B SEQUENCING WATER VALVE
Nominal Body Rating:
250 psi (1724
Water Temperature Limits:
35F (2C) min to 250F (121 C) max
Packing:
Rubber V-ring, spring loaded, self adjusting
Seats:
Brass, upper seat removable, lower seat integral
Plugs:
Brass
Disc:
Molded-in composition
Operator Diaphragm:
Molded neoprene, rolling type
Operator Maximum Safe Air Pressure:
25 psi (172
Air Connections:
Combination barb fitting for
and
(4 mm
and 6 mm) 0. D. plastic tubing
MAINTENANCE
Equipment Required
Commercial cleaning solvent degreaser
0 to 30 psi (0 to 107
pressure gage
Cleaning
Remove all dirt and grease accumulation from the underside
of the actuator and around the packing nut and stem. Use
soivent if necessary.
A
WARNING
Use solvents in a well ventilated area. Avoid
prolonged inhalation of solvents or contact with the
skin. Careless handling of solvents can cause
permanent injury to the respiratory system and skin
tissue.
CAUTION
Do not allow solvent to come into contact with the
diaphragm as it will cause serious damage.
Adjust the system temperature controller through its
control range. The valve should operate to control the
flow of water as required to provide heating or cooling
(when both hot and chilled water are available).
Make sure the branchline pressure builds up to near full
main pressure when controller is set at the extreme end
of the throttling range. With the temperature controller
set at either extreme setting, full flow should occur.
There should be no flow at mid-pressure (see Table 1).
Adjustment
Make the following adjustments after repairing the
or
Vary the branchline pressure to the inlet port on the
Note the pressure range at which no
movement (dwell) occurs.
Repeat above procedure for the
Use a screwdriver or spring adjustment wrench to
adjust the tension of the spring on the
by
turning the spring clockwise to reduce, or counter-
clockwise to increase, the switching point of no
movement. The switching point must be within the
dwell.
Operational Check
If a gage is not already present, insert a 0 to 30 psi (0
to 107
gage in the branch line.