VRW2 DYNAMIC PRESSURE- REGULATING FLANGED CONTROL VALVES
7
62-3116—01
3.
Wire the Terminal Strip according to the appropriate dia-
gram for your actuator. See Fig. 5.
4.
500 ohm resistors are supplied for 4-20mA to 2-10 Vdc
conversions. Two 2.2Kohm resistors are supplied for dig-
ital/3-Point Floating control. In this mode the actuator is
sensitive to induced electrical voltages from other
sources. To prevent such interference, wire the
2.2Kohm, 0.5W resistor between pins 4 and 1 and a sec-
ond 2.2Kohm, 0.5W resistor between pins 3 and 1.
Fig. 5. Wiring connections.
5.
The actuator is preset for an analog input signal, normally closed
operation. If this is suitable for the application simply connect the
wiring per diagram. Once the power has been connected the
actuator will run a calibration program and then begin normal
operation. If the signal requirement must be changed, proceed to
instruction 6.
6.
Remove power and set all Programming Dip Switches to OFF by
sliding DIP switch toggles away from edge of circuit board (in
direction of arrows in Fig. 6–9).
7.
Apply power and within 10 seconds, press and release the Reset
Button. The programming and indication LED should start blink-
ing.
8.
Turn Programming Dip Switch #1, #2, or #3 ON then OFF to
select signal requirement.
Fig. 6. Set control input type.
ON OFF ON OFF ON OFF
5.2
106
(6.7)
147 (9.3)
146 (9.2)
220 (13.9)
362 (22.84)
442 (27.9)
OFF OFF ON OFF ON OFF
5.3
107
(6.8)
148 (9.3)
146 (9.2)
221 (13.9)
363 (22.90)
445 (28.1)
ON ON OFF OFF ON OFF
5.4
108
(6.8)
149 (9.4)
146 (9.2)
221 (13.9)
364 (22.96)
448 (28.3)
OFF ON OFF OFF ON OFF
5.5
108
(6.8)
150 (9.5)
147 (9.3)
221 (13.9)
365 (23.03)
452 (28.5)
ON OFF OFF OFF ON OFF
5.6
109
(6.9)
151 (9.5)
147 (9.3)
221 (13.9)
366 (23.09)
455 (28.7)
OFF OFF OFF OFF ON OFF
5.7
110
(6.9)
153 (9.7)
147 (9.3)
221 (13.9)
367 (23.15)
458 (28.9)
ON ON ON ON OFF OFF
5.8
111
(7.0)
154 (9.7)
147 (9.3)
222 (14.0)
368 (23.22)
461 (29.1)
OFF ON ON ON OFF OFF
5.9
111
(7.0)
155 (9.8)
147 (9.3)
222 (14.0)
369 (23.28)
465 (29.3)
ON OFF ON ON OFF OFF
6.0
112
(7.1)
156 (9.8)
147 (9.3)
222 (14.0)
370 (23.34)
468 (29.5)
Table 4. Maximum Flow Rate Settings. (Continued)
Dip Switch Settings
Stem
Rotations
From
Closed
VRW2JV...
2-1/2 & 3"
(DN65/80)
5.1~58 psid
(35~400 kPa)
VRW2JW...
2-1/2 & 3"
(DN65/80)
11.6~58 psid
(80~400 kPa)
VRW2KV...
3 & 4"
(DN80/100)
5.1~58 psid
(35~400 kPa)
VRW2KW...
3 & 4"
(DN80/100)
8.6~58 psid
(59~400 kPa)
VRW2LV...
5 & 6"
(DN125/150)
5.1~58 psid
(35~400 kPa)
VRW2LW...
5 & 6"
(DN125/150)
8.6~58 psid
(59~400 kPa)
#1
#2
#3
#4
#5
#6
gpm (L/s)
gpm (L/s)
gpm (L/s)
gpm (L/s)
gpm (L/s)
gpm (L/s)
2-10VDC
ANALOG 2-10VDC
FEEDBACK
CONTROL SIGNAL
24V AC/DC
AC/DC-NEUTRAL/COMMON
500 OHM
5
4
3
2
1
4-20 mA
ANALOG 4-20 mA
FEEDBACK
CONTROL SIGNAL
24V AC/DC
AC/DC-NEUTRAL/COMMON
500 OHM
3
4
5
2
1
4-20 mA
PWM
FEEDBACK
CONTROL SIGNAL
24V AC/DC
AC/DC-NEUTRAL/COMMON
3
4
5
2
1
M31287
4-20 mA
3-POINT FLOATING
FEEDBACK
SIGNAL CW CLOSE
24V AC/DC
AC/DC-NEUTRAL/COMMON
3
4
5
2
1
SIGNAL CCW OPEN
1
ALL OFF
LED
#1 ON
SWITCH #1: DIGITAL/3-POINT FLOATING
#1 OFF
M31288
2 3
1 2 3
1 2 3
#3 ON
SWITCH #3: ANALOG 2-10VDC OR 4-20mA
#3 OFF
1 2 3
1 2 3
#2 ON
SWITCH #2: PWM (PULSE WIDTH MODULATION)
#2 OFF
1 2 3
1 2 3