Honeywell VR8215 Series Скачать руководство пользователя страница 6

VR8215S,T DIRECT IGNITION COMBINATION GAS CONTROLS

69-2253—01

6

Check and Adjust Gas Input 

and Burner Ignition

IMPORTANT

1. Do not exceed input rating stamped on 

appliance nameplate, or manufacturer’s 
recommended burner orifice pressure for size 
orifice(s) used. Make certain primary air supply 
to main burner is properly adjusted for complete 
combustion. Follow appliance manufacturer 
instructions.

2. IF CHECKING GAS INPUT BY CLOCKING GAS 

METER: Make certain there is no gas flow 
through the meter other than to the appliance 
being checked. Other appliances must remain 
off with the pilots extinguished (or deduct their 
consumption from the meter reading). Convert 
flow rate to Btuh as described in form 70-2602, 
Gas Controls Handbook, and compare to Btuh 
input rating on appliance nameplate.

3. IF CHECKING GAS INPUT WITH 

MANOMETER: Make sure the gas control is in 
the OFF position before removing outlet 
pressure tap plug to connect manometer 
(pressure gauge). Also move the gas control 
switch back to the OFF position when removing 
the gauge and replacing the plug. Before 
removing inlet pressure tap plug, shut off gas 
supply at the manual valve in the gas piping to 
the appliance or, for LP, at the tank. Also shut off 
gas supply before disconnecting manometer and 
replacing plug. Repeat Gas Leak Test at plug 
with main burner operating.

NOTE: Check the inlet pressure before adjusting the 

pressure regulator.

Standard and Slow-Opening (S and T) Models 

1.

Carefully check the main burner lightoff. Make sure 
that the main burner lights smoothly and that all 
ports remain lit.

2.

Check the full rate manifold pressure listed on the 
appliance nameplate. Gas control full rate outlet 
pressure should match this rating.

3.

With main burner operating, check the control flow 
rate using the meter clocking method or check 
pressure using a manometer connected to the 
outlet pressure tap on the control. See Fig. 6.

4.

If necessary, adjust the pressure regulator to match 
the appliance rating. See Tables 6 and 7 for factory-
set nominal outlet pressure and adjustment range.
a. Remove the pressure regulator adjustment cap 

screw.

b. Using a screwdriver, turn the inner adjustment 

screw (Fig. 6) clockwise 

 to increase or

counterclockwise 

 to decrease the gas 

pressure to the burner.

c. Always replace the cap screw and tighten firmly 

to prevent gas leakage.

5.

If the desired outlet pressure or flow rate cannot be 
achieved by adjusting the gas control, check the 
gas control inlet pressure using a manometer at the 
inlet pressure tap of the gas control. If the inlet 
pressure is in the nominal range (see Tables 6 and 
7), replace the gas control. Otherwise, take the 
necessary steps to provide proper gas pressure to 
the control.

Check Safety Lockout 

(Slow-Opening Controls Only)

1.

With the system power off and the thermostat set to 
call for heat, manually shut off the gas supply.

2.

Energize ignition control and start timing safety 
lockout time. When spark ignition terminates, stop 
timing.

NOTE: When using the VR8215T, the specified 

ignition control safety lockout time must 
exceed 8.5 seconds for the system to 
function properly.

3.

After spark cutoff, manually reopen the gas control 
switch. No gas should flow to the main burner.

4.

Reset the system by adjusting the thermostat below 
room temperature, wait 30 seconds, and then move 
the thermostat setting up to call for heat. Normal 
ignition should occur.

Table 6.  Pressure Regulator Specification 

Pressures (in. wc).

Check Safety Shutdown Performance

WARNING

Fire or Explosion Hazard.
Can cause property damage, severe injury 
or death.

Perform the safety shutdown test any time work is 
done on a gas system.

NOTE: Read steps 1 through 7 before starting, and 

compare to the safety shutdown or safety 
lockout tests recommended for the direct ignition 
(DI) module. Where different, use the procedure 
recommended for the ignition module.

1.

Turn off gas supply.

2.

Set thermostat or controller above room 
temperature to call for heat.

3.

Watch for ignition spark or for glow at hot surface 
igniter either immediately or following prepurge. 
See Direct Ignition module specifications.

4.

Time the length of spark operation. See the Direct 
Ignition module specifications.

5.

After the module locks out, open the manual gas 
cock and make sure no gas is flowing to the main 
burner. 

6.

Set the thermostat below room temperature and 
wait one minute.

7.

Operate system through one complete cycle to 
make sure all controls operate properly.

Model 

Type

Type of 

Gas

Nominal 

Inlet 

Pressure 

Range

Factory Set 

Nominal 

Outlet 

Pressure

Setting 

Range

Standard, 
Slow

NAT

5.0-7.0

3.5

2.5-3.5

LP

12.0-14.0 10.0

8.0-12.0

Содержание VR8215 Series

Страница 1: ... Body Pattern Straight through see Table 1 for inlet and outlet size Electrical Ratings Voltage and Frequency 24 Vac 60 Hz Current Draw 0 5A Capacity See Table 1 Conversion Use conversion factors in Table 2 to convert capacities for other gases Regulation Range See Table 1 Natural LP Gas Conversion Kits See Table 4 Approvals CSA Design Certificate Table 4 Natural LP Gas Conversion Kits Model Size ...

Страница 2: ...system Corrosive Chemicals Corrosive chemicals can attack the control eventually causing a failure If chemicals are used for routine cleaning avoid contact with the control Where chemicals are suspended in air as in some industrial or agricultural applications protect the control with an enclosure Dust or Grease Accumulation Heavy accumulations of dust or grease can cause the control to malfunctio...

Страница 3: ...lacement application mount the gas control in the same location as the old control Locate the combination gas control where it cannot be affected by steam cleaning high humidity or dripping water corrosive chemicals dust or grease accumulation or excessive heat To assure proper operation follow these guidelines Locate gas control in a well ventilated area Mount gas control high enough above cabine...

Страница 4: ...gas control and make sure it matches the available supply Install a transformer and other controls as required 2 Connect the control circuit to the gas control terminals See Fig 7 and 8 3 Adjust thermostat heat anticipator to 0 50A rating stamped on valve label GAS CONTROL GAS CONTROL HORIZONTAL DROP PIPED GAS SUPPLY PIPED GAS SUPPLY 3 IN 76 MM MINIMUM 3 IN 76 MM MINIMUM RISER GAS CONTROL TUBING G...

Страница 5: ...k in the appliance vestibule 4 With the main burner in operation paint the pipe joints including bushings and the control inlet and outlet with rich soap and water solution 5 If another leak is detected turn the gas control to off tighten the joints and pipe connections 6 Replace the part if a leak cannot be stopped Turn On System Push the on off switch to the ON position Turn On Main Burner Follo...

Страница 6: ...ounterclockwise to decrease the gas pressure to the burner c Always replace the cap screw and tighten firmly to prevent gas leakage 5 If the desired outlet pressure or flow rate cannot be achieved by adjusting the gas control check the gas control inlet pressure using a manometer at the inlet pressure tap of the gas control If the inlet pressure is in the nominal range see Tables 6 and 7 replace t...

Страница 7: ... as if it has been wet SERVICE WARNING Fire or Explosion Hazard Can cause property damage severe injury or death Do not disassemble the gas control it contains no replaceable components Attempted disassembly repair or cleaning can damage the control resulting in gas leakage CAUTION Equipment Damage Hazard Can burn out thermostats or other components in the control string Never apply a jumper acros...

Страница 8: ...n your appliance 4 Push the on off switch to the OFF position 5 Wait five minutes to allow any gas in the combustion chamber to vent Then if you smell gas STOP Follow Step 1 in the Warning above If you do not smell gas continue with the next step 6 If you do not smell gas push the electronic on off switch to the ON position 7 Replace the burner access panel 8 Reset the thermostat to the desired te...

Отзывы: