VRW2 DYNAMIC PRESSURE- REGULATING FLANGED CONTROL VALVES
62-3116—01
8
Programming Normally Open or Normally Closed Setting
The Actuator is delivered from the factory set to the “normally
closed” function for an analog control signal so that a minimum
signal of 2V or 4mA will close the valve and a maximum signal of
10V or 20mA will open the valve to maximum flow.
Fig. 7. Actuator programming.
Programming Failsafe Open or Failsafe Closed Setting
This function applies to battery backup, failsafe models only that
provide power storage to drive the actuator either open to the
Maximum Flow Setting or fully closed in the event of a power supply
failure.
Fig. 8. Failsafe programming.
Programming PWM Time Base Resolution Setting
This function applies only if the Actuator has been programmed to
accept Pulse Width Modulation (PWM) signal.
Fig. 9. PWM time base programming.
Programming Actuator Zero and Span Adjustment
1.
Remove power.
2.
Re-apply power to terminal 2 and within 10 seconds, press and
hold the Reset Button until the indication LED blinks once.
3.
Release the Reset Button. The indication LED should remain illu-
minated.
4.
Apply the new zero voltage to terminal 3. (Any value between 0-7
Vdc)
5.
Press and release the Reset Button to memorize this value. The
LED should blink once as confirmation.
6.
Apply the new maximum voltage to terminal 3. (Any voltage
between 3-10 Vdc and at least 3 Vdc greater than the zero value.)
7.
Press and release the Reset Button to memorize this value. The
indication LED should blink once as confirmation and then cease
to be illuminated. The Actuator will now operate with the new zero
and span.
8.
If the LED provides 3 sequences of 4 blinks the zero and span
program was unsuccessful. This may occur if the difference
between zero and maximum voltage were not equal or greater
than 3 Vdc.
Fig. 10. Actuator programming and LED blink pattern.
#1 ON
FOR NORMALLY CLOSED, SET PROGRAMMING #1 TO OFF
#1 OFF
M31289
1 2 3
1 2 3
FOR NORMALLY OPEN, SET PROGRAMMING #1 TO ON
FOR FAILSAFE CLOSED, SET PROGRAMMING #2 TO OFF
M31290
FOR FAILSAFE OPEN, SET PROGRAMMING #2 TO ON
#2 ON
#2 OFF
1 2 3
1 2 3
FOR 0.1 TO 25 SECONDS/100mS RESOLUTION,
SET PROGRAMMING #3 TO OFF
M31291
FOR 0.1 TO 5 SECOND/20mS RESOLUTION,
SET PROGRAMMING #3 TO ON
#3 ON
#3 OFF
1 2 3
1 2 3
LED
M31292
LED
LED
LED