 B SEQUENCING WATER VALVE

REPAIR

Equipment Required

Valve Seat Removal Tool (available from Memphis
Service Center):

 CCT3843   for 

 0. D. copper tubing 

in nominal) valve size

 CCT3833 -for 

 and 

 O.D. copper

tubing 

 and 

 nominal) valve sizes

14002734-001 Lubricant for stem, packing, and

packing nut
Lead Seal Number 2) or Crain packing of Teflon tape

for bonnet threads.

Diaphragm Replacement

Refer to Figure 3 and Table 3 while performing this
procedure.

Shut off air supply to VP522.
Disconnect air piping at actuator assembly.
Disengage slide from stem button.

Loosen the two socket head screws securing the

actuator assembly to the valve bonnet, and lift off
actuator assembly.

  WARNING

The actuator is spring loaded via the large coil spring.
To avoid personal injury, carefully loosen the two
filister head screws from the spider base. Alternate a
few turns at a time while firmly holding the spider base
down against the spider.

Turn actuator upside down on a flat surface and
disassemble to remove spring load.
Turn actuator back over and remove top and
diaphragm.

Inspect diaphragm cup at this time. If the cup is badly

corroded, replace it.

Reassemble actuator assembly in reverse order with
new diaphragm.
Replace the actuator assembly on the valve bonnet and

tighten the two socket head screws.

Engage slide on the stem button.
Reconnect air piping.

Turn air supply back on.

Packing Replacement

Refer to Figure 3 and Table 3 while performing this

procedure.

 Shut off air supply to VP522.
 Remove actuator assembly as outlined in Steps 1

through 4 of DIAPHRAGM REPLACEMENT.

Remove the stem button and slide the brass tube off of

the stem and disc holder assembly. A hole is provided

near the top of the stem for insertion of an awl, nail, or
similar tool to hold the stem while removing or replacing

the stem button.

Remove packing nut.
Remove packing discs (3) and packing followers from

packing nut. Retain both packing followers. Discard old
packing.
Remove packing spring from valve bonnet.
Clean out packing nut and packing spring with a
commercial solvent degreaser.

Use solvents in a well ventilated area. Avoid
prolonged inhalation of solvents or contact with the

skin. Careless handling of solvents can cause
permanent injury to the respiratory system and
skin tissue.

Inspect the spring and replace if necessary.
Inspect the valve stem for scratches or abrasions, and
replace if necessary. See STEM AND DISC HOLDER
REBUILD KIT.

Lubricate packing spring, stem, and new packing.
Assemble packing discs (cup down) and previously
removed packing followers (bevel up) in the proper

sequence.

Slide packing spring over stem into valve bonnet.
Carefully screw packing disc and spring follower

“sandwich” over stem threads.
Apply light coating of lead seal or two wraps of Teflon
tape to bonnet threads.

Install packing nut, brass tube, and stem button.
Install actuator assembly on valve body and secure.
Restore system to operation.

Stem and Disc Holder Rebuild Kit

NOTE: When ordering a replacement stem and disc holder

rebuild kit listed in Table 4, a new brass tube, stem
button, setscrew, and three packing discs are also
included. When replacing the stem and disc holder

assembly, the other parts included should also be

replaced.

Refer to Figure 3 and Tables 3 and 4 while performing this
procedure.

Shut off air supply to the VP522.

Remove actuator assembly as outlined in Steps 1

through 4 of DIAPHRAGM REPLACEMENT. Remove
packing discs and packing followers as in Steps 2 and
3 of the PACKING REPLACEMENT section.

Remove valve bonnet for access to upper valve seat.
Inspect and replace the upper seat, if necessary, using

the required valve seat removal tool.
While the valve is open, check the integral lower seat in
the valve body for wear and clean out any foreign
matter that may be in the valve body. If the lower seat is
bad, replace the entire valve assembly.

Install the new stem and disc holder assembly and/or
upper seat.
Reassemble other parts in reverse order.

Содержание VP522A

Страница 1: ...ortioning valve that controls the flow of first hot and then cold water to a fan coil unit as branchline pressure increases and the reverse as branchline pressure decreases No flow occurs at mid pressure See Table 1for operating sequence The VP522B diverts the return water from the coil directly to return piping of the system feeding the coil During the dwell period of the VP522A when both ports a...

Страница 2: ...pens Cold port open 100 Specifications See Table 2 for VP522 model number size capacity index and close off rating Table 2 VP522 Specifications Not available for replacement Use valve with different nominal pipe size and same capacity index T Not available for replacement Use valve with different capacity index 5 Rating will maintain closure against 15 psi 103 kPa difference in return line pressur...

Страница 3: ...ome into contact with the diaphragm as it will cause serious damage 0 0 Adjust the system temperature controller through its control range The valve should operate to control the flow of water as required to provide heating or cooling when both hot and chilled water are available Make sure the branchline pressure builds up to near full main pressure when controller is set at the extreme end of the...

Страница 4: ...LACE DIAPHRAGM MAKE OPERATIONAL CHECK I YES CHECK SYSTEM Pr PRESSURES DISASSEMBLE VALVE AND INSPECT FOR FOREIGN MATERIAL OR BLOCKED PORTS CHECK FOR BROKEN PARTS CLEAN AND I REPLACE AS NECESSARY I DISASSEMBLE VALVE REPLACE WORN SEATS AND PLUGS REPLACE VALVE IF LOWER SEAT IS DEFECTIVE 1 YES DISASSEMBLE VALVE INSPECT FOR FOREIGN MATERIAL OR BENT STEM CLEAN OR REPLACE STEM AND LUBRICATE IRESTORE VALVE...

Страница 5: ...followers from packing nut Retain both packing followers Discard old packing Remove packing spring from valve bonnet Clean out packing nut and packing spring with a commercial solvent degreaser AWARNING Use solvents in a well ventilated area Avoid prolonged inhalation of solvents or contact with the skin Careless handling of solvents can cause permanent injury to the respiratory system and skin ti...

Страница 6: ...VP522A and B Parts List See Fig 3 Fig Key No Part No Description 2 3 4 4 5 6 7 a 9 10 10 10 10 11 12 13 14 15 16 17 17 1 8 19 20 21 22 23 23 314456 23 314462 24 See Table 4 Stem and Disc Holder Assembly 25 Valve Body 312760 309 zlo4 313816 00063 314436 00065 315412 315413 314460 315409 310143 310137 310135 313825 Screw 8 32 x 1 2 in slot head 4 Lockwasher No 4 4 Actuator top Diaphragm 1 Diaphragm ...

Страница 7: ...E ACTUATOR ASSEMBLY 312817L ALL A MODELS EXCEPT Al 039 A1047 AND Al237 312817S FOR A1039 A1047 AND Al237 MODELa 312817W FOR 81003 MODELS 312817Y FOR B1011 AND B1029 MODELS X2053 1 Fig 3 VP522A and B Exploded View SeeTable 3 75 2598 ...

Страница 8: ...me and Building Control Honeywell Inc Honeywell Limited Honeywell Limitee Honeywell Plaza 740 Ellesmere Road P O Box 524 Scarborough Ontario Minneapolis MN 55408 0524 MlP 2V9 Helping You Control Your World 75 2598 Rev 6 92 Printed in U S A ...

Отзывы: