5

69-0814—1

L1 
(HOT)

L2

1

1

2

3

4

2

4

3

M8053

S8610F,H

MV

MV/PV PV

GND
(BURNER)

24V
GND

24V

TH-W

VENT
DAMPER
PLUG

SPARK

WIRING
HARNESS

THERMOSTAT

D80D VENT
DAMPER

LIMIT
CONTROLLER

PILOT
BURNER
GROUND

IGNITER
SENSOR

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

ALTERNATE LIMIT CONTROLLER LOCATION.

CONTROLS IN 24V CIRCUIT MUST NOT BE IN GROUND LEG TO TRANSFORMER.

REMOVE PLUG ONLY IF USING VENT DAMPER. FUSE BLOWS ON STARTUP WHEN PLUGIS REMOVED AND VENT DAMPER 
WIRING HARNESS IS INSTALLED; THEN MODULE WILL OPERATE ONLY WHEN VENT DAMPER IS CONNECTED. 

PV

PV/MV

MV

VR8404
COMBINATION
GAS CONTROL

QUICK 
CONNECTS

Fig. 7—VR8404 wiring connections in intermittent ignition system with S8600.

Startup and Checkout

WARNING

FIRE OR EXPLOSION HAZARD
CAN CAUSE PROPERTY DAMAGE,
SEVERE INJURY, OR DEATH.
1. Do not force the gas control knobs. Use only

your hand to turn the gas control knobs. Never
use any tools.

2. If the gas control knobs will not operate by

hand, call a qualified service technician to
replace the entire gas control.

3. Both knobs must be in the same position for

operation or shutoff.

GAS CONTROL KNOBS SETTINGS

The gas control knobs have two settings:

OFF: Prevents pilot and main burner gas flow.
ON: Permits gas to flow into the control body. Under

control of the thermostat and intermittent pilot
module, gas can flow to the pilot and main burner.

NOTE: Gas controls are shipped with the gas control

knobs in the ON position.

PERFORM GAS LEAK TEST

WARNING

FIRE OR EXPLOSION HAZARD
CAN CAUSE PROPERTY DAMAGE,
SEVERE INJURY, OR DEATH.
Check for gas leaks with a rich soap and water
solution any time work is done on a gas control.

GAS LEAK TEST

1. Paint all pipe connections upstream of the gas con-

trol with a rich soap and water solution. Bubbles indicate a
gas leak.

2. If a gas leak is detected, tighten the pipe connection.
3. Stand clear while lighting main burner to prevent

injury caused from hidden gas leaks that could cause flash-
back in the appliance vestibule. Turn on the entire gas
control and light the main burner as described below.

!

!

Содержание VR8404

Страница 1: ...e drop 37 3 MJ meter3 0 64 specific gravity natural gas at 0 25 kPa pressure drop Use conversion factors in Table 1 to convert capacities for other gases TABLE 1 GAS CAPACITY CONVERSION FACTORS Gas Specific Gravity Multiply Listed Capacity By Manufactured 0 60 0 516 Mixed 0 70 0 765 Propane 1 53 1 62 ELECTRICAL RATINGS Voltage and Frequency 24 Vac 60 Hz 50 60 Hz models available on request Current...

Страница 2: ...Teflon tape 3 Insert bushing in entire gas control and thread pipe carefully into bushing until tight CHOOSE GAS CONTROL LOCATION Locate the gas control in the appliance vestibule on the gas manifold In replacement applications locate the entire gas control in the same location as the old gas control Do not locate the entire gas control where it can be affected by steam cleaning high humidity drip...

Страница 3: ...mpound resis tant to LP gas Refer to Fig 2 5 Remove seals over gas control inlet and outlet if necessary 6 Connect pipe to gas control inlet and outlet Use a wrench on the manifold rather than on the gas control Refer to Figs 3 and 4 Fig 2 Use moderate amount of pipe compound Pipe Size Thread Pipe This Amount Maximum Depth Pipe Can Be Inserted Into Control 3 4 13 16 3 4 1 1 1 16 1 Fig 3 Top view o...

Страница 4: ...f available or use the general instructions provided Fig 5 Always use new compression fitting Fig 6 VR8404 wiring connections in intermittent ignition system with S86 24V 2 24V 1 GND S86F H S860D MV MV MV PV MV PV PV PV GND BURNER 4 1 1 1 2 3 4 2 3 3 L1 HOT L1 HOT L2 L2 THERMOSTAT OR CONTROLLER LIMIT CONTROLLER VR8404 GAS CONTROL PILOT BURNER GROUND PILOT GAS SUPPLY Q345 Q364 Q348 Q362 Q381 PILOT ...

Страница 5: ...as control knobs will not operate by hand call a qualified service technician to replace the entire gas control 3 Both knobs must be in the same position for operation or shutoff GAS CONTROL KNOBS SETTINGS The gas control knobs have two settings OFF Prevents pilot and main burner gas flow ON Permits gas to flow into the control body Under control of the thermostat and intermittent pilot module gas...

Страница 6: ...the appliance being checked Makecertainthatotherappliancesareturned off with pilot burners extinguished or de duct that gas consumption from the meter reading Convert the flow rate to Btuh as described in the Gas Controls Handbook form 70 2602 and compare to the Btuh input rating on the appliance nameplate Standard Opening and Slow Opening Pressure Regulator 1 The gas control outlet pressure shoul...

Страница 7: ... INJURY OR DEATH Do not disassemble the gas control or either valve They contain no replaceable components Attempted disassembly or repair can damage the gas control Regular preventive maintenance is important in applica tions such as commercial cooking agricultural and indus trial operations that place a heavy load on system controls because In many such applications particularly commercial cooki...

Страница 8: ...sion 5 Call a qualified service technician to replace the entire gas control if it has been flooded with water 6 Replace the entire gas control in the event of any physical damage tampering bent termi nals missing or broken parts stripped threads or evidence of exposure to heat IMPORTANT Follow the operating instructions pro vided by the manufacturer of your heating appliance The information below...

Отзывы: