W7340, W7345 COMMUNICATING ECONOMIZER LOGIC MODULES

63-2569—04 4

Fig. 3. Mounting to a Duct or Panel.

Enthalpy Sensor (W7340 only)

To measure enthalpy, the logic module accepts signals from 

either:

— C7600C Humidity and 10K NTC temperature sensors.

— or a C7400 Enthalpy Sensor.

IMPORTANT

• When using C7400 Enthalpy Sensors, connect the 

enthalpy sensors to the humidity sensor terminals; 

leave the temperature sensor terminals empty.

• Use C7400A sensor with W7340A or W7340B.

• Use C7400C sensor with W7340C.

OUTDOOR AIR SENSING

1.

Mount each sensor in any orientation that exposes it to 

freely circulating air and protects it from rain, snow, and 

direct sunlight.

2.

Connect it to the logic module.

RETURN AIR SENSING

1.

For differential enthalpy or temperature control mount a 

second sensor in the return air duct.

2.

Connect it to the logic module.

Demand Control Ventilation (DCV) Sensor Input 
(W7340 only)

The DCV sensor can be any sensor that provides a 0-10 Vdc 

output over a range of 

0 to 2000

 ppm of CO

2

. The DCV signal 

modulates the outdoor damper to provide ventilation based on 

occupancy. Mount the sensor according to the manufacturer 

specifications. If not available, mount the sensor in an area 

with unobstructed air circulation.

IMPORTANT

• Ensure proper polarity of sensor connections. 

Incorrect polarity negates the sensor signal.

W7340B: The W7340B DCV economizer logic modules 

incorporate a minimum position setting that defaults to 20%, 

but can be overridden using the Modbus communication link.

The W7340B DCV maximum position sets the damper position 

to a position that the damper goes to if the CO

2

 sensor fails. If 

the minimum position set point is higher than the DCV 

maximum position, on sensor failure, the damper goes to the 

higher of the two DCV maximum and minimum position setting. 

There is no limit on the damper position on a call from the CO

2

 

sensor (DCV); the damper can go 100% open.

W7340C: The W7340C DCV economizer logic module has the 

ability to set 

DCV minimum damper position 

and 

minimum 

position

. The 

DCV minimum position

 is set to ventilate the 

building contaminants and the 

minimum position

 is set to 

ventilate for the building contaminants and the building 

occupants. The installer sets the damper 

DCV minimum 

position

 and the 

minimum position

 based on the design 

occupancy and CFM of outdoor air requirements for the space. 

The damper will modulate open between the

 DCV minimum 

damper position

 and the 

minimum position

 based on input 

from a CO

2

 sensor. The damper will not drive 100% open on a 

call for ventilation, but can drive 100% open on a call for 

cooling. If the CO

2

 sensor fails the damper will drive to the 

minimum position

 ventilating for building contaminants and 

the building occupants. If the DCV minimum position has not 

been set using the following procedure, the default setting will 

be 50% of the minimum position setting.

DCV Min and Min Position Damper Set Up

Set up instructions for W7340C DCV damper positions:

1.

Remove RAT sensor from RAT terminals.

2.

Connect CO

2

 sensor to DCV terminals.

3.

Apply power to economizer logic module.

4.

Wait 10 to 15 seconds for the CO2 sensor to initialize. 

Short RAT terminals.

5.

Remove CO

2

 sensor from DCV terminals.

6.

DCV LED will blink 2 times. If LED does not blink, cut 

power to economizer logic and repeat steps 1-5.

7.

Set DCV minimum position using MIN POS/DCV MIN 

potentiometer.

8.

Remove RAT short.

9.

DCV minimum position is saved to memory and DCV 

LED blinks 5 times.

10.

Turn off power to economizer logic module.

11.

Connect RAT sensor.

12.

Turn power on to economizer logic module.

13.

Set minimum position using MIN POS/DCV MIN 

potentiometer.

IMPORTANT

Steps 3-8 must be completed within 3 minutes after 

power up otherwise the configuration process will be 

terminated, no changes will be saved and you will 

need to repeat steps 1-13.

M17638

Содержание W7340

Страница 1: ...onal S963B1136 Remote Potentiometer for remote minimum damper position control Communicates using a modified Modbus protocol Case matches the lines of the M7215 Damper Motor LED indicates the status of the device input W7340 Only Operates from the Modbus input environmental sensors and a DCV sensor to provide a totally integrated control system Combines minimum damper position potentiometer with s...

Страница 2: ...alpy or dry bulb curve setting 3 W7340C has the ability to set DCV minimum position and has the E curve setting Dimensions See Fig 1 Temperature Ratings Operating Ambient 40 to 149 F 40 to 65 C Shipping 25 to 125 F 32 to 52 C Humidity Ratings Noncondensing 5 to 95 RH Condensing 100 RH Inputs and Outputs See Table 1 Electrical Ratings Input Voltage 24 Vac 25 50 60 Hz Class 2 Nominal Power Consumpti...

Страница 3: ...tected from rain snow and direct sunlight The logic module mounts on the side of an M7215 Damper Motor or directly on a sheet metal duct or panel NOTE Refer to Figures 4 and 5 for representative locations of connected system devices CAUTION Equipment Damage Hazard Mounting screws longer than 5 8 in can damage internal motor components When mounting the module to an M7215 use only the included 6 5 ...

Страница 4: ...n the damper position on a call from the CO2 sensor DCV the damper can go 100 open W7340C The W7340C DCV economizer logic module has the ability to set DCV minimum damper position and minimum position The DCV minimum position is set to ventilate the building contaminants and the minimum position is set to ventilate for the building contaminants and the building occupants The installer sets the dam...

Страница 5: ...NTIAL ENTHALPY CONTROL PROVIDES GREATER ENERGY SAVINGS THAN SINGLE ENTHALPY CONTROL USE EITHER MIXED AIR SENSOR OR DISCHARGE AIR SENSOR NOT BOTH A C7600 HUMIDITY SENSOR USED IN CONJUNCTION WITH A 10K NTC TEMPERATURE SENSOR CAN BE USED INSTEAD OF A C7400 ENTHALPY SENSOR FOR DRY BULB CONTROL USE ONLY A 10K NTC TEMPERATURE SENSOR M22814 INDOOR AIR CO2 SENSOR MODBUS EXHAUST AIR DISCHARGE AIR INDOOR FA...

Страница 6: ... dc common connections Fig 6 W7340 Typical Wiring P1 TR1 TR1 24 VAC TR TR P EXF M23875 PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED OPTIONAL REMOTE MINIMUM POSITION POTENTIOMETER WHEN USING C7400 ENTHALPY SENSORS CONNECT THE ENTHALPY SENSOR TO THE HUMIDITY SENSOR TERMINALS LEAVE THE TEMPERATURE SENSOR TERMINALS EMPTY 1 2 3 3 3 3 3 2 R B W CCW OPEN MOD BUS CW CLOSE S963B M7215 W7340...

Страница 7: ...ing heating It holds the outdoor air damper at the minimum position setting The W7340 operates as a basic free cooling controller Table 2 details the input output I O logic of the W7340 The logic module energizes the Unit Control and Indoor Fan contacts and operates according to Table 2 SETTINGS AND ADJUSTMENT W7345 Potentiometers with screwdriver adjustment slots located on the face of the device...

Страница 8: ...modulating between DCV minimum position and 100 open d Modulation based on DCV signal limited by minimum position e Modulation based on the greater of the DCV and mixed air sensor signals Adjusting Minimum Damper Position The minimum position potentiometer maintains the minimum outdoor air flow into the building during occupied period NOTE If the mixed air temperature drops to 45 F 7 C the mixed a...

Страница 9: ...e sensors and two C7600C Humidity Sensors connected to one logic module With outdoor and return air sensors the logic module compares outdoor air to return air instead of to a setpoint as it does for single enthalpy The logic module selects the lower enthalpy air return or outdoor for cooling for example when outdoor air has lower enthalpy than return air the outdoor air damper opens to bring in o...

Страница 10: ...6 3 8 4 0 4 2 4 4 4 6 9 0 1 0 0 8 0 7 0 6 0 5 0 4 0 3 0 20 10 E N T H A L P Y B T U P E R P O U N D D R Y A I R 85 29 90 32 95 35 100 38 105 41 110 43 35 2 35 2 40 4 40 4 105 41 110 43 45 7 45 7 50 10 50 10 55 13 55 13 60 16 60 16 65 18 65 18 70 21 70 21 75 24 75 24 80 27 80 27 85 29 90 32 95 35 100 38 APPROXIMATE DRY BULB TEMPERATURE F C A A B B C C D D M23879 R E L A T I V E H U M I D I T Y 1 1 ...

Страница 11: ...ia Modbus function code 8 no flash priority needed NOTES All pulse counts Table 4 are based on the number of times the light pulses off In the event of a Communications Failure the LED pulses on for 0 25 seconds every 2 seconds Table 4 W7340 Economizer Checkout Description Pulse count Diagnostic bit Booting 0 3 min after power up NA 12 Mixed air temperature sensor fault 8 7 Outdoor air temperature...

Страница 12: ... Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Toronto Ontario M1V 4Z9 customer honeywell com W7340 W7345 COMMUNICATING ECONOMIZER LOGIC MODULES U S Registered Trademark 2007 Honeywell International Inc 63 2569 04 J I Rev 06 07 ...

Отзывы: