TH8110U TOUCH SCREEN PROGRAMMABLE THERMOSTATS

69-1700

10

Table 6. Advanced Settings Menu.

Select

Installer 

Setup 

Number

Factory Setting

Other Choices

Comments

Option

Description

Options

Description

Furnace Filter 
Change 
Reminder

0500

0

Furnace filter 
change reminder 
off

1-6

1—

10 run time days                                                 

2—

30 run time days                                                    

3—

60 run time days                                                 

4—

90 run time days                                                    

5—

120 run time days                                                       

6—

365 run time days                                                     

Run time based on 
call for fan.

Humidifier Pad 
Replacement 
Reminder

0510

0

Humidifier pad 
replacement 
reminder off

1-3

1—

90 calendar days                                                                                                                        

2—

180 calendar days                                                                                                          

3—

365 calendar days                                                   

UV Lamp 
Replacement 
Reminder

0520

0

UV Lamp 
replacement 
reminder off

1

1—

365 calendar days

Adaptive 
Intelligent 
Recovery™ 

0530

1

Adaptive 

Intelligent 
Recovery™ 
control is 
activated (system 
starts early so 
setpoint is 
reached by start 
of program 
period).

0

0—

conventional 

recovery (system starts 
recovery at 
programmed time)

Number of 
Periods

0540

4

Four periods 
available (Wake, 
Leave, Return, 
Sleep)

2

Two periods availbable 
(Wake and Sleep)

Not shown in non-
programmable is 
selected. 2 or 4 
applies to all days of 
the week.

Minimum 
Compressor 
Off Time

0580

5

Five minute 
minimum off time 
for compressor

0, 2, 3, 4

Minimum number of 
minutes compressor is 
off between calls for 
compressor

 —

Heat 
Temperature 
Range Stop

0600

90

Highest heating 
setpoint.

40 to 89

Temperature range (1°F 
increments) of heating 
setpoint.

Shown in 1/2 °C.

Cool 
Temperature 
Range Stop

0610

50

Lowest cooling 
setpoint.

51 to 99

Temperature range (1°F 
increments) of cooling 
setpoint.

Shown in 1/2 °C.

Clock Format

0640

12

12-hour clock 
format

24

24-hour clock format

Extended Fan 
on time Heat

0650

0

No extended fan 
operation after 
call for heat ends

90

Fan operation is 
extended 90 seconds 
after call for heat ends.

Not shown if fan 
operation is set to 
fossil fuel or in Cool 
Only Systems

Extended Fan 
on time Cool

0660

0

No extended fan 
operation after 
call for cool ends

90

Fan operation is 
extended 90 seconds 
after call for cool ends.

 Not shown in Heat 
Only Systems.

Содержание VisionPRO TH8110U

Страница 1: ...tion 2 Check the ratings given in the instructions to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After completing installation use these instructions to check out the product operation Selecting Location Install the thermostat about 5 ft 1 5m above the floor in an area with good air circulation at average temperature See Fi...

Страница 2: ...et of terminal identifications Table 2 that corresponds with system type conventional or heat pump in Fig 3 2 Loosen the screws for the appropriate system type selected see Table 2 Insert wires in the terminal block under the loosened screw See Fig 4 3 Securely tighten each screw 4 Push excess wire back into the hole 5 Plug the hole with nonflammable insulation to prevent drafts from affecting the...

Страница 3: ...ELAY FAN RELAY R C POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED REMOVE FACTORY INSTALLED JUMPER OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR AVAILABLE ON SELECT MODELS WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE 1 1 3 2 3 OPTIONAL 24 VAC COMMON CONNECTION Y2 RC S1 R S2 W W2 Y G C 2 CONVENTIONAL M19897 OUTDOOR INDOOR TEMPERATURE SENSOR HEAT RELAY R C POWER SU...

Страница 4: ...9899 OUTDOOR INDOOR TEMPERATURE SENSOR POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED FACTORY INSTALLED JUMPER OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR AVAILABLE ON SELECT MODELS WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE 1 3 2 3 Y2 RC S1 R S2 W W2 Y G C 2 CONVENTIONAL R TR C 1 TR W B R SERIES 20 MOTOR OR VALVE M19900 OUTDOOR INDOOR TEMPERATURE SENSOR FAN...

Страница 5: ...splay is ready to enter calendar date Fig 15 Fig 15 Setting calendar and time after initial powerup IMPORTANT The tab on back of thermostat in lower left corner must be removed to activate this feature Using the Thermostat The thermostat has a touch screen interface Words or symbols appear highlighting keys as needed to complete tasks Press keys with your fingertips Sharp tips on pens or pencils c...

Страница 6: ...ering Installer Setup 1 Thermostat must be powered either with Alkaline AAA batteries or with 24 Vac Common wire 2 From the home screen press System key Press Done or Cancel key to return to home screen 3 Five blank touch keys show on the bottom of the screen between the Done and Cancel keys Press and hold the two blank keys on either side of the center blank key for approximately five seconds unt...

Страница 7: ...h 1 12 Select number that represents current calendar month Date Day 0150 15 Digit s represents current calendar date 1 31 Select number that represents current calendar date Schedule Options 0160 4 7 day programming 0 0 nonprogrammable System Type Selection 0170 1 1 Heat 1 Cool Conventional System 1 6 1 1 heat 1 cool 2 single stage heat pump no aux heat 3 heat only no fan 4 heat only with fan 5 h...

Страница 8: ...ge changes default cph for 2nd stage heat Continuous Backlight 0280 0 Backlight not on continuously Thermostat backlight comes on with each key press 1 Backlight is on continuously thermostat must have a common wire attached for this function Option is always shown however continuously on backlight works only if thermostat is wired with 24 vac Common Additional Menu Choices 0290 0 Only main menu o...

Страница 9: ... 5 F 3 C 6 6 F 3 5 C 7 7 F 4 C 8 8 F 4 5 C 9 9 F 5 C Shown only if automatic changeover is selected Temperature Indication Scale 0320 0 Temperature is displayed in F 1 Temperature is displayed in C Daylight Savings 0330 1 Daylight savings enabled United States 0 0 daylight savings is disabled Set to 0 in areas that do not follow daylight savings Remote Temperature Sensor Outdoor or Indoor 0340 0 N...

Страница 10: ... 0540 4 Four periods available Wake Leave Return Sleep 2 Two periods availbable Wake and Sleep Not shown in non programmable is selected 2 or 4 applies to all days of the week Minimum Compressor Off Time 0580 5 Five minute minimum off time for compressor 0 2 3 4 Minimum number of minutes compressor is off between calls for compressor Heat Temperature Range Stop 0600 90 Highest heating setpoint 40 ...

Страница 11: ...Standard temperature control in heating 1 3 1 less aggressive temperature control could cause temperature undershoot 3 more aggressive temperature control could cause temperature overshoot Applies to recovery ramp and use of auxiliary heat during recovery Choose 1 if getting temperature overshoot Choose 3 if getting temperature undershoot Temperature Control in Cool 0690 2 Standard temperature con...

Страница 12: ...heck for 24 Vac between C and Rc Verify AAA batteries installed correctly and good Temperature settings do not change The upper or lower temperature limits were reached Check temperature setpoints Check Installer Setup Numbers 0600 and 0610 modify The keypad is fully locked Check Installer Setup Number 0670 to change keypad lock options Heating or cooling does not come on Thermostat minimum off ti...

Отзывы: