VisionPRO
®
IAQ
5 69-1816EFS—09
0405
Ventilation fan
action
1
Ventilation on forces fan on
2
Ventilation does not force fan on
0406
Ventilation in high
humidity
1
On (heat mode only)
0 Off
0430
Ventilation lockout
0 Disabled
1
Lockout for high temperatures
**
2
Lockout for low temperatures
**
3
Lockout for high and low temperatures
**
0431
Ventilation lockout
high temperature
100 100°F (38°C): Settings 5°F apart (3°C)
[Other options: (90°F to 110°F/32°C to 43.5°C)]
0432
Ventilation lockout
low temperature
-10 -10°F (-23.5°C): Settings 5°F apart (3°C)
[Other options: (-20°F to 0°F/-29°C to -18°C)]
0450
DATS Inhibit
0
Disabled: Settings 5°F apart (3°C)
[Other options: (35°F to 65°F/1.5°C to 18.5°C)]
0500
Furnace filter
change alert
E
Auto Discover
**
7
270-day run time
0
Off
8
365-day run time
1
10-day run time
9
30 calendar days
2
30-day run time
10 60 calendar days
3
60-day run time
11 90 calendar days
4
90-day run time
12 120 calendar days
5
120-day run time
13 180 calendar days
6
180-day run time
14 365 calendar days
0502
Furnace filter
alert options
0
Timer counts Heat & Cool run time
1
Timer counts Cool run time only
0510
Humidifier pad
change alert
*
E
Auto Discover
**
0 Off
1
90 calendar days or 30 days run time
2
180 calendar days or 60 days run time
3
365 calendar days or 90 days run time
0520
UV lamp change
alert
E
Auto Discover
**
0 Off
1
365 calendar days (1 year)
2
730 calendar days (2 years)
0530
Adaptive Intelligent
Recovery™
1 On
**
0 Off
0540
Program periods
4
4 program periods
(Wake, Leave, Return, Sleep)
2
2 program periods (Wake, Sleep)
0580
Compressor off
time (min.)
5
5 minute compressor off time
**
[Other options: 0 to 4 minutes]
0600
Heat temperature
range stop
90 Max. heat temperature setting is 90°F (32°C)
[Other options: 40 to 90°F (4°C to 32°C)]
0610
Cool temperature
range stop
60 Min. cool temperature setting is 60°F (15°C)
[Other options: 60-99°F (15°C to 37°C)]
0640
Clock format
12 12-hour time (i.e., "3:30 pm")
24
24-hour time (i.e., "15:30")
0650
Extended fan
timer (heat)
0
Off
[Other options: Fan runs for 30, 60, 90 or 120 seconds after call for
heating ends]
Setup function
Settings & options (factory default in bold)
Installer setup
**See pages 6 & 7
* Humidifier Pad replacement will be displayed in the user interface as run
time days if ISU 372 is set to 1 or 3 and calendar days if ISU 372 is set to 0.