Actuators and Final Control Elements
70-6925
139
H
u
m
idi
st
at
s
an
d
Th
er
m
o
st
at
s
Controller
s
Sensors
Relay
s
Switch
es
Actuators
Va
lv
e
s
Ac
ces
sor
ie
s
En
gi
ne
eri
ng
Gu
ide
Cr
o
s
s
Refere
nc
e
In a double-seated valve (Fig. 29), the controlled agent flows
between the two seats. This placement balances the inlet
pressures between the two discs of the plug assembly and
reduces the actuator force needed to position the plug
assembly. Double-seated valves generally do not provide tight
close-off because one disc may seat before the other and
prevent the other disc from seating tightly.
Fig. 29. Double-Seated Valve.
Figure 30 shows three-way globe valve assemblies. The mixing
valve has two inlets and a common outlet. The diverting valve
has a common inlet and two outlets.
Three-way valves may be piped to be normally open or
normally closed to the heating or cooling load. If a three-way
valve has linear characteristics and the pressure differentials
are equal, constant total flow is maintained through the
common inlet or outlet port.
Fig. 30. Three-Way Valve Assemblies.
BRANCH
LINE
INLET
FLOW
OUTLET
FLOW
C2612
NORMALLY OPEN VALVE
F3
F2
F1
BRANCH
LINE
F1
INLET
FLOW
INLET FLOW
OUTLET FLOW
OUTLET
FLOW
C2615
F2
MIXING VALVE, NORMALLY CLOSED TO
STRAIGHT-THROUGH FLOW
BRANCH
LINE
F1
INLET
FLOW
OUTLET
FLOW
F2
DIVERTING VALVE, NORMALLY OPEN TO
STRAIGHT-THROUGH FLOW