air sensor signals Adjusting Minimum Damper Position The minimum position potentiometer maintains the minimum outdoor air flow into the building during occupied period NOTE If the mixed air temperature drops to 45 F 7 C the mixed a...

Страница 9: ...e sensors and two C7600C Humidity Sensors connected to one logic module With outdoor and return air sensors the logic module compares outdoor air to return air instead of to a setpoint as it does for single enthalpy The logic module selects the lower enthalpy air return or outdoor for cooling for example when outdoor air has lower enthalpy than return air the outdoor air damper opens to bring in o...

Страница 10: ...6 3 8 4 0 4 2 4 4 4 6 9 0 1 0 0 8 0 7 0 6 0 5 0 4 0 3 0 20 10 E N T H A L P Y B T U P E R P O U N D D R Y A I R 85 29 90 32 95 35 100 38 105 41 110 43 35 2 35 2 40 4 40 4 105 41 110 43 45 7 45 7 50 10 50 10 55 13 55 13 60 16 60 16 65 18 65 18 70 21 70 21 75 24 75 24 80 27 80 27 85 29 90 32 95 35 100 38 APPROXIMATE DRY BULB TEMPERATURE F C A A B B C C D D M23879 R E L A T I V E H U M I D I T Y 1 1 ...

Страница 11: ...ia Modbus function code 8 no flash priority needed NOTES All pulse counts Table 4 are based on the number of times the light pulses off In the event of a Communications Failure the LED pulses on for 0 25 seconds every 2 seconds Table 4 W7340 Economizer Checkout Description Pulse count Diagnostic bit Booting 0 3 min after power up NA 12 Mixed air temperature sensor fault 8 7 Outdoor air temperature...

Страница 12: ... Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Toronto Ontario M1V 4Z9 customer honeywell com W7340 W7345 COMMUNICATING ECONOMIZER LOGIC MODULES U S Registered Trademark 2007 Honeywell International Inc 63 2569 04 J I Rev 06 07 ...

Отзывы: