Honeywell VR4300 Скачать руководство пользователя страница 8

8

!

Maintenance

WARNING

FIRE OR EXPLOSION HAZARD CAN
CAUSE PROPERTY DAMAGE, SEVERE
INJURY, OR DEATH

Improper cleaning or reassembly may cause gas
leakage. When cleaning, assure that control is
reassembled properly and perform gas leak test.

Regular preventive maintenance is important in appli-

cations that place a heavy load on system controls, such as
in the commercial cooking and agricultural and industrial
industries because:

• In many such applications, particularly commercial

cooking, the equipment operates 100,000-200,000
cycles per year. Such heavy cycling can wear out the
gas control in one to two years.

• Exposure to water, dirt, chemicals and heat can

damage the gas control and shut down the control
system.

The maintenance program should include regular check-

out of the gas control as described in the Start-up and
Checkout section, and the control system as described in
the appliance manufacturer’s literature.

Maintenance frequency must be determined individu-

ally for each application. Some considerations are:

Cycling frequency

. Appliances that may cycle

100,000 times annually should be checked monthly.

Intermittent use

. Appliances that are used seasonally

should be checked before shutdown and again before
the next use.

Consequence of unexpected shutdown.

 Where the

cost of an unexpected shutdown would be high, the
system should be checked more often.

Dusty, wet, or corrosive environment

. Since these

environments can cause the gas control to deteriorate
more rapidly, the system should be checked more
often.

The gas control should be replaced if:
• It does not perform properly during checkout or

troubleshooting.

• The gas control knob is hard to turn or push down, or

it fails to pop back up when released.

• The gas control is likely to have operated for more

than 200,000 cycles.

!

Service

WARNING

FIRE OR EXPLOSION HAZARD CAN
CAUSE PROPERTY DAMAGE, SEVERE
INJURY OR DEATH

Do not disassemble the gas control; it contains no
replaceable components. Attempted disassembly
or repair may damage the gas control.

!

CAUTION

Do not apply a jumper across or short the valve
coil terminals. This may burn out the heat antici-
pator in the thermostat.

IMPORTANT: Allow 60 seconds after shutdown before

re-energizing step-opening model to assure lightoff
at step pressure.

IF THE PILOT BURNER FLAME WILL NOT LIGHT

1. Assure the main gas supply valve is open and the

pilot gas supply line is purged of air.

2. Attempt to light pilot burner flame following proce-

dures in Light the Pilot Burner Flame, page 6. If pilot
burner flame still will not light:

a. Check the pilot gas adjustment screw. If closed,

readjust the pilot flame.

b. Perform the Gas Leak Test at the compression fit-

ting. If a gas leak is detected, replace the old com-
pression fitting or tighten the newly installed one.
Refer to Fig. 4.

c. Assure that the pilot burner tubing or pilot burner

orifice is not clogged.

IF THE PILOT BURNER FLAME GOES OUT WHEN
THE GAS CONTROL KNOB IS RELEASED

1. Assure the gas control knob is held in at least one

minute to allow the thermocouple time to heat.

2. Check the pilot burner flame adjustment. Refer to

Adjust the Pilot Burner Flame, page 6.

3. Check the wiring between the thermocouple and the

gas control valve operator.

4. Assure thermocouple connection to the power unit is

tightened one-fourth turn beyond finger tight.

5. If pilot burner flame still goes out, measure the open

and closed thermocouple output voltage. Compare it to the
acceptable range charts in the thermocouple specifications
or in the Gas Controls Handbook. Replace the thermo-
couple if voltages are outside the acceptable range.

6. Check the power unit resistance. If above 11 ohms,

replace the gas control.

IF THE MAIN BURNER WILL NOT COME ON
WITH A CALL FOR HEAT

1. Assure the gas control knob is in the ON position.
2. Adjust the thermostat several degrees above room

temperature.

3. Use an ac voltmeter to measure the voltage across

terminals L1 and L2:

a. If no voltage is present, check the control circuit for

proper operation.

b. If voltage is present, but first operator did not 

click

open, check for excessive inlet gas pressure. If inlet
gas pressure is correct, replace the gas control.

4. Measure the open and closed thermocouple output

voltages and compare to the acceptable range charts in the
thermocouple specifications or in the Gas Controls Hand-
book. Replace the thermocouple if voltages are outside the
acceptable range.

IF THE MAIN BURNER IS OVERFIRING

Adjust the gas control pressure regulator to the correct

pressure. If the regulator cannot be adjusted and supply
pressure is in the normal range, replace the gas control.

Содержание VR4300

Страница 1: ...ontinuous pilot gas controls are used in gas fired applianceswithcapacitiesupto300feet3 houratoneinchwc pressure drop 5 7 meters3 hour at 0 25 kPa on natural gas They include a manual valve safety shutoff two automatic operators a pressure regulator pilot adjustment and a con duit cover See Table 1 for temperature ranges and regulator types BODY PATTERN Straight through body pattern INLET X OUTLET...

Страница 2: ...gascontrolsetfornaturalgasonLPgas or a gas control set for LP gas on natural gas To convert a gas control from natural gas to LP gas or from LP gas to natural gas contact your Honeywell representative Convert standard or slow opening gas controls from one gas to another with a conversion kit ordered sepa rately Order part number 393691 to convert from natural to LP gas Order part number 394588 to ...

Страница 3: ...as Control 1 Mount the gas control 0 90 degrees in any direction including vertically from the upright position of the gas control knob 2 Mount the gas control so gas flow is in the direction of the arrow on the bottom of the gas control 3 Thread pipe the amount shown in Table 4 for inser tion into gas control Do not thread pipe too far Valve distortion or malfunction may result if the pipe is ins...

Страница 4: ...ply before making wiring con nections to prevent electrical shock or equipment damage 1 Checkthepowersupplyratingonthegascontroland assure it matches the available supply Install thermostat and other controls as required 2 When the gas control is installed external to the appliance install the conduit cover on the conduit fitting Do not secure conduit cover at this time 3 Connect control circuit t...

Страница 5: ...Inches Meters Inches Meters Inches Meters 12 0 3 47 1 2 30 0 8 18 0 5 18 0 5 41 1 0 26 0 7 16 0 4 24 0 6 35 0 9 22 0 6 14 0 4 30 0 8 29 0 8 18 0 5 11 0 3 36 0 9 23 0 6 15 0 4 9 0 2 40 1 0 19 0 5 12 0 3 7 0 2 48 1 2 11 0 3 7 0 2 60 1 5 Do not use Fig 7 Installing thermocouple to the power unit Fig 8 Wiring connections for 120 volt control 5 69 0683 1 120V THERMOSTAT POWER SUPPLY PROVIDE DISCONNECT ...

Страница 6: ...ascontrolknobdownaboutoneminute then release If the pilot flame goes out turn the gas control knob clockwise to OFF and repeat steps 1 through 3 If pilot flame remains lit turn the gas control knob counterclockwise to ON ADJUST THE PILOT BURNER FLAME The pilot flame should envelop 3 8 to 1 2 inch 10 to 13 millimeters of the thermocouple tip Refer to Fig 9 To adjust the pilot flame 1 Remove the pil...

Страница 7: ...er operation 4 If desired outlet pressure or flow rate cannot be achieved by adjusting the gas control check the inlet pressure using a manometer at inlet pressure tap or up stream of the gas control If the inlet pressure is in the normalrange refertoTable7or8 replacetheexistinggas control Otherwise take the necessary steps to provide proper gas pressure to the gas control 5 Carefully check main b...

Страница 8: ...e energizing step opening model to assure lightoff at step pressure IFTHEPILOTBURNERFLAMEWILLNOTLIGHT 1 Assure the main gas supply valve is open and the pilot gas supply line is purged of air 2 Attempt to light pilot burner flame following proce dures in Light the Pilot Burner Flame page 6 If pilot burner flame still will not light a Check the pilot gas adjustment screw If closed readjust the pilo...

Страница 9: ...c power to the appliance 3 Remove the gas control access panel 4 Push in the gas control knob slightly and turn clock wise to OFF NOTE The gas control knob cannot be turned from PILOT to OFF unless it is pushed in slightly Do not force the gas control knob 5 Wait five minutes to clear out any unburned gas If you then smell gas STOP Follow step 3 in the Warnings above If you do not smell gas contin...

Страница 10: ...nd Building Control Helping You Control Your World Honeywell Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 740 Ellesmere Road Golden Valley Minnesota 55422 Scarborough Ontario M1P 2V9 QUALITY IS KEY Printed in U S A ...

Отзывы: